Your triple A will stop the circ. when the boiler water gets to the low limit.
smtm wrote:Sting wrote:If this is still the old mechanical relay system, you can excite the relay manually and proof its operation to close the B1 B2 terminal. Measure voltage at B1 - Is it there? Is C1 C2 closed? if yes then B1 and B2 will be open. This is a poor control device at best for a solid fuel appliance but its cheep.
Whats wrong with jumping the TT points???? The likelihood of the relay failing closed is about as remote as hitting the lottery, and it provides far better boiler control - depending on the rest of the system control.
There is no voltage at B1 or B2 (with the temp below the low temp settings), unless the timer is activated.
when the timer is active you see power at these points -- it must be a back feed
Sting wrote: Did you read the link about how to set the Triple A and do you have it set so the b1 and b2 should be closed?
Sting wrote:OK -- not to be annoying but still attempting to address the last question 00 Ill have to re-askSting wrote: Did you read the link about how to set the Triple A and do you have it set so the b1 and b2 should be closed?
Sting wrote:no
And by that short answer - don't simply assume I am an *censored* - I am and Ill line up 12 women in under 6 minutes to pay testimonial - but that's not the point
Cheating on the test never taught us anything - learn how to set that dam thing and set it correctly for YOUR application
I cannot see across the public internet into your boiler room and tell you to do z when you may need to do t
smtm wrote:Figured out the problem thanks to scrapper jr![]()
The timer was wired directly to the stoker motor and not to the ZR terminal
A jumper from "1" to the ZR terminal and problem solved.
NEPA Crossroads is a creation of Nepadigital.Com ©2009 • Contact Admin | Terms of Use | Privacy Policy
Powered by phpBB © phpBB Group