Furnace Always Building Pressure

 
ODDSNENDS4U
Member
Posts: 93
Joined: Wed. Oct. 07, 2009 6:51 pm
Location: Newtown PA Heating 5600 Sq. Ft. built in 1854

Post by ODDSNENDS4U » Wed. Oct. 07, 2009 9:49 pm

Hi,
What is the back flow valve?
What I have is this http://www.taco-hvac.com/en/products/Boiler%20Fee ... tegory=115
Thanks
Den


 
User avatar
whistlenut
Member
Posts: 3548
Joined: Sat. Mar. 17, 2007 6:29 pm
Location: Central NH, Concord area
Stoker Coal Boiler: AA130's,260's, AHS130&260's,EFM900,GJ & V-Wert
Hand Fed Coal Boiler: Franks,Itasca 415,Jensen, NYer 130,Van Wert
Hot Air Coal Stoker Furnace: Alaska, EFM, Keystoker, Yellow Flame
Hot Air Coal Stoker Stove: Alaska, Keystoker-2,Leisure Line
Hand Fed Coal Stove: Alaska, Gibraltar, Keystone,Vc Vigilant 2
Hand Fed Coal Furnace: Ford, Jensen, NYer, Van Wert,
Baseburners & Antiques: Glenwoods
Coal Size/Type: Barley, Buck, Rice ,Nut, Stove
Other Heating: Oil HWBB

Post by whistlenut » Wed. Oct. 07, 2009 10:09 pm

Even if you are on well water, you are required to install a backflow preventer on the inlet line to your boiler. Where I live, when we aren't playing the 'cow tipping' (meadow muffins) game we install a combo unit from watts that has the same type of valve you do for rapid fill and a backflow device attached that prevents any water from returning from the boiler cavity and getting into your drinking water by accident. Boiler water is not to be consumed, hence the backflow valve. Looking at the Taco you have, understand that there is the ability to adjust the inflow pressure and operate a fast fill valve by tipping the little lever straight up to bypass the preset pressure. If you have done this and thought it was OK to leave straight up, YOU LOOSE! Release the spring tension on the little lever and see if you notice any difference.

You are testing my little brain, and I know the solution is simple. We don't have any 'Pressure Regulator Czars' on-line tonight, so we may just have to make a real decision without one! OMGawd..make a decision without the input of 12500 over educated, panty wearing, shaved legged ......oops, off topic.....that was Washington, DC, not NEPA!
Pilgrim: did you have the valve lever up straight? I sure hope so, I'm old and have to go to bed, and I want you to be happy with your new-found BOILER!

 
ODDSNENDS4U
Member
Posts: 93
Joined: Wed. Oct. 07, 2009 6:51 pm
Location: Newtown PA Heating 5600 Sq. Ft. built in 1854

Post by ODDSNENDS4U » Thu. Oct. 08, 2009 7:29 am

Morning,
The lever is in the closed position. The taco has a built in back flow stopper. After work today I will take it off and see if I can clean it out.
Thanks for your help and Ill update asap.
Den

 
ODDSNENDS4U
Member
Posts: 93
Joined: Wed. Oct. 07, 2009 6:51 pm
Location: Newtown PA Heating 5600 Sq. Ft. built in 1854

Post by ODDSNENDS4U » Thu. Oct. 08, 2009 9:10 pm

Still building pressure. I took the taco valve off and took it apart and it was really gunked up with rust and sediment. I cleaned it up real good and the problem is still there. Any idea what the adjustment screw is for on the top?
Den

 
User avatar
stoker-man
Verified Business Rep.
Posts: 2071
Joined: Mon. Nov. 19, 2007 9:33 pm
Location: Lehigh Valley, PA
Hand Fed Coal Boiler: 1981 efm wcb-24 in use 365 days a year
Coal Size/Type: Anthracite/Chestnut
Other Heating: Hearthstone wood stove

Post by stoker-man » Fri. Oct. 09, 2009 6:31 am

That adjusts the pressure of the boiler. I'd set it for about 12 pounds when the boiler is cold. Did you shut off all cold water to the domestic coil. Relieve the pressure in the line by opening a hot water sink tap and let it open overnight. See if that stops the pressure buildup.

Warning:

There is one problem: If you have a pinhole leak in the coil, with the cold water supply closed and an open hot water tap, you could get boiler water in the plumbing.

 
User avatar
Sting
Member
Posts: 2983
Joined: Mon. Feb. 25, 2008 4:24 pm
Location: Lower Fox Valley = Wisconsin
Other Heating: OBSO Lennox Pulse "Air Scorcher" burning NG

Post by Sting » Fri. Oct. 09, 2009 8:17 am


**Broken Link(s) Removed**
page 5 or 6 may help you understand the contraption :lol:

 
ODDSNENDS4U
Member
Posts: 93
Joined: Wed. Oct. 07, 2009 6:51 pm
Location: Newtown PA Heating 5600 Sq. Ft. built in 1854

Post by ODDSNENDS4U » Fri. Oct. 09, 2009 2:57 pm

The Bellgosset page you sent says I should shut off the valve before the feedvalve after I get the correct pressure. I had that valve open,
Could this have been my problem?
Den


 
jim d
Member
Posts: 1271
Joined: Mon. Dec. 08, 2008 7:16 pm
Location: taunton ma
Contact:

