Trouble With Hitzer Install

 
bksaun
Member
Posts: 1037
Joined: Sat. Oct. 28, 2006 9:24 am
Location: Hustonville, Ky
Hand Fed Coal Boiler: Legacy SF-270
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Stoker/Bit, Pea or Nut Anthracite

Post by bksaun » Sat. Dec. 24, 2011 12:28 am

Its still pulling too hard, stove temp is 360 and its pulling 1.6-1.9WC. Dean from hitzer just sent me a restrictor plate to install, so I will let it go out tomorrow and put the plate in and try it again.

Today I shut all the air off, sealed it tight, let it set for 2 hours and the stove temp never dropped below 200, it was still pulling .06wc. I could hear the air being pulled through the air wash in the main door. The outside temp was in the low 40's.

This is still better than not enough draft, with patience this can be overcome.

Bk


 
User avatar
LsFarm
Member
Posts: 7383
Joined: Sun. Nov. 20, 2005 8:02 pm
Location: Michigan
Stoker Coal Boiler: Axeman Anderson 260
Hand Fed Coal Boiler: Self-built 'Big Bertha' SS Boiler
Baseburners & Antiques: Keystone 11, Art Garland

Post by LsFarm » Tue. Dec. 27, 2011 9:01 pm

Is the 503 a tight fit in the fireplace 'box' ?? Are you using a decorative 'surround' to finish off the gap between the stove and the front of the fireplace facia?

If you have a gap, you could install an other 6" pipe up the chimney, parallel to the current 10' piece of SS. seal around the two pipes again with fiberglass. On the bottom exposed end of the new pipe install a 90* ell, and a piece of straight 6" pipe, bring it out to the front of the fireplace and install a Baro damper. Leaving the damper inside the fireplace will cause it to exhaust very hot air, bringing it out to the front of the firplace will let it exhaust room temperature air.

Just an idea, post a photo of the install, maybe you don't have any extra room to install a 6" Baro duct.

Greg L

 
bksaun
Member
Posts: 1037
Joined: Sat. Oct. 28, 2006 9:24 am
Location: Hustonville, Ky
Hand Fed Coal Boiler: Legacy SF-270
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Stoker/Bit, Pea or Nut Anthracite

Post by bksaun » Sun. Jan. 01, 2012 9:29 pm

No extra room for a baro, only 3 inches of clearance. right now its 37* outside the draft vent is 1/2 open and my baro is showing 1.4-1.7wc, its pretty windy out tonight.

Bk

 
User avatar
fastcat
Member
Posts: 444
Joined: Thu. Nov. 12, 2009 11:50 pm
Location: CNY (McGraw)
Hand Fed Coal Stove: Hitzer 50-93
Coal Size/Type: Blaschak Nut/Stove Mix

Post by fastcat » Sun. Jan. 01, 2012 11:52 pm

Best thing you could do is show us a picture of the setup and a close pic of the manometer.
bksaun wrote:No extra room for a baro, only 3 inches of clearance. right now its 37* outside the draft vent is 1/2 open and my baro is showing 1.4-1.7wc, its pretty windy out tonight.

Bk

 
katman
Member
Posts: 94
Joined: Fri. Dec. 07, 2007 2:18 pm
Location: Davidsonville, md.
Hot Air Coal Stoker Stove: Harman Magnum
Other Heating: Harman PB 105 Pellet Boiler

Post by katman » Wed. Jan. 04, 2012 9:49 am

I had similar problems with my fireplace--outside chimney with flue much larger than the stovepipe. I even tried extending the chimney, made no difference, then I ran pipe all the way to the top. Pulled a little better but not much when cold. Once it was hot it pulled fine. So, to start with a cold chimney I would burn a few single sheets of newspaper to "preheat" and get the flow going in the chimney. While doing this I would also get some small kindling going that would burn hot and fast. This solved the start-up problem and kept the house from filling with smoke. Once the fire was going and hot the only way I could achieve control was to put a damper on top of the chimney, controlled with a chain/pulley system.

 
bksaun
Member
Posts: 1037
Joined: Sat. Oct. 28, 2006 9:24 am
Location: Hustonville, Ky
Hand Fed Coal Boiler: Legacy SF-270
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Stoker/Bit, Pea or Nut Anthracite

Post by bksaun » Wed. Jan. 04, 2012 4:31 pm

Here are a few pictures, look at the draft :shock: the damper is closed completely and air is open 1/4 inch, outside temp is 18*, if I leave it set like this and the outside temp goes up to 40* the draft will drop to 1.5wc, still to much.
My internal damper has an added piece of steel about an 1-1/4" wide to close it down even more.Stove temp is about 280*, burning just over 2 bags in 24 hrs.

I've got to find a way to slow this run away train down, wish I knew what my stack temps were.
DSCF0453.jpg
.JPG | 127.5KB | DSCF0453.jpg
DSCF0454.jpg
.JPG | 86KB | DSCF0454.jpg
DSCF0452.jpg
.JPG | 117.9KB | DSCF0452.jpg

 
User avatar
Rick 386
Member
Posts: 2508
Joined: Mon. Jan. 28, 2008 4:26 pm
Location: Royersford, Pa
Stoker Coal Boiler: AA 260 heating both sides of twin farmhouse
Hot Air Coal Stoker Stove: LL Hyfire II w/ coaltrol in garage
Coal Size/Type: Pea in AA 260, Rice in LL Hyfire II
Other Heating: Gas fired infared at work
Contact:

Post by Rick 386 » Thu. Jan. 05, 2012 8:45 am

BK,

Can you install a larger restrictor plate?? Use the one you got from Dean as a pattern and just make it bigger ???

