AHS S-130 Manometer Monitor Location

AHS S-130 Manometer Monitor Location

PostBy: watkinsdr On: Fri Apr 01, 2011 2:00 am

I'm getting ready to install my new S-130. I've been using a Dwyer manometer with my Koker for a couple of years now; and, want to use the manometer with my new boiler. Where's the best place to locate the manometer's sensor on a S-130?

Thank you in advance.
watkinsdr
 
Stoker Coal Boiler: AHS S260 Boiler

Re: AHS S-130 Manometer Monitor Location

PostBy: WNY On: Fri Apr 01, 2011 6:15 am

normally between the exhaust connection from the stove and the baro.
WNY
 
Hot Air Coal Stoker Stove: Keystoker 90K, Leisure Line Hyfire I
Coal Size/Type: Rice
Stove/Furnace Make: Keystoker, LL & CoalTrol
Stove/Furnace Model: 90K, Hyfire I, VF3000 Soon

Re: AHS S-130 Manometer Monitor Location

PostBy: watkinsdr On: Fri Apr 01, 2011 7:19 am

Makes sense! Thanks!!
watkinsdr
 
Stoker Coal Boiler: AHS S260 Boiler

Re: AHS S-130 Manometer Monitor Location

PostBy: Freddy On: Fri Apr 01, 2011 7:25 am

You'll use much less coal if you locate the entire system within 75 feet of a palm tree. ;)
Freddy
 
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Hot Air Coal Stoker Stove: Reading piece o' junk in the barn (rice)
Coal Size/Type: Pea size, Superior, deep mined

Re: AHS S-130 Manometer Monitor Location

PostBy: Sting On: Fri Apr 01, 2011 9:06 am

Freddy wrote:You'll use much less coal if you locate the entire system within 75 feet of a palm tree. ;)


Is this some sort of lame April Fools advice?

Come on - you can do better :P
Sting
 
Other Heating: BurnHAM=NG-gas