Can You Get Condensation Inside A Solid Fuel Boiler?

Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: kstills On: Sat Jan 14, 2012 11:30 am

I've been told no, I've read on here yes.

Verdict?
kstills
Member
 
Posts: 257
Joined: Tue Jan 18, 2011 7:41 am
Location: New Britain, PA
Stove/Furnace Make: Leisure Line
Stove/Furnace Model: LL 110k

Visit Lehigh Anthracite

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: WNY On: Sat Jan 14, 2012 11:35 am

Not any different from any other boiler, if you get down below the dew point, it will condense. I think around 120-130 degrees? I think thats why they tell you not to run below 140 degrees, so it doesn't condense.
User avatar
WNY
Site Moderator
 
Posts: 5452
Joined: Mon Nov 14, 2005 9:40 am
Location: Cuba, NY
Stove/Furnace Make: Keystoker, LL & CoalTrol
Stove/Furnace Model: 90K, Hyfire I, VF3000 Soon

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: jim d On: Sat Jan 14, 2012 12:14 pm

it doesn't have anything to do w/ the fuel it's the dew point temp appox 130 so 140 is a good temp to shoot for this is the return h2o
jim d
Member
 
Posts: 1306
Joined: Mon Dec 08, 2008 8:16 pm
Location: taunton ma
Stove/Furnace Make: alaska//coaljck
Stove/Furnace Model: liberty// cj3

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: kstills On: Sat Jan 14, 2012 12:22 pm

Well then, time to up the high and low limits. :)
kstills
Member
 
Posts: 257
Joined: Tue Jan 18, 2011 7:41 am
Location: New Britain, PA
Stove/Furnace Make: Leisure Line
Stove/Furnace Model: LL 110k

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: coaledsweat On: Sat Jan 14, 2012 12:37 pm

kstills wrote:Verdict?

Running a boiler under 140* is asking for trouble. Oxygen disassociates from water at around 153*. At 130* you are feeding your boiler to the forces of nature.
User avatar
coaledsweat
Site Moderator
 
Posts: 6143
Joined: Fri Oct 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stove/Furnace Model: Axeman-Anderson 260M

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: jim d On: Sat Jan 14, 2012 12:45 pm

make sure you have a bypass to tempe rthe return h2o
jim d
Member
 
Posts: 1306
Joined: Mon Dec 08, 2008 8:16 pm
Location: taunton ma
Stove/Furnace Make: alaska//coaljck
Stove/Furnace Model: liberty// cj3

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: steamup On: Sun Jan 15, 2012 2:45 pm

This is a highly techinical question. In pure theory, coal combustion will not condense like gas and oil combustion. Why, because coal is carbon and when combined with oxygen will result in carbon dioxide. (C + O2 => CO2 (12 kg C)+(32 kg O) => (34 kg CO2) ). Gas and oil are hydrocarbons. When hydrogen is combusted, you get water. (2 H2 + O2 => 2 H2O (4 kg H)+(32 kg O) => (36 kg H2O) ) So, in pure theory, coal will not condense to form water.

However, real world issues are that coal is neither 100 percent pure carbon nor perfectly dry. Therefore, any moisture in the coal that is evaporated during combustion, could condense if there was sufficiently cool enough combustion chamber walls.

The sulfer in the coal is combusted to form sulphur dioxide. (S + O2 => SO2 (32 kg S) + (32 kg O) => (64 kg SO2) ) While the sulphur will not condense until really low temperature, it could combine with the water to form sulphuric acid. (H2SO4). This would attack any metal surface over time.

Another problem is that any water temperature below 140 deg. F., is not very useful for heat. Another topic of concern would be on of thermal shock on cast iron equipment. ( not so much of a concern for welded steel boilers).

So, in conclusion, the rule of thumb of 140 deg. f return may not be as hard and fast for coal, but is a good number to stick with.

Note - wood is a different animal, more moisture content and creosote problems.
User avatar
steamup
Member
 
Posts: 1206
Joined: Fri Oct 03, 2008 12:13 pm
Location: Napoli, NY
Stove/Furnace Make: HS Tarm, Keystoker, Axeman-And
Stove/Furnace Model: Tarm 502 wood/oil, K-6, AA-130

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: kstills On: Sun Jan 15, 2012 2:59 pm

steamup wrote:This is a highly techinical question. In pure theory, coal combustion will not condense like gas and oil combustion. Why, because coal is carbon and when combined with oxygen will result in carbon dioxide. (C + O2 => CO2 (12 kg C)+(32 kg O) => (34 kg CO2) ). Gas and oil are hydrocarbons. When hydrogen is combusted, you get water. (2 H2 + O2 => 2 H2O (4 kg H)+(32 kg O) => (36 kg H2O) ) So, in pure theory, coal will not condense to form water.

However, real world issues are that coal is neither 100 percent pure carbon nor perfectly dry. Therefore, any moisture in the coal that is evaporated during combustion, could condense if there was sufficiently cool enough combustion chamber walls.

The sulfer in the coal is combusted to form sulphur dioxide. (S + O2 => SO2 (32 kg S) + (32 kg O) => (64 kg SO2) ) While the sulphur will not condense until really low temperature, it could combine with the water to form sulphuric acid. (H2SO4). This would attack any metal surface over time.

Another problem is that any water temperature below 140 deg. F., is not very useful for heat. Another topic of concern would be on of thermal shock on cast iron equipment. ( not so much of a concern for welded steel boilers).

So, in conclusion, the rule of thumb of 140 deg. f return may not be as hard and fast for coal, but is a good number to stick with.

Note - wood is a different animal, more moisture content and creosote problems.



Ok, since you used numbers......lol.