Is there a clean out door on that chimney ?? Perhaps a sliding plate to replace the clean out door ???

Just thinking out loud with the fingers too close to the keyboard.

Rick


 
User avatar
CT coal burner
Member
Posts: 68
Joined: Fri. Aug. 19, 2011 4:30 pm
Location: Manchester, CT
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Nut

Post by CT coal burner » Thu. Jan. 05, 2012 8:23 pm

Your ash door slide is open about twice the amount I keep mine. The air is rushing right through the stove, burning up the coal, and taking all the heat out the chimney. Do you have a good seal around the shroud?
Just a thought.

 
bksaun
Member
Posts: 1037
Joined: Sat. Oct. 28, 2006 9:24 am
Location: Hustonville, Ky
Hand Fed Coal Boiler: Legacy SF-270
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Stoker/Bit, Pea or Nut Anthracite

Post by bksaun » Thu. Jan. 05, 2012 9:00 pm

Actually Dean made a larger damper, he said its closed as far as we dare close it. The shroud is well sealed and the flex pipe is sealed with insulation as well. No clean out door on the chimney.

If I close the ash door slide further the stove temp drops to around 200 and it wont throw much heat and the draft is still 1.4-1.6.

I even closed it all the way and left it for 2 hours, stove temp dropped to 150* and draft was 0.6-0.8wc.

Thinking I may cut a 6 inch hole about 2 feet above the stove, install a baro and T it in high enough to allow a short piece of flex, just enough to be able to hook it up and push it into place. Sounds like a real pain to do. It would not be pretty but I could hang a trivet in front of the baro to cover it up and it would still be able to pull air through it.

I may climb up on the roof and try covering up 1/2 the chimney to see if that will make a difference first.

 
franco b
Site Moderator
Posts: 11417
Joined: Wed. Nov. 05, 2008 5:11 pm
Location: Kent CT
Hand Fed Coal Stove: V ermont Castings 2310, Franco Belge 262
Baseburners & Antiques: Glenwood Modern Oak 114
Coal Size/Type: nut and pea

Post by franco b » Thu. Jan. 05, 2012 10:20 pm

bksaun wrote:I may climb up on the roof and try covering up 1/2 the chimney to see if that will make a difference first.
I was going to suggest a sheet of metal with a 6 inch hole in it.

 
User avatar
freetown fred
Member
Posts: 30300
Joined: Thu. Dec. 31, 2009 12:33 pm
Location: Freetown,NY 13803
Hand Fed Coal Stove: HITZER 50-93
Coal Size/Type: BLASCHAK Nut

Post by freetown fred » Thu. Jan. 05, 2012 11:39 pm

If you're going up on the roof anyway, franco b's suggestion is the way to do it RIGHT!

 
User avatar
Keepaeyeonit
Member
Posts: 1681
Joined: Wed. Mar. 24, 2010 7:18 pm
Location: Northeast Ohio.( Grand river wine country )
Baseburners & Antiques: Glenwood #8
Coal Size/Type: Nut & stove
Other Heating: 49 year old oil furnace, and finally a new heat pump

Post by Keepaeyeonit » Sat. Jan. 14, 2012 6:49 am

Bksaun, how we doing on the low stove temp :?: .Keepaeyeonit

 
bksaun
Member
Posts: 1037
Joined: Sat. Oct. 28, 2006 9:24 am
Location: Hustonville, Ky
Hand Fed Coal Boiler: Legacy SF-270
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Stoker/Bit, Pea or Nut Anthracite

Post by bksaun » Sat. Jan. 14, 2012 3:55 pm

Too much ice and snow on it, Ill install the plate in a couple of days when it clears up. It got down to about 15* night before last and my draft was at an all time high, 2.5WC.

 
bksaun
Member
Posts: 1037
Joined: Sat. Oct. 28, 2006 9:24 am
Location: Hustonville, Ky
Hand Fed Coal Boiler: Legacy SF-270
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Stoker/Bit, Pea or Nut Anthracite

Post by bksaun » Mon. Jan. 16, 2012 7:39 pm

I put the plate on top of the chimney, it has a 6 inch hole in it and so far with everything set the same the draft is at 1.8-1.9wc, at least I got it down below 2.0wc, but its still too high.

Guess I could cut a 6 inch hole in the face of the fireplace and pipe in a baro, I still think most of the heat is headed up the chimney.

Bk

 
User avatar
Keepaeyeonit
Member
Posts: 1681
Joined: Wed. Mar. 24, 2010 7:18 pm
Location: Northeast Ohio.( Grand river wine country )
Baseburners & Antiques: Glenwood #8
Coal Size/Type: Nut & stove
Other Heating: 49 year old oil furnace, and finally a new heat pump

Post by Keepaeyeonit » Mon. Jan. 16, 2012 9:00 pm

Wow that's high,It's to bad you don't have the room for a baro in your pipe down by the stove so you don't have to punch a hole in the front of your fireplace.My draft was strong but not that high(1.0 to 1.5 or so)now with the cold temps the baro is almost always opened a bit and pulling .06 to .07.Keepaeyeonit


Post Reply