Setting up New EFM 520

 
User avatar
stoker-man
Verified Business Rep.
Posts: 2071
Joined: Mon. Nov. 19, 2007 9:33 pm
Location: Lehigh Valley, PA
Hand Fed Coal Boiler: 1981 efm wcb-24 in use 365 days a year
Coal Size/Type: Anthracite/Chestnut
Other Heating: Hearthstone wood stove

Post by stoker-man » Wed. Oct. 05, 2011 5:32 am

You don't need a black spot; just slightly darker than orange when it's been sitting for 10 minutes. The black spot may appear when you are stoking hard, such as in the morning when the unit runs for long periods of time and you'll see the dark area while it's working.

 
User avatar
coal berner
Member
Posts: 3600
Joined: Tue. Jan. 09, 2007 12:44 am
Location: Pottsville PA. Schuylkill County PA. The Hart Of Anthracite Coal Country.
Stoker Coal Boiler: 1986 Electric Furnace Man 520 DF

Post by coal berner » Wed. Oct. 05, 2011 12:36 pm

cardinal wrote:coal berner: what are your winter time settings. Now at 4 teeth 4.5 air 2min per 1/2 hour. manometer settings are (-.02 at fire door) ( - .04 at stack) .Just raised chimney to 16 feet, had to bring in outside air for boiler. I have coal/ oil 520 efm . Dryer was taking air from boiler shutting down oil gun. I want to run all coal . I just started coal fire, hope it stays alive high set at 200 low at 160 (10 diff ) nobody home durning day .I hope it dosen't temp up to 200 shutting down timer this is all knew to me hope I did the right thing, going back to coal like my parents had. Thanks for all your help on here
Your draft and Type of coal will determine where the air will be set not all coal is the same some need more air to burn completely others will need less air to burn completely watch the draft and coal that will tell you what settings will work
for your set up you may need more air to burn the coal completely or you may need less air all depends on coal your using
and how well your chimney drafts .

My winter setting is 170 low 200 high 10 diff timer 1.5 minutes every hr. feed rate 3 to 4 depending on outside temp
air setting 5 to 6 depending what feed rate I am using I burn buckwheat # 1 size coal it needs higher air to burn
completely being it is larger then rice coal but it feeds less coal per hr so I use less coal then using rice also buck is much cleaner and always available the price does not fluctuate like with rice does in winter time at most breakers.

 
cardinal
Member
Posts: 64
Joined: Sat. Sep. 03, 2011 10:29 pm
Location: CARBON COUNTY,PA.
Stoker Coal Boiler: EFM 520
Coal Size/Type: Rice

Post by cardinal » Wed. Oct. 05, 2011 5:17 pm

Thanks for your help, and your time.You guys are all pro's at burning coal


 
User avatar
franpipeman
Member
Posts: 690
Joined: Fri. Jan. 11, 2008 4:27 pm
Location: Wernersville pa
Stoker Coal Boiler: efm 520 stoker fitzgibbons pressure vessel
Hand Fed Coal Stove: harman, russo
Coal Size/Type: rice
Other Heating: alpine propane condensing boiler radiant floor

Post by franpipeman » Wed. Oct. 26, 2011 11:50 am

I am not afraid to be confused sometime and this is one of them " The draft at the stack should be negative
.04 to negative .05 inches of water column" This is from the manual of draft measurments Isnt .04 inch of water equal to less than a sixteenth of a inch of draft. thanks in advance for any help

 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Wed. Oct. 26, 2011 1:55 pm

Yup, you got it. :!:

 
User avatar
franpipeman
Member
Posts: 690
Joined: Fri. Jan. 11, 2008 4:27 pm
Location: Wernersville pa
Stoker Coal Boiler: efm 520 stoker fitzgibbons pressure vessel
Hand Fed Coal Stove: harman, russo
Coal Size/Type: rice
Other Heating: alpine propane condensing boiler radiant floor

Post by franpipeman » Wed. Oct. 26, 2011 4:27 pm

t hat will hardly move a manometer especially the clear tubing I was planning to use


 
User avatar
Rob R.
Site Moderator
Posts: 18003
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Wed. Oct. 26, 2011 4:32 pm

If you get a manometer with the proper scale, you will be able to read it. Here is an example:

 
User avatar
franpipeman
Member
Posts: 690
Joined: Fri. Jan. 11, 2008 4:27 pm
Location: Wernersville pa
Stoker Coal Boiler: efm 520 stoker fitzgibbons pressure vessel
Hand Fed Coal Stove: harman, russo
Coal Size/Type: rice
Other Heating: alpine propane condensing boiler radiant floor

Post by franpipeman » Wed. Oct. 26, 2011 4:58 pm

You are absolutely correct mark that is the way to read such small displacments but being the cheap (34$) skate that I am I may borrow my radon mitigation manometer and use that I am tighther than a cows a## during fly time in may.

 
User avatar
franpipeman
Member
Posts: 690
Joined: Fri. Jan. 11, 2008 4:27 pm
Location: Wernersville pa
Stoker Coal Boiler: efm 520 stoker fitzgibbons pressure vessel
Hand Fed Coal Stove: harman, russo
Coal Size/Type: rice
Other Heating: alpine propane condensing boiler radiant floor

Post by franpipeman » Wed. Oct. 26, 2011 5:28 pm

upon further review I will spring for the manometer. I do have resources where I could borrow them but its an hour of time and a gallon of gas