AHS-130 Flapper Problem

 
User avatar
coaledsweat
Site Moderator
Posts: 13768
Joined: Fri. Oct. 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stoker Coal Boiler: Axeman Anderson 260M
Coal Size/Type: Pea

Post by coaledsweat » Tue. Oct. 26, 2010 11:10 pm

I would check the fan to vessel space setting. Loosen the shaft so you can slide it in and out to find out where it is in relation with the face of the boiler. If it moves in a considerable distance before it hits, that is your problem. Not sure about the AHS, but the AAs will move about 1/2-3/4 of an inch. Reset it about an 1/8" or so off the boilers face (spin it by hand until it stops scraping, back it up from there, tighten, realign your pulleys) and see if that flapper slams for you.


 
jmmazzy
Member
Posts: 95
Joined: Wed. Aug. 27, 2008 7:00 pm

Post by jmmazzy » Wed. Oct. 27, 2010 8:36 am

coaledsweat wrote:I would check the fan to vessel space setting. Loosen the shaft so you can slide it in and out to find out where it is in relation with the face of the boiler. If it moves in a considerable distance before it hits, that is your problem. Not sure about the AHS, but the AAs will move about 1/2-3/4 of an inch. Reset it about an 1/8" or so off the boilers face (spin it by hand until it stops scraping, back it up from there, tighten, realign your pulleys) and see if that flapper slams for you.
Done all that and the 1/8" does draw more air, as I tried it on my boiler.
AA130FIREMAN wrote:
Easy fix, have you son move back home with you :lol: Another thought, does the flapper door swing freely and how far away is it. My AA uses a threaded bolt and 2 nuts on either side to keep the flapper away at idol, some times it would hang up on the threads if it was too close to the inner nut. If AHS uses the same cutting edge technology as the AA :D
No thanks on the son moving back. Flapper is free, the most puzzling thing is even when I try to hold it in place, nothing.

 
Bob
Member
Posts: 304
Joined: Sun. Mar. 18, 2007 11:28 am
Location: Schuylkill County
Stoker Coal Boiler: AHS 130
Coal Size/Type: Pea/Anthracite

Post by Bob » Wed. Oct. 27, 2010 10:34 am

Perhaps there is a manufacturing defect that creates an air leak.

I suggest this because you have established that the fan provides proper air flow yet an air flow is not created at the shutter valve sufficient to close it.

Your initial description suggests that air is NOT being drawn up through the coal in the firepot--" I fired her up last week and after 2 days she died ". Therefore it appears the air has to be coming from somewhere else. The fact that the flapper is not pulled closed seems to demonstrate the air is not coming from the port covered by the shutter valve. There is no where else for the air to come from in a AHS boiler that is correctly constructed.

Perhaps you could identify the problem by removing all coal and ash and then removing the grate and inspecting the firepot from below. The other alternative would be to return the unit to AHS for inspection/repair.

 
jmmazzy
Member
Posts: 95
Joined: Wed. Aug. 27, 2008 7:00 pm

Post by jmmazzy » Wed. Oct. 27, 2010 11:41 am

Gismo said: I have a AA 130 but they are simular.The space between the bottom of the fire pot
and the ash tray regulates max air flow.When you fill the pot it creates a vacuum pulling
the draft breaker door shut.

Put everything back together, filled the pot with ash turned it on an BAM the flapper shut tight, never did that in the 2 years I had her before. My eye is now on the thermocouple and the fuji controller, maybe over shaking but no unburnt coals. Grate on temp is set at 130. Got to take out the manual. Any tricks to these controllers. Whats the resistance on the thermocoupler for testing, does anybody know?

Mazzy

 
User avatar
gizmo
Member
Posts: 98
Joined: Fri. Dec. 25, 2009 9:24 am
Location: Southern Minnesota
Stoker Coal Boiler: AA-130
Coal Size/Type: Anthracite/Pea
Other Heating: NONE

Post by gizmo » Wed. Oct. 27, 2010 11:56 am

I am sure this sounds waco,but most of my problems are caused by
turning the ash temp.DOWN to low.This causes the fire to get to thin,
even though you get no unbernt coal,they run better with a thicker fire
which is what I get when I run a hotter ash setting(like 140 Deg.)

 
cabinover
Member
Posts: 2344
Joined: Wed. Feb. 04, 2009 7:13 am
Location: Fair Haven, VT
Stoker Coal Boiler: Hybrid Axeman Anderson 130
Baseburners & Antiques: Sparkle #12
Coal Size/Type: Pea, Buckwheat, Nut
Other Heating: LP Hot air. WA TX for coal use.

