Build Up In The AA-130 Ash Cone

Re: Build Up In The AA-130 Ash Cone

PostBy: LsFarm On: Mon Feb 01, 2010 9:53 am

Measured with a probe thermometer, 18" above the boiler's breach, I see a minimum of 450*, usually 500-550* for each burn. My differential is set at max, it is around 22-25*. So the boiler works a little each time it fires. Otherwise, the Anthrastat won't cool enough from incoming air to make a circuit and allow ashing. Without ashing, the fire gets too shallow. So I leave my differential so that the boiler runs and works for awhile each time it fires.

If I see only 400*, I have either a shallow fire, a big clinker or it just spit out a clinker and the fire dropped dramaticly, leaving a very deep layer of fresh coal.

Greg L
Burning Pea/Buckwheat through an antique stoker [semi retired SSboiler],
Running an Axeman-Anderson 260M boiler burning Pea, About 150-250#per day
Farming, Fixing, Fabricating and Flying: 'spare time' what's that?
User avatar
LsFarm
Site Moderator
 
Posts: 5619
Joined: Sun Nov 20, 2005 9:02 pm
Location: Michigan
Stove/Furnace Make: Axeman Anderson and Custom
Stove/Furnace Model: Boilers: AA 260M, BBertha 250K


Re: Build Up In The AA-130 Ash Cone

PostBy: brckwlt On: Mon Feb 01, 2010 10:26 am

HOW and WHAT can i reseal the ash cone with?

Im pretty sure that is my problem. I do have lots of unburnt coal this morning and the fire is not burning much at all on the left side of the boiler where the ash cone would be.

Last night i let the fire die out and completely removed all coal and ashes from the boiler and had no clinkers to speak of. All of this started when i cleaned the ash cone saturday night. If i did not mention when i cleaned the ash cone, i used a wire to get the fly ash out and also tapped it with a small wrench. :oops: :doh:


Freddy wrote:Are you still burning hundreds of pounds a day? maybe once a week will my exhaust temp get over 400 degrees, whereas you seem to be above that most of the time.


Yea i am, when its cold here like say a hi of 25 lo of 10 i burn about 170 lbs a day. When its more mild like high 50 and lo 35-40 i might burn around 100 lbs a day
burning pea coal from harmony mine, picked up in my 2002 Pontiac "Coalfire"
User avatar
brckwlt
Member
 
Posts: 2925
Joined: Tue Jan 27, 2009 9:32 pm
Location: Sunbury, PA
Stove/Furnace Make: Axeman-Anderson
Stove/Furnace Model: Rebuilt 1953 AA-130

Re: Build Up In The AA-130 Ash Cone

PostBy: coaledsweat On: Mon Feb 01, 2010 10:34 am

I'm not sure the cone needs a seal as mine wasn't, anyone know the deal on that?
http://fossil.energy.gov/education/ener ... entary.pdf
Nothing is impossible for people who don't have to do it themselves.
User avatar
coaledsweat
Site Moderator
 
Posts: 5059
Joined: Fri Oct 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stove/Furnace Make: STEEL KING hand fired boiler
Stove/Furnace Model: Axeman-Anderson 260M

Re: Build Up In The AA-130 Ash Cone

PostBy: brckwlt On: Mon Feb 01, 2010 1:45 pm

I called Matthaus and he told me to seal the ash cone with high temp trv. So i have to let the fire die out and take off the chimney pipe and seal it from the top of the boiler looking down to the bottom of the ash cone. Hopefully this fixes my problem or else i will be really confused.
burning pea coal from harmony mine, picked up in my 2002 Pontiac "Coalfire"
User avatar
brckwlt
Member
 
Posts: 2925
Joined: Tue Jan 27, 2009 9:32 pm
Location: Sunbury, PA
Stove/Furnace Make: Axeman-Anderson
Stove/Furnace Model: Rebuilt 1953 AA-130

Re: Build Up In The AA-130 Ash Cone

PostBy: Bob On: Mon Feb 01, 2010 4:52 pm

brckwlt wrote:Could i of possibly messed up my ash cone last night when i was cleaning it out? or wouldnt that cause the problem i am experiencing right now?


