McGiever wrote:Carbon MonOxide Detectors are 'swell' if you are home to hear them. But, who will shut down the stove when your not home?
This device needs to made know here in "Venting, Plumbing, Chimneys, Controls, and Coal Bins"
Fields WMO-1 Detects Blocked Flue
McGiever is spot-on here with this post and all should have a look at it...
I will detail my setup on the old Alaska having a WMO-1 in operation...

- (99.09 KiB) Viewed 11 times
- View: New Page • Popup • Select:BBCode
- Field Controls WMO-1 200 degree fume switch
[nepathumb]30232[/nepathumb]

- (134.73 KiB) Viewed 17 times
- View: New Page • Popup • Select:BBCode
- Broader view of WMO-1 mounted through side wall of stove
[nepathumb]30233[/nepathumb]

- (140.22 KiB) Viewed 11 times
- View: New Page • Popup • Select:BBCode
- This switch supplies 120VAC to/through the N/C contact of the WMO-1
[nepathumb]30234[/nepathumb]

- (133.24 KiB) Viewed 9 times
- View: New Page • Popup • Select:BBCode
- 120VAC goes through N/C contact of WMO-1 then to this bottom outlet that supplies the Coal-trol with juice which in turn powers the combustion blower, stoker feeder and distribution blower...
[nepathumb]30235[/nepathumb]
I run this stove on a Field Controls SWG-4HDS power vent and if it were to fail the stove now has no way to evacuate the gasses in the fire box... In an event like this the firebox temp would rise quickly and with no place for the gasses to go they would find their way to the WMO-1 which has a hollow tube that protrudes into the firebox and is open-ended at the switch side... Once the hot gasses pass through the hollow tube they will heat up the switch which is made to "break" at 200 degrees F... When the switch breaks it cuts power from in my case the Coal-trol control module (shutting down combustion blower, stoker feeder gear motor and distribution blower) or whatever you have plugged in to the WMO-1 setup... Very important and a must have for power vent users, and ultimately makes the use of a power vent a much better option than a natural draft chimney, at least in my opinion that is...

- (139.55 KiB) Viewed 6 times
- View: New Page • Popup • Select:BBCode
- This switch supplies power to the power vent... Power vent should be on its own branch and NOT powered by the WMO-1...
[nepathumb]30236[/nepathumb]

- (151.63 KiB) Viewed 7 times
- View: New Page • Popup • Select:BBCode
- Now you see that the power vent is not powered by the WMO-1, it is on its own circuit as it should be...
[nepathumb]30238[/nepathumb]
Now think the other way around... Lets say that your power vent is working fine but it takes on a heavy sustained head wind and the gust over powers the venter causing a lack of draft on the stove... The WMO-1 will shut down the stove once again, but, your venter will continue to run because it is powered from a separate outlet and NOT from the WMO-1... With the venter still able to run it will continue to exhaust the stove as the burning bed of coal dies out...
Hope that makes sense???