HYFIRE II INSTALL

HYFIRE II INSTALL

PostBy: Hot Rocks On: Sun Jul 11, 2010 9:36 am

Picked up new stove on saturday, I have some other projects going on right now so the install will be slow, I will keep you posted maybe some pictures, I know how much everyone likes pictures.My setup is 1420 sf unfinished basement,1420 sf 1st floor, 770 sf 2nd floor, 22 year old house, 2x4 walls r-19 insulation lots of windows, r-49 in ceiling. Stove will be in basement with heat jacket, 14 inch duct going into cold air return on furnace (heat pump). I am going to be able to control or close any of the cold air returns.That will be trial & error,example 2nd floor returns open, 1st floor returns closed, basement door open. Coal-trol t-stat will be on 1st floor 40 feet away from stove. Will have a fan limit switch to control furnace fan. The stove has a 21-t double loop coil , I will have 2 tanks 50 gal. each about 10 feet away they will be elevated, the system will thermosyphon,I will also use a 007 circulator on a wall switch running 24/7. I will be able to draw or return water to ether tank
Hot Rocks
 
Hot Air Coal Stoker Stove: Hyfire II
Coal Size/Type: Rice
Other Heating: Water Coil

Re: HYFIRE II INSTALL

PostBy: Flyer5 On: Wed Jul 14, 2010 10:10 am

Let us know how you like the 460 air meter when you start setting the draft .Also we like pictures . Thanks Dave
Flyer5
 
Stoker Coal Boiler: Leisure Line WL110
Hot Air Coal Stoker Stove: Leisure Line Pioneer

Re: HYFIRE II INSTALL

PostBy: Hot Rocks On: Sat Jul 17, 2010 6:15 am

Any suggestions on which fan limit switch ? I was looking at honeywell L4064B2236, 8 inch insertion, I have heat jacket with 14 inch duct. also how high above stove body should i put switch
Hot Rocks
 
Hot Air Coal Stoker Stove: Hyfire II
Coal Size/Type: Rice
Other Heating: Water Coil

Visit Leisure Line Stove

Re: HYFIRE II INSTALL

PostBy: Wood'nCoal On: Sat Jul 17, 2010 7:48 am

We love pictures here!
Wood'nCoal
 
Stoker Coal Boiler: 1959 EFM 350
Hand Fed Coal Stove: Harman Magnafire Mark I
Coal Size/Type: Rice and Chestnut
Other Heating: Fisher Fireplace Insert

Re: HYFIRE II INSTALL

PostBy: Hot Rocks On: Sat Jul 17, 2010 5:42 pm

Just finished electric & tested,on back of hopper
Attachments
hyfire II electrical 001.jpg
(143.66 KiB) Viewed 104 times
View: New PagePopup • Select:BBCode
[nepathumb]21280[/nepathumb]
hyfire II electrical 002.jpg
(121.65 KiB) Viewed 113 times
View: New PagePopup • Select:BBCode
[nepathumb]21281[/nepathumb]
Hot Rocks
 
Hot Air Coal Stoker Stove: Hyfire II
Coal Size/Type: Rice
Other Heating: Water Coil

Re: HYFIRE II INSTALL

PostBy: tsb On: Sat Jul 17, 2010 8:37 pm

Your going to be in your underware all next winter.
tsb
 
Stoker Coal Boiler: Binford 2000
Hot Air Coal Stoker Stove: LL Pioneer top vent
Hand Fed Coal Stove: Saey Hanover II

Re: HYFIRE II INSTALL

PostBy: WNY On: Tue Jul 20, 2010 8:23 am

You electrical boxes and switches look familiar......:)
WNY
 
Hot Air Coal Stoker Stove: Keystoker 90K, Leisure Line Hyfire I
Coal Size/Type: Rice
Stove/Furnace Make: Keystoker, LL & CoalTrol
Stove/Furnace Model: 90K, Hyfire I, VF3000 Soon

Re: HYFIRE II INSTALL

PostBy: Hot Rocks On: Tue Jul 20, 2010 5:39 pm

Dave I got the idea for the outlets & switches from your post. thanks for the info. Dean
Hot Rocks
 
Hot Air Coal Stoker Stove: Hyfire II
Coal Size/Type: Rice
Other Heating: Water Coil

Re: HYFIRE II INSTALL

PostBy: Hot Rocks On: Mon Sep 13, 2010 8:33 pm

Some updated pictures of install. I still have to hook up water coil , I have all the fittings & pipe just need to get another water heater. I want to get cold air returns hooked up also.I better get working on it before it gets cold :o
hyfire II electrical 004.jpg
(137.04 KiB) Viewed 70 times
View: New PagePopup • Select:BBCode
[nepathumb]22108[/nepathumb]
Attachments
hyfire II electrical 003.jpg
(95.86 KiB) Viewed 58 times
View: New PagePopup • Select:BBCode
[nepathumb]22107[/nepathumb]
hyfire II electrical 005.jpg
(145.45 KiB) Viewed 70 times
View: New PagePopup • Select:BBCode
[nepathumb]22109[/nepathumb]
hyfire II electrical 006.jpg
(111.3 KiB) Viewed 54 times
View: New PagePopup • Select:BBCode
[nepathumb]22110[/nepathumb]
hyfire II electrical 007.jpg
(116.47 KiB) Viewed 28 times
View: New PagePopup • Select:BBCode
[nepathumb]22111[/nepathumb]
hyfire II electrical 008.jpg
(128.66 KiB) Viewed 46 times
View: New PagePopup • Select:BBCode
[nepathumb]22112[/nepathumb]
hyfire II electrical 009.jpg
(153.02 KiB) Viewed 42 times
View: New PagePopup • Select:BBCode
[nepathumb]22113[/nepathumb]
Hot Rocks
 