My experience is with the AHS 130 but I think the cone is similar. The opening in the bottomof the cone in my boiler is about 1/2" diameter. There is no way the chips the size you have shown could come through the cone on my boiler. I am wondering if those chips are pieces of the cone and that you need to replace the cone.
Bob
Member
 
Posts: 206
Joined: Sun Mar 18, 2007 11:28 am
Location: Schuylkill County
Stove/Furnace Make: AHS 130

Re: Build Up In The AA-130 Ash Cone

PostBy: LsFarm On: Mon Feb 01, 2010 5:38 pm

Remove your ash pan, lie down on your back, stick your head in where the ashpan sits. use a small flashlight and a mirror if needed and look at the outer diameter of the ash cone.. where the cone's larger diameter touches the 'cyclone' tube or wall. This gap must be sealed with either furnace cement, or HiTemp silicone caulk/glue.. I tried silicone first, but either there was some coating on the steel, maybe a layer of fiyash that didn't brush off, or maybe it got too hot, but the silicone peeled off.

So the second time, I used a piece of door gasket, the rope type stuff, and wearing rubber gloves, put a fat bead of furnace cement from a caulking gun under the lip of the cone, and using the doorseal rope, pushed the rope and caulk up till it jammed in the narrowing gap. I then smeared more furnace cement over the rope with my fingers.. So the gap is filled with a piece of rope packed in with furnace cement as a glue/sealant.

If the cone has disintegrated, Axeman keeps them in stock, and can ship one out to you quickly.. But you need to seal the new one in the cyclone tube as well, it must be sealed.. if not you are getting way too much oxygen-depleted air sucked back into the coal fire, and this causes unburnt coal.

Greg L
Burning Pea/Buckwheat through an antique stoker [semi retired SSboiler],
Running an Axeman-Anderson 260M boiler burning Pea, About 150-250#per day
Farming, Fixing, Fabricating and Flying: 'spare time' what's that?
User avatar
LsFarm
Site Moderator
 
Posts: 5619
Joined: Sun Nov 20, 2005 9:02 pm
Location: Michigan
Stove/Furnace Make: Axeman Anderson and Custom
Stove/Furnace Model: Boilers: AA 260M, BBertha 250K

Re: Build Up In The AA-130 Ash Cone

PostBy: Freddy On: Tue Feb 02, 2010 5:30 am

Bob wrote:My experience is with the AHS 130 but I think the cone is similar.


I have a friend with the AHS 130. The cone is the same size as my AA, but you are right, the hole in the bottom of the AHS is smaller. Not say if one is better than the other. It's just the way they are.

My AA wwill hit 450 every now & then....if it's been just idlling along, then get's a big call for heat, it'll run a good long time & get that high. Most of the time it stays lower, but let's say it's been sunny all day...it's hardly run at all, then in the evening laundry is done, showers are taken, the house calls for heat, it'll run good & hard & get up to 425-450. I've never seen it over 450 though.
Orrington, Maine
Fred
User avatar
Freddy
State of Maine Moderator
 
Posts: 3493
Joined: Fri Apr 11, 2008 2:54 pm
Location: Orrington, Maine
Stove/Furnace Make: Axeman Anderson up and running
Stove/Furnace Model: 130

Re: Build Up In The AA-130 Ash Cone

PostBy: brckwlt On: Tue Feb 02, 2010 3:57 pm

Yesterday i shut down the boiler around 10am to let the fire die out so i could re seal the ash cone. During that time, once the fire was out i completely took apart the flu pipe and re did it according to the aa manual. When i had my boiler installed last October i told the plumber to follow the diagram in the manual and when i came home from work he had all six inch from the boiler to the chimney. So i took all of that out and started with five inch coming off of the boiler and ran that into the T where have two baro's then ran six inch from the baro's to the chimney. That was something i wanted down since day one. Needless to say this little project took me longer then i thought it would, i have never done this before but i figure i can pretty much do anything if i just try it. It might not be the prettiest job in the world, but at least i did it myself.

So back to the ash cone. When i took apart the old flu pipe i looked down into the opening where the ash cone is and noticed there was nothing sealing the ash cone. there were so big gaps around it. So i sealed it from the top (as Matthaus told me to) and then i also sealed it from the bottom. the ash cone itself appeared to have no damage to it and seemed fine to me.