If I run a continuous circulation at lower temps, I won't have to worry (much) about condensation and I can run lower water temps which would result in savings on fuel?
kstills
Member
 
Posts: 257
Joined: Tue Jan 18, 2011 7:41 am
Location: New Britain, PA
Stove/Furnace Make: Leisure Line
Stove/Furnace Model: LL 110k

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: Berlin On: Sun Jan 15, 2012 6:05 pm

steamup wrote:This is a highly techinical question. In pure theory, coal combustion will not condense like gas and oil combustion. Why, because coal is carbon and when combined with oxygen will result in carbon dioxide. (C + O2 => CO2 (12 kg C)+(32 kg O) => (34 kg CO2) ). Gas and oil are hydrocarbons. When hydrogen is combusted, you get water. (2 H2 + O2 => 2 H2O (4 kg H)+(32 kg O) => (36 kg H2O) ) So, in pure theory, coal will not condense to form water.

However, real world issues are that coal is neither 100 percent pure carbon nor perfectly dry. Therefore, any moisture in the coal that is evaporated during combustion, could condense if there was sufficiently cool enough combustion chamber walls.

The sulfer in the coal is combusted to form sulphur dioxide. (S + O2 => SO2 (32 kg S) + (32 kg O) => (64 kg SO2) ) While the sulphur will not condense until really low temperature, it could combine with the water to form sulphuric acid. (H2SO4). This would attack any metal surface over time.

Another problem is that any water temperature below 140 deg. F., is not very useful for heat. Another topic of concern would be on of thermal shock on cast iron equipment. ( not so much of a concern for welded steel boilers).

So, in conclusion, the rule of thumb of 140 deg. f return may not be as hard and fast for coal, but is a good number to stick with.

Note - wood is a different animal, more moisture content and creosote problems.


Dewpoint is determined by humidity and temp, which, as steamup has mentioned, coal will have a vastly lower amount of moisture/humidity in its flue gas. condensation with coal anthracite or bit is almost a non-issue unless your coal is dripping wet when it's fired into the boiler.
User avatar
Berlin
Site Moderator
 
Posts: 1540
Joined: Thu Feb 09, 2006 2:25 pm
Location: Buffalo/Adirondacks, NY
Stove/Furnace Make: Will-burt burning BITUMINOUS
Stove/Furnace Model: Model 77 Combustioneer

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: kstills On: Sun Jan 15, 2012 6:37 pm

Berlin wrote:
steamup wrote:This is a highly techinical question. In pure theory, coal combustion will not condense like gas and oil combustion. Why, because coal is carbon and when combined with oxygen will result in carbon dioxide. (C + O2 => CO2 (12 kg C)+(32 kg O) => (34 kg CO2) ). Gas and oil are hydrocarbons. When hydrogen is combusted, you get water. (2 H2 + O2 => 2 H2O (4 kg H)+(32 kg O) => (36 kg H2O) ) So, in pure theory, coal will not condense to form water.

However, real world issues are that coal is neither 100 percent pure carbon nor perfectly dry. Therefore, any moisture in the coal that is evaporated during combustion, could condense if there was sufficiently cool enough combustion chamber walls.

The sulfer in the coal is combusted to form sulphur dioxide. (S + O2 => SO2 (32 kg S) + (32 kg O) => (64 kg SO2) ) While the sulphur will not condense until really low temperature, it could combine with the water to form sulphuric acid. (H2SO4). This would attack any metal surface over time.

Another problem is that any water temperature below 140 deg. F., is not very useful for heat. Another topic of concern would be on of thermal shock on cast iron equipment. ( not so much of a concern for welded steel boilers).

So, in conclusion, the rule of thumb of 140 deg. f return may not be as hard and fast for coal, but is a good number to stick with.

Note - wood is a different animal, more moisture content and creosote problems.


Dewpoint is determined by humidity and temp, which, as steamup has mentioned, coal will have a vastly lower amount of moisture/humidity in its flue gas. condensation with coal anthracite or bit is almost a non-issue unless your coal is dripping wet when it's fired into the boiler.


That's good news, for me at least, and appears to be a little understood benefit of burning coal.

Maybe it needs a sticky...?
kstills
Member
 
Posts: 257
Joined: Tue Jan 18, 2011 7:41 am
Location: New Britain, PA
Stove/Furnace Make: Leisure Line
Stove/Furnace Model: LL 110k

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: cokehead On: Sun Jan 15, 2012 7:06 pm

I believe the question was can you water vapor condensing in the boiler or flue when Running at low stack temps and that has been well covered. I find that when my mini-boiler is out and cold, humidity from the summer air condenses on the cool iron inside and out which causes rust. :mad: In theory the sulfur could react with the condensation exacerbating the problem. I use the mini-boiler to heat the water in a 77 gallon indirect and only run it about 8 hours every 3 days or so. Basically as needed.
User avatar
cokehead
Member
 
Posts: 1527
Joined: Thu Dec 27, 2007 9:28 pm
Location: Mystic, CT
Stove/Furnace Make: Locke, Godin, Tarm in da works
Stove/Furnace Model: Warm Morning 617-A, 3721, 502

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: dave brode On: Sun Jan 15, 2012 7:40 pm

I ruined a very nice 5 section cast iron boiler by running the water temps too low [bit coal, iron fireman stoker]. I ran it 130-140* spring/fall, maybe 160 in cold winter. I thought that I was saving money. It was pristine when I put it into use. It took 17 years, but the apx 3/8" casting were deeply pitting in the upper section.

When cleaning the upper chamber, I did notice that the fly ash was stuck onto the metal, like it was glued on. Not until I joined this group that I learned what was happening.

Dave
User avatar
dave brode
Member
 
Posts: 416
Joined: Fri Jan 15, 2010 6:47 pm
Location: Frostburg, Maