will this work?

will this work?

PostBy: Boots On: Thu Dec 01, 2011 11:40 pm

Forgive my crude drawings but will this work or is there a better/more efficient way to plumb an add on boiler? I currently have an oil fired boiler in place and will be adding a coal fired boiler onto the system. I want to continue to use my existing domestic water coil that is in my oil boiler. In my mind i could lower the set point on the oil fired boiler (to what i dont know) and let the coal boiler do all of the work. when the circulator pumps kick on it will pull the heated water through the system and both boilers. and the ball valves were intended to give me the ability to isolate the coal boiler from the system if needed. and the upper most ball valve would be in the "open" position only if i were using only the oil boiler.

Image
Boots
Member
 
Posts: 109
Joined: Thu Nov 10, 2011 5:38 pm
Location: Central PA
Stove/Furnace Make: Burnham
Stove/Furnace Model: SFB-101 hand fired boiler.


Re: will this work?

PostBy: 2001Sierra On: Thu Dec 01, 2011 11:53 pm

Tarm USA has everything configured.
http://www.woodboilers.com/admin/upload ... 111Web.pdf
They have done all the homework, with many configurations.
My neighbor runs a Tarm and we followed the guidlines illustrated here.
User avatar
2001Sierra
State of New York Moderator
 
Posts: 780
Joined: Wed May 20, 2009 8:09 am
Location: Wynantskill NY, 10 miles from Albany
Stove/Furnace Make: Keystoker with Coal-Trol
Stove/Furnace Model: Keystoker 90 Chimney Vent

Re: will this work?

PostBy: ValterBorges On: Fri Dec 02, 2011 12:01 am

User avatar
ValterBorges
Member
 
Posts: 569
Joined: Mon Sep 05, 2011 10:12 pm
Location: Berlin, CT
Stove/Furnace Make: AHS
Stove/Furnace Model: S260

Re: will this work?

PostBy: Rob R. On: Fri Dec 02, 2011 12:39 pm

If you want to continue using the tankless oil in the oil boiler, your proposed setup won't work...think about it, with your piping arrangement the only time heated water flows from the coal boiler to the oil boiler is when one of your zones is calling for heat. You need to circulate between the two boilers if you want to use the tankless in the oil boiler.
User avatar
Rob R.
Member
 
Posts: 5022
Joined: Fri Dec 28, 2007 5:26 pm
Location: Chazy, NY
Stove/Furnace Make: EFM
Stove/Furnace Model: 520

Re: will this work?

PostBy: coaledsweat On: Fri Dec 02, 2011 1:26 pm

Rob R. wrote:If you want to continue using the tankless oil in the oil boiler, your proposed setup won't work...think about it, with your piping arrangement the only time heated water flows from the coal boiler to the oil boiler is when one of your zones is calling for heat. You need to circulate between the two boilers if you want to use the tankless in the oil boiler.

Exactly, you will need a separate pump to do that job. I would also recommend a stack damper on the oil burner to reduce thermal losses up the oil burner's chimney flue if you chose that route.
User avatar
coaledsweat
Site Moderator
 
Posts: 6140
Joined: Fri Oct 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stove/Furnace Model: Axeman-Anderson 260M

Re: will this work?

PostBy: Bear038 On: Fri Dec 02, 2011 1:46 pm

Ones I have seen when they want to use both, just use the coal boiler to keep the oil boiler hot. That is a circulator loop to oil unit, and then the thermostats still run circulators for house.
Bear038
Member
 
Posts: 188
Joined: Sun Nov 28, 2010 9:03 am
Location: Freeland, MD
Stove/Furnace Make: Harman
Stove/Furnace Model: Mark II

Re: will this work?

PostBy: Boots On: Sat Dec 03, 2011 10:48 am

coaledsweat wrote:
Rob R. wrote:If you want to continue using the tankless oil in the oil boiler, your proposed setup won't work...think about it, with your piping arrangement the only time heated water flows from the coal boiler to the oil boiler is when one of your zones is calling for heat. You need to circulate between the two boilers if you want to use the tankless in the oil boiler.

Exactly, you will need a separate pump to do that job. I would also recommend a stack damper on the oil burner to reduce thermal losses up the oil burner's chimney flue if you chose that route.



Ones I have seen when they want to use both, just use the coal boiler to keep the oil boiler hot. That is a circulator loop to oil unit, and then the thermostats still run circulators for house


Are the two of you suggesting the same thing? I'm not sure I fuelly understand. Could someone point me to a diagram of this setup? Would you wire the circ pump between the two boilers to run constantly? Or could/would you set it up so that when the t-stat on the oil boiler called for heat it would just start the circ pump that was between the two boilers?

Also, why could you not use a water to water heat exchanger?
Boots
Member
 
Posts: 109
Joined: Thu Nov 10, 2011 5:38 pm
Location: Central PA
Stove/Furnace Make: Burnham
Stove/Furnace Model: SFB-101 hand fired boiler.