coal -trol question

coal -trol question

PostBy: wally61 On: Fri Apr 13, 2007 10:54 am

hooked up yesterday and ran fine all day and night.set up to go to 76 dergrees at 5 in morning.came down and stove was in full mode got to 80 degrees bofore starting to shut down.do i need to set my max lower?nin is 4 max is 38 called paul or neil have not heard back yet
wally61
 
Stove/Furnace Make: alaska
Stove/Furnace Model: channing III dv coal-trol

PostBy: ewcsretired On: Fri Apr 13, 2007 7:01 pm

When I first started using the Coal Trol I set mine up to lower temp at night and then come up at 5 am. Like your experience, the overshoot was more than desired. I solved the problem by setting the temp to one constant temp, with no setback.

The coal trol is a great device, no more guessing and adjusting feed rates.
ewcsretired
 

PostBy: bksaun On: Fri Apr 13, 2007 7:10 pm

Mine works properly, with no overshoot. Can the heated air reach the thermostat easily?

BK
bksaun
 