Post Reply
 
cardinal
Member
Posts: 64
Joined: Sat. Sep. 03, 2011 10:29 pm
Location: CARBON COUNTY,PA.
Stoker Coal Boiler: EFM 520
Coal Size/Type: Rice

Post by cardinal » Thu. Jan. 05, 2012 9:39 pm

I have a Honeywell 1 stage digital thermostat.(with batteries) I set in on 70 and room temp says 70 but it keeps clicking on and off and calling for heat it seems to be very sensitive. I thought with a thermostat its a one degree difference between the setting and the temperature .Is there anything on the market that is not digital Thanks

 
User avatar
Rob R.
Site Moderator
Posts: 18004
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Thu. Jan. 05, 2012 9:41 pm

What model is it? Most of them have a setting for the number of cycles per hour.

 
cardinal
Member
Posts: 64
Joined: Sat. Sep. 03, 2011 10:29 pm
Location: CARBON COUNTY,PA.
Stoker Coal Boiler: EFM 520
Coal Size/Type: Rice

Post by cardinal » Thu. Jan. 05, 2012 11:12 pm

Honeywell 50000952-001 on bar code TH511OD on back


 
CoalUserWannabe
Member
Posts: 136
Joined: Thu. Jan. 13, 2011 3:00 pm

Post by CoalUserWannabe » Fri. Jan. 06, 2012 12:44 am

it's part of the features of a good design !
you can turn that feature off, it has nothing to do with the temperature, but that's the feature in Honywell, you really need to maintain a steady temperature !
it's called Cycle rate Per Hour or something like that, it's a variable number I CPH and it varies 1 to 12 .

Using a thermostat without this feature, will cause a bigger swing , depending on the recovery of your system.

 
User avatar
RAYJAY
Member
Posts: 433
Joined: Sun. Nov. 09, 2008 7:06 am
Location: UNION DALE PA
Stoker Coal Boiler: VAN WERT - 600 VA HOT WATER
Hot Air Coal Stoker Stove: HARMAN- MAGUM STOKER
Coal Size/Type: BUCKWHEAT ON BOTH
Other Heating: NG BOILER

Post by RAYJAY » Fri. Jan. 06, 2012 1:56 am

I'm using a digital also never had that problem I use a hunter 42999b have one on the Harman and one on a gas heater got it at wally world works great,

http://www.hunterair.com/product/just-right-digit ... t-b-42999B

 
cardinal
Member
Posts: 64
Joined: Sat. Sep. 03, 2011 10:29 pm
Location: CARBON COUNTY,PA.
Stoker Coal Boiler: EFM 520
Coal Size/Type: Rice

Post by cardinal » Fri. Jan. 06, 2012 6:28 pm

My CPH was 7, I set it at 3 Thanks for the help


 
homecomfort
Member
Posts: 485
Joined: Sat. Feb. 05, 2011 1:10 pm
Location: Bucks county, Pa.

Post by homecomfort » Fri. Jan. 06, 2012 6:37 pm

digital t-stats can be more sensitive to drafts, like from the hole in the wall that has the wiring, or sunlight, lamps and cause cycling.

 
User avatar
mozz
Member
Posts: 1363
Joined: Mon. Sep. 17, 2007 5:27 pm
Location: Wayne county PA.
Stoker Coal Boiler: Axeman Anderson 1982 AA-130 Steam

Post by mozz » Fri. Jan. 06, 2012 7:26 pm

The old rounds ones had an adjustment called "anticipator" you set that according to your boiler or furnace type.

Post Reply