Dott727 wrote:I am looking for some advice as to the best way to connect a new AHS 130 to my existing propane boiler. The diagram provided on the AHS website seems backwards to me. My new coal boiler will set about 30 feet form my propane unit and will be used in the winter only. Would you recommend PEX tubing or copper, where would be the best location for the circulating pump, what about isolation valves...? Any help or advice would be greatly appreciated.
Yanche wrote:You should not use PEX tubing, use copper. How you pipe the two together will depend on what you are trying to do. Even though you have said you will only use the AHS 130 in winter I would suggest you pipe it so you can use it all year long. Depending on your fuel costs coal vs. propane it may be cheaper to heat your domestic hot water in the summer with coal. If not now perhaps in the future. I piped my S-130 in series with my oil boiler and have ball valves to isolate the coal boiler if needed. This way I can heat my coal boiler in summer eliminating the moisture rusting problem. Adjusting the valves controls the amount of summer heat. Circulation pump should be in the supply piping to your radiators or baseboard units right after the air trap.
Other considerations. Do you want automatic switch over to propane if the coal fire goes out? Do you need the BTU output of both boilers on a very, very cold day? Can your propane boiler run without electricity? If so, pipe it to be a no power backup. If you have lots of uninsulated piping the room above the boiler room gets too hot. Consider a indoor/outdoor aquastat to extend the coal use season. Helps the "it's to hot" problem. Be sure to size you expansion tank for the combined water volume. Think through valving off a hot boiler and how water from an expansion tank will now get back to the cooling boiler.
coaledsweat wrote:If you leave your existing system alone and plumb a loop between the boilers using a reverse flow and check valves, the circulator on the coal boiler should run once the coal boiler makes minimum temp (this should be just above your existing systems temperature fall to fire point). If you have a tankless coil or draw water off your boiler for your domestic you will now get it heated with coal. In addition your existing unit remains up to temperature at all times and will fire when the coal boiler falls below its minimum temp and the circulator will stop. Totally auto with no wiring between them.
Didn't your AHS come with an Aquastat?
Yanche wrote:The AHS comes standard with an Aquastat and a second over temperature temperature switch. I would pipe the two boilers in series with isolating ball valves on the coal boiler and a valved bypass pipe shunting the supply and return. In winter the bypass is closed, the boilers are in series and your control system can provide automatic switch over if the coal fire goes out. In summer close the supply and return valves and open the bypass valve. Now only your non coal boiler is heating your indirect hot water heater. This is how my system is piped. Works well. I find that by partially opening only the supply valve in summer I can get enough heat, by gravity flow, into the coal boiler to prevent condensation. This is desirable depending on your summertime relative humidity and how prone to corrosion your boiler is.
No. You will have the additional friction losses of the piping and the elbows but you are not adding to the "head". Should work fine. Rule of thumb is to use piping no less than one pipe size below the supply and/or return fittings. I'm more conservative and use the same size. For the AHS S-130, it's 1-1/2 inch.Dott727 wrote:Yanche wrote:The AHS comes standard with an Aquastat and a second over temperature temperature switch. I would pipe the two boilers in series with isolating ball valves on the coal boiler and a valved bypass pipe shunting the supply and return. In winter the bypass is closed, the boilers are in series and your control system can provide automatic switch over if the coal fire goes out. In summer close the supply and return valves and open the bypass valve. Now only your non coal boiler is heating your indirect hot water heater. This is how my system is piped. Works well. I find that by partially opening only the supply valve in summer I can get enough heat, by gravity flow, into the coal boiler to prevent condensation. This is desirable depending on your summertime relative humidity and how prone to corrosion your boiler is.
My boilers will be 30-40 feet apart. Do you think it would be necessary to install an additional pump?
Dott727 wrote:Are there any disadvanages to plumbing the units this way? If you connect them in series and dont use the coal boiler in the summer, I will have to heat the coal boiler with propane in the summer.
NEPA Crossroads is a creation of Nepadigital.Com ©2009 • Contact Admin | Terms of Use | Privacy Policy
Powered by phpBB © phpBB Group