Post by cabinover » Wed. Oct. 27, 2010 11:57 am

If it was overshaking that much wouldn't you lose your fire? Doesn't make a whole lot of sense does it?

 
User avatar
AA130FIREMAN
Member
Posts: 1954
Joined: Sat. Feb. 28, 2009 4:13 pm

Post by AA130FIREMAN » Wed. Oct. 27, 2010 12:11 pm

gizmo wrote:I am sure this sounds waco,but most of my problems are caused by
turning the ash temp.DOWN to low.This causes the fire to get to thin,
even though you get no unbernt coal,they run better with a thicker fire
which is what I get when I run a hotter ash setting(like 140 Deg.)
I will second that, I was tring to lower the temp of the asher, and now I seem to have better ashes, finer with less clinkers, when I adjust the temp up, only do 3 degrees a day and wait for the change. Small steps are better than great leaps. :D


 
User avatar
Yanche
Member
Posts: 3026
Joined: Fri. Dec. 23, 2005 12:45 pm
Location: Sykesville, Maryland
Stoker Coal Boiler: Alternate Heating Systems S-130
Coal Size/Type: Anthracite Pea

Post by Yanche » Wed. Oct. 27, 2010 5:02 pm

jmmazzy wrote:. Whats the resistance on the thermocoupler for testing, does anybody know?

Mazzy
As you say the temperature sensor on the ash controller is a thermocouple. It's a welded joint of two dissimilar metals. Resistance will be very low, too low to measure with any common VOM. Perhaps you were thinking of a thermistor, a device that changes resistance with temperature. In the HVAC industry a common thermistor has a resistance of 10K ohms at room temperature. Your AHS thermocouple should show a short when measured with a common meter.

 
jmmazzy
Member
Posts: 95
Joined: Wed. Aug. 27, 2008 7:00 pm

Post by jmmazzy » Wed. Oct. 27, 2010 5:39 pm

Started her up. Lowered grate temp. to 120 as recommended by AHS manual for warm weather conditions and will increase it as the outdoor temps drop,seams to be running excellent. Checked thermocouple with my fluke thermometer, reading accurate on the fuji controller. Dumped heat and cycled stoker 5 or 6 times, seems to be working fine, flapper doing nicely. I'm beginning to believe that all my testing should have been done with the fire pot filled with more ash as I put 2 one gallon buckets in on top of what was already there, and there was a lot. I will take a vaccumn test tomorrow through the sight hole on the flapper (thanks gizmo) and report back.


Mazzy
Last edited by jmmazzy on Wed. Oct. 27, 2010 5:41 pm, edited 1 time in total.

 
User avatar
Pa papa
Member
Posts: 96
Joined: Thu. Oct. 29, 2009 7:38 pm
Location: Summerville,PA
Stoker Coal Boiler: AHS-130
Coal Size/Type: Pea; anthracite
Other Heating: oil fired boiler; LP insert

Post by Pa papa » Wed. Oct. 27, 2010 5:39 pm

...and a DC voltage (millivolts) when the end is heated

 
jmmazzy
Member
Posts: 95
Joined: Wed. Aug. 27, 2008 7:00 pm

Post by jmmazzy » Thu. Oct. 28, 2010 3:32 pm

Done the draft test on son's stoker, -1.0 inches of mercury and seems fine, fan set 1/8" from back plate.
Done the draft test on my stoker, -2.0 inches of mercury and never had a problem. fan set 5/8" from back plate direct from AHS.
When there is a good load calling when its real cold out my stoker rumbles almost like an oil boiler.
Being that the blower fan is actualy an induced draft fan at the fire pot any problem would have to be at the fire pot, the opening at the antratube, hopper, cone, or the fan itself. After spending many hours on these units they do look identical to each other inside and out.
So what I'm getting at is because of the differance in draft (air) we know one will burn more than the other, more fuel on the fire more BTU's. Does anybody know or have any idea how to do a efficency test to a AHS stoker using this method to get the max. rated BUT's?