The boiler was down for about 24 hours and in that time the house went from 71 to 48. I lost 23 degrees in 24 hours. Is that a lot to loose over 24 hours. outside temps were as high as 30 and as low as 20. When i refired the boiler this morning at 10am the house was 48 like i mentioned and in the last 5 hours the temp is up to 66 degrees. So i was able to heat the house 18 degrees so far in 5 hours. This seems pretty good to me since i have 17 rads and miles of 2 1/2 inch pipe in the basement.

Since the re fire i am not having any problems with getting a fire the whole way across the burn pot. and i have also noticed that i am not getting quite as hot of flu temps as i use to. sometimes i would get close to 540 or 550 on long runs. Now after 5 hours it is about 480.
burning pea coal from harmony mine, picked up in my 2002 Pontiac "Coalfire"
User avatar
brckwlt
Member
 
Posts: 2925
Joined: Tue Jan 27, 2009 9:32 pm
Location: Sunbury, PA
Stove/Furnace Make: Axeman-Anderson
Stove/Furnace Model: Rebuilt 1953 AA-130

Re: Build Up In The AA-130 Ash Cone

PostBy: LsFarm On: Tue Feb 02, 2010 5:21 pm

I'd say the difference in the flue temp is because your water temp is probably still less than target of ?? 170-180* ? So the heat is being transfered into the water, just like it is supposed to.. Once the house is up to temp and the water is up to temp the flue temps will rise.

Another possibility is that the velocity of the gasses in the flue are higher with the 5" pipe, so this may effect the temp of the pipe, especially if you are using at magnetic thermometer.

Greg L
Burning Pea/Buckwheat through an antique stoker [semi retired SSboiler],
Running an Axeman-Anderson 260M boiler burning Pea, About 150-250#per day
Farming, Fixing, Fabricating and Flying: 'spare time' what's that?
User avatar
LsFarm
Site Moderator
 
Posts: 5619
Joined: Sun Nov 20, 2005 9:02 pm
Location: Michigan
Stove/Furnace Make: Axeman Anderson and Custom
Stove/Furnace Model: Boilers: AA 260M, BBertha 250K

Re: Build Up In The AA-130 Ash Cone

PostBy: Blackdiamonddoug On: Tue Feb 02, 2010 5:29 pm

aa260 above 500 once 250 adverage with natural draft 400 to 450 on a regular stoke
I use a pipe to break up klinkers
Oil boiler tripped out yesterday caused circulator to stop running and my fire climbed in the feed tube Temp switch (fuseable link) shut off boiler.

BDD
Last edited by Blackdiamonddoug on Tue Feb 02, 2010 6:24 pm, edited 1 time in total.
[attachment=]
User avatar
Blackdiamonddoug
Member
 
Posts: 275
Joined: Wed Jun 11, 2008 8:52 am
Location: haverhill Ma
Stove/Furnace Make: axemen 260 rebuilt by Matt
Stove/Furnace Model: stoker AA 260

Re: Build Up In The AA-130 Ash Cone

PostBy: brckwlt On: Tue Feb 02, 2010 6:00 pm

LsFarm wrote:I'd say the difference in the flue temp is because your water temp is probably still less than target of ?? 170-180* ? So the heat is being transfered into the water, just like it is supposed to.. Once the house is up to temp and the water is up to temp the flue temps will rise.

Another possibility is that the velocity of the gasses in the flue are higher with the 5" pipe, so this may effect the temp of the pipe, especially if you are using at magnetic thermometer.

Greg L



I have two probe typer thermometers. one close to the boiler in the 5 inch section and one after the baro

water temps are between 190-200 for the last 4-5 hours while the boiler was running and steady
burning pea coal from harmony mine, picked up in my 2002 Pontiac "Coalfire"
User avatar
brckwlt
Member
 
Posts: 2925
Joined: Tue Jan 27, 2009 9:32 pm
Location: Sunbury, PA
Stove/Furnace Make: Axeman-Anderson
Stove/Furnace Model: Rebuilt 1953 AA-130

Re: Build Up In The AA-130 Ash Cone

PostBy: brckwlt On: Wed Feb 03, 2010 7:17 pm

Here are some pictures of the new flu pipe i installed when i was fixing the ash cone. Please remember i am not a professional.

