Aldo8811 wrote:So I did a little work on it this evening, my red nut is 15 turns away from the boiler, the air shutter on the stoker is open about half way, the air on the little fan is open half way as well (the fan is off at rest). While checking tonight, the stoker was on and a lot of air was blowing out the little fan so I wired it to come on with the stoker. I have, during a call for for heat, turned the stoker off and check the draft, -.04. I haven't checked it lately at rest but it typically is a strong neg .02
What are you using for a draft control? According to the manual, your draft is higher than recommended.

 
User avatar
Aldo8811
Member
Posts: 49
Joined: Tue. Oct. 04, 2011 10:11 pm
Location: Central Maine

Post by Aldo8811 » Mon. Dec. 05, 2011 8:14 pm

Rob
Using a barometric damper. I added a little weight to it last night and got the draft down to just a smidge over ( or I guess it's really under ) neg .02. I also removed 1 more pin from the timer. Still burning tonight so I guess I haven't killed it yet.

 
User avatar
Rob R.
Site Moderator
Posts: 17979
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Mon. Dec. 05, 2011 8:25 pm

This is what Keystoker says about draft:

 
User avatar
Aldo8811
Member
Posts: 49
Joined: Tue. Oct. 04, 2011 10:11 pm
Location: Central Maine

Post by Aldo8811 » Mon. Dec. 05, 2011 8:33 pm

I think im at that point right now... I only know my chimney really sucks! lol


 
User avatar
Rob R.
Site Moderator
Posts: 17979
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Mon. Dec. 05, 2011 8:51 pm

That's a good thing!

What size is your flue pipe and draft control? 8"?

 
User avatar
Aldo8811
Member
Posts: 49
Joined: Tue. Oct. 04, 2011 10:11 pm
Location: Central Maine

Post by Aldo8811 » Mon. Dec. 05, 2011 9:17 pm

yes. 8" all the way to the top 27 or so feet. I had to add 3 of the little hooks from shop light chains to help with the balance on the barometric damper in order to get to the neg .02

 
User avatar
Rob R.
Site Moderator
Posts: 17979
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Mon. Dec. 05, 2011 9:22 pm

Your trick with the extra weights will work, and so would a second draft control. Your method is certainly more cost effective.