Mazzy

 
User avatar
Yanche
Member
Posts: 3026
Joined: Fri. Dec. 23, 2005 12:45 pm
Location: Sykesville, Maryland
Stoker Coal Boiler: Alternate Heating Systems S-130
Coal Size/Type: Anthracite Pea

Post by Yanche » Thu. Oct. 28, 2010 6:48 pm

jmmazzy wrote: Does anybody know or have any idea how to do a efficency test to a AHS stoker using this method to get the max. rated BUT's?

Mazzy
In a closed loop hydronic heating system the circulator pump characteristic flow curve can be used to compute flow. In effect the pump becomes a flow meter. You measure the pressure differential across the pump with a pressure gauge at the inlet and outlet of the pump. The pressure difference is a measure of the piping resistance (pipe head) and gives you the operating point on the manufactures pump curve. You then read the flow (GPM) from the curve. Next you measure the boiler supply and return water temperatures. Then you have what you need to calculate BTU's delivered per unit time, i.e., BTU/hr.
This equation is only an approximation because it assumes the water temperature is 60 deg F. Clearly in a boiler test it is not. A more accurate equation adds a term for the density of water at the higher temperature.

For common residential circulators and piping systems the pressure difference across the circulator is only a few psi. You need a differential pressure gauge, for example, like those sold by Dwyer. To select a gauge you re-plot the pump curve in psi rather than feet of head. It's important to select a gauge that has sufficient resolution.

 
jmmazzy
Member
Posts: 95
Joined: Wed. Aug. 27, 2008 7:00 pm

Post by jmmazzy » Thu. Oct. 28, 2010 8:12 pm

Thank Yanche, but I haven't used those formulars since I was an apprentice Local #77 Plumbers & Pipefitters now Local #51. and I'm retired now if that tells something. Remember I Have 2 systems, both with primary loops and don't plan on cutting into them, do the calucations and trying to do the stoker ajustments all at once, I'll be there for a while. What I am looking for is at some point in time AHS & Axman Anderson tested there units and came up with a BTU rating. To do this they needed to calculate how much draft (air) they needed to fire over that fire pot. How did they measure it?, static pressure, vaccumn, or something else an how. All this should tell us where the induced combustion fan should be ajusted at and take the appropriate reading for ajustment. It's like an oil burner and nossel that is sellected for a particulare boiler, nossel, air band, sutter ect. I can't get this from AHS, all I get is ajust the fan like this is plug & play. All us antratube owners should have this info.

Mazzy

 
User avatar
gizmo
Member
Posts: 98
Joined: Fri. Dec. 25, 2009 9:24 am
Location: Southern Minnesota
Stoker Coal Boiler: AA-130
Coal Size/Type: Anthracite/Pea
Other Heating: NONE

Post by gizmo » Thu. Oct. 28, 2010 9:00 pm

Hi,I was just wondering if you figure you have to many btu,s or are you short
on output.Everything I do to mine is to try and tame the monster down.Its
way big for my heat load in two seperate buildings + domestic hot water.The
only time I look at draft is when its not running, waiting for a heat call,thats
is when the draft steals heat from me.

 
User avatar
Yanche
Member
Posts: 3026
Joined: Fri. Dec. 23, 2005 12:45 pm
Location: Sykesville, Maryland
Stoker Coal Boiler: Alternate Heating Systems S-130
Coal Size/Type: Anthracite Pea

Post by Yanche » Thu. Oct. 28, 2010 9:58 pm

jmmazzy wrote:Thank Yanche, but ... What I am looking for is at some point in time AHS & Axman Anderson tested there units and came up with a BTU rating. To do this they needed to calculate how much draft (air) they needed to fire over that fire pot. How did they measure it?, static pressure, vaccumn, or something else an how. All this should tell us where the induced combustion fan should be ajusted at and take the appropriate reading for ajustment. It's like an oil burner and nossel that is sellected for a particulare boiler, nossel, air band, sutter ect. I can't get this from AHS, all I get is ajust the fan like this is plug & play. All us antratube owners should have this info.

Mazzy
Here's the reference to the AA test report I transcribed and posted almost 5 years ago:

Bureau of Mines Report 4936 Axeman-Andersen Anthratube Boiler

It's a history book of instruments used way before the start of my engineering life. It shows all the test methods they used.


Post Reply

Return to “Stoker Coal Boilers Using Anthracite (Hydronic & Steam)”