I have a 5 inch T coming off of the boiler and 5 inch pipe running up to the two baros that are six inch and the six inch continues to the chimney. Since i do not have a clean out for that flu i took a piece of six inch pipe and bent it to fit underneath of the six inch that runs into the chimney. This way i can stick a shop vac hose into that opening to clean out whatever builds up in there.
Attachments
IMG_0899.JPG
(152.57 KiB) Viewed 30 times
View: New PagePopup • Select:BBCode
[nepathumb]18812[/nepathumb]
IMG_0896.JPG
(75.9 KiB) Viewed 11 times
View: New PagePopup • Select:BBCode
[nepathumb]18813[/nepathumb]
IMG_0894.JPG
(126.56 KiB) Viewed 13 times
View: New PagePopup • Select:BBCode
[nepathumb]18814[/nepathumb]
IMG_0892.JPG
(149.22 KiB) Viewed 14 times
View: New PagePopup • Select:BBCode
[nepathumb]18815[/nepathumb]
IMG_0887.JPG
(123.13 KiB) Viewed 18 times
View: New PagePopup • Select:BBCode
[nepathumb]18816[/nepathumb]
IMG_0888.JPG
(105.03 KiB) Viewed 9 times
View: New PagePopup • Select:BBCode
[nepathumb]18817[/nepathumb]
burning pea coal from harmony mine, picked up in my 2002 Pontiac "Coalfire"
User avatar
brckwlt
Member
 
Posts: 2925
Joined: Tue Jan 27, 2009 9:32 pm
Location: Sunbury, PA
Stove/Furnace Make: Axeman-Anderson
Stove/Furnace Model: Rebuilt 1953 AA-130

Re: Build Up In The AA-130 Ash Cone

PostBy: Blackdiamonddoug On: Fri Feb 05, 2010 6:22 pm

wow two baro damper in paraell
I like the gold color
BDD
[attachment=]
User avatar
Blackdiamonddoug
Member
 
Posts: 275
Joined: Wed Jun 11, 2008 8:52 am
Location: haverhill Ma
Stove/Furnace Make: axemen 260 rebuilt by Matt
Stove/Furnace Model: stoker AA 260

Re: Build Up In The AA-130 Ash Cone

PostBy: brckwlt On: Fri Feb 05, 2010 7:04 pm

The two baro's are out of necessity. When the boiler is running hard the one is open the whole way and the second is open partially. On very windy days the second one is open at least half way.
burning pea coal from harmony mine, picked up in my 2002 Pontiac "Coalfire"
User avatar
brckwlt
Member
 
Posts: 2925
Joined: Tue Jan 27, 2009 9:32 pm
Location: Sunbury, PA
Stove/Furnace Make: Axeman-Anderson
Stove/Furnace Model: Rebuilt 1953 AA-130

Re: Build Up In The AA-130 Ash Cone

PostBy: brckwlt On: Fri Feb 05, 2010 11:21 pm

How should the inside of the burn pot look? I have recently noticed whats looks like flakey stuff on the sides of the burn pot. Is this just build up from fly ash? or is this something to be concerned about? i took these pics with my cell phone while the boiler was running. i can take more pics with a better camera if need be. Does anyone have pictures of the inside of their burn pot i could compare to?
Attachments
Photo0490.jpg
(67.6 KiB) Viewed 6 times
View: New PagePopup • Select:BBCode
[nepathumb]18905[/nepathumb]
Photo0491.jpg
(64.19 KiB) Viewed 8 times
View: New PagePopup • Select:BBCode
[nepathumb]18906[/nepathumb]
burning pea coal from harmony mine, picked up in my 2002 Pontiac "Coalfire"
User avatar
brckwlt
Member
 
Posts: 2925
Joined: Tue Jan 27, 2009 9:32 pm
Location: Sunbury, PA
Stove/Furnace Make: Axeman-Anderson
Stove/Furnace Model: Rebuilt 1953 AA-130