Post by jim d » Fri. Oct. 09, 2009 3:12 pm

if you shut off the valve be fore the feed valve and it is holding and your pressure still goes up then it's not the pr valve causing your problems does it stay up all the time and continue to rise or does it go back down when the water cool s down that would be your ex tank or like stoker said it could be your coil if you shut the cold feed to the coil over nit you couldfind that out thats about all there is that could be causing that the pross of elimination will tell you

 
User avatar
Sting
Member
Posts: 2983
Joined: Mon. Feb. 25, 2008 4:24 pm
Location: Lower Fox Valley = Wisconsin
Other Heating: OBSO Lennox Pulse "Air Scorcher" burning NG

Post by Sting » Fri. Oct. 09, 2009 5:00 pm

ODDSNENDS4U wrote:The Bellgosset page you sent says I should shut off the valve before the feedvalve after I get the correct pressure. I had that valve open,
Could this have been my problem?
Den
Could be

Close the valve per your reading and see :!:

 
User avatar
whistlenut
Member
Posts: 3548
Joined: Sat. Mar. 17, 2007 6:29 pm
Location: Central NH, Concord area
Stoker Coal Boiler: AA130's,260's, AHS130&260's,EFM900,GJ & V-Wert
Hand Fed Coal Boiler: Franks,Itasca 415,Jensen, NYer 130,Van Wert
Hot Air Coal Stoker Furnace: Alaska, EFM, Keystoker, Yellow Flame
Hot Air Coal Stoker Stove: Alaska, Keystoker-2,Leisure Line
Hand Fed Coal Stove: Alaska, Gibraltar, Keystone,Vc Vigilant 2
Hand Fed Coal Furnace: Ford, Jensen, NYer, Van Wert,
Baseburners & Antiques: Glenwoods
Coal Size/Type: Barley, Buck, Rice ,Nut, Stove
Other Heating: Oil HWBB

Post by whistlenut » Fri. Oct. 09, 2009 6:27 pm

Try to make only one change at a time. Don't shut off the boiler feed and the domestic hot water at the same time. Isolate the potential problem by areas, but not all at once. If your water feed was pretty nasty, you may later want to install a water filter so at least that won't reoccur.

I am still wondering about a pinhole in the coil, but one step at a time. You must have a pressure relief valve on the hot water discharge also. Most are set at 70 to 80 psi. This is NOT the boiler PRV, it only applies to the domestic hot water discharge.

Just remember, it isn't rocket science, but it sure can be frustrating reading between the lines. :o :shock: ;)

 
User avatar
e.alleg
Member
Posts: 1285
Joined: Fri. Feb. 16, 2007 10:31 am
Location: western ny

Post by e.alleg » Sat. Oct. 10, 2009 1:28 am

How hard is it to repair a pinhole in the HW coil?

 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Sat. Oct. 10, 2009 5:44 am

e.alleg wrote:How hard is it to repair a pinhole in the HW coil?
How hard is it to repair a pinhole in the HW coil?
I've never known it to be successfully done. Even if it could be repaired, if there's one pinhole, there are 50 that are just about to leak. It's time for a new coil. That's not to say you can't try. A repair might work for a few days or a few months. Remove the coil, locate the leak, make a lead free solder repair. The problem lies in that with most coils only about 25% of the coil can be seen or reached. Every leak I've ever seen has been in a place that you couldn't solder if you wanted to.

 
ODDSNENDS4U
Member
Posts: 93
Joined: Wed. Oct. 07, 2009 6:51 pm
Location: Newtown PA Heating 5600 Sq. Ft. built in 1854

Post by ODDSNENDS4U » Sat. Oct. 10, 2009 8:33 pm

Hi,
Latest update on my pressure problem on my "boiler" . I had the valve before the feed valve turned off all night and the pressure still went up. I can tell by the bucket I have under the prv line. When I checked the pressure this morning it was at 20psi so I suppose the prv released enough to bring it down. Any way. I turned the valve back on before the feeed valve and Tonight I am going to shut the main valve to the domestic water off and see if I get water in my bucket again. I am going to open a hot water tap in my bathroom next to the boiler.
Ill update tomorrow.
Den

 
User avatar
009to090
Member
Posts: 5104
Joined: Fri. Jan. 30, 2009 10:02 am
Location: Live Oak, FL

Post by 009to090 » Sat. Oct. 10, 2009 8:36 pm

With your TPR releasing as much as it is, it wouldn't be a bad idea to replace it with a new one after you find your problem. They get weak, after they release a few times. :idea:
Last edited by 009to090 on Sat. Oct. 10, 2009 9:11 pm, edited 1 time in total.

 
ODDSNENDS4U
Member
Posts: 93
Joined: Wed. Oct. 07, 2009 6:51 pm
Location: Newtown PA Heating 5600 Sq. Ft. built in 1854

Post by ODDSNENDS4U » Sat. Oct. 10, 2009 9:07 pm

Hi,
Something else I kept forgetting to mention. We seem to be not getting hot water all the time like we used to. The wife just reminded me after her shower that she ended her shower with warm water instead of hot like it used to be. Any thoughts?
Den


Post Reply

Return to “Stoker Coal Boilers Using Anthracite (Hydronic & Steam)”