Hot Air Coal Stoker Stove: Hyfire II
Coal Size/Type: Rice
Other Heating: Water Coil

Re: HYFIRE II INSTALL

PostBy: Flyer5 On: Mon Sep 13, 2010 9:36 pm

Looks great so far . Looks like you will have a warm winter . Dave
Flyer5
 
Stoker Coal Boiler: Leisure Line WL110
Hot Air Coal Stoker Stove: Leisure Line Pioneer

Re: HYFIRE II INSTALL

PostBy: WNY On: Tue Sep 14, 2010 4:25 pm

Looks almost the same as my install, less the hot water coil.... :)

Enjoy the heat!
WNY
 
Hot Air Coal Stoker Stove: Keystoker 90K, Leisure Line Hyfire I
Coal Size/Type: Rice
Stove/Furnace Make: Keystoker, LL & CoalTrol
Stove/Furnace Model: 90K, Hyfire I, VF3000 Soon

Re: HYFIRE II INSTALL

PostBy: ceccil On: Wed Sep 15, 2010 11:36 am

Wow are you going to make some hot water with that thing. Especially if both burners are running.

Do you have a way to dump excess heat from the water. I have a single loop coil and a single burner and do occasionally pop the relief valve. I believe your setup is going to need it. Very nice job.
ceccil
 
Stove/Furnace Make: Keystoker, Harman
Stove/Furnace Model: 90K, Mark III

Re: HYFIRE II INSTALL

PostBy: Flyer5 On: Wed Sep 15, 2010 5:53 pm

When I had my stove with a coil . I just used a 6' base board heater and a good quality mixing valve .When the water went above 150 -160 it would circ through the baseboard . Worked well , cannot remember the exact layout but it was somehow paralleled in .Dave
Flyer5
 
Stoker Coal Boiler: Leisure Line WL110
Hot Air Coal Stoker Stove: Leisure Line Pioneer

Re: HYFIRE II INSTALL

PostBy: Hot Rocks On: Fri Oct 22, 2010 9:06 pm

More pictures of install. I fired up both burners on 10/20, stove is just on low idle,turned min. down to 4 , draft is .04 ,front of stove is about 300 , I can put my hand on stack pipe. The hot water tempering tank is about 130 going in coil, 140 coming out.
hyfire II install 010.jpg
(103.88 KiB) Viewed 39 times
View: New PagePopup • Select:BBCode
Dwyer 460 air meter, I have a new in the box model 25 I will not be using. Dave at LL set me up with the 460 air meter, it works very good and needs no oil
[nepathumb]22727[/nepathumb]
]
hyfire II install 011.jpg
(87.48 KiB) Viewed 27 times
View: New PagePopup • Select:BBCode
[nepathumb]22728[/nepathumb]
Attachments
hyfire II install 013.jpg
(108.92 KiB) Viewed 30 times
View: New PagePopup • Select:BBCode
[nepathumb]22729[/nepathumb]
hyfire II install 015.jpg
(107.18 KiB) Viewed 37 times
View: New PagePopup • Select:BBCode
[nepathumb]22730[/nepathumb]
hyfire II install 019.jpg
(97.18 KiB) Viewed 9 times
View: New PagePopup • Select:BBCode
[nepathumb]22731[/nepathumb]
hyfire II install 012.jpg
(106.78 KiB) Viewed 23 times
View: New PagePopup • Select:BBCode
[nepathumb]22732[/nepathumb]
hyfire II install 020.jpg
(91.14 KiB) Viewed 11 times
View: New PagePopup • Select:BBCode
[nepathumb]22733[/nepathumb]
hyfire II install 018.jpg
(90.74 KiB) Viewed 18 times
View: New PagePopup • Select:BBCode
[nepathumb]22734[/nepathumb]
hyfire II install 017.jpg
(114.4 KiB) Viewed 62 times
View: New PagePopup • Select:BBCode
[nepathumb]22735[/nepathumb]
Hot Rocks
 
Hot Air Coal Stoker Stove: Hyfire II
Coal Size/Type: Rice
Other Heating: Water Coil

Re: HYFIRE II INSTALL

PostBy: Bpashocker On: Sat Oct 23, 2010 6:48 am

Thats a great instalation. i have a Hyfire II and every year i try to think of way to make more efficient.
Bpashocker
 
Stove/Furnace Make: Leisure Line
Stove/Furnace Model: Hyfire 2