By: bleecker On: Sun Dec 26, 2010 7:27 pm
Again--many thanks.
1. I have two zones with two separate circ pumps.
2. The two circ relays are Honeywell RA832A's, one looks much newer than the other. I have a suspicion that my installer went "parts bin" on me when he installed the system.
3. You are correct--The aguer and blower shut off at 140, though the circ pumps will continue if the zone is calling for heat.
4. I have been down the road with two different plumbers about the bypass pipe. Both insisted that I don't need it. They both said that they would install the bypass, but it would be a waste of money. I don't like to argue with experts, and I don't like to waste money. However, if you guys think that a bypass would help solve the problem, I'll do it.
5. I have had "weak" heat since the boiler was installed. I have tried to deal with the guy who did the work, but he can be a real prick. He won't do service calls after the warrantee is up--too long of a drive. It's not worth it for him. How is he still in business? I don't know . . .
Stokerman: When you said try 10/9, is that 10 teeth and 9 air?
Thanks again everyone for tolerating the weak arc in my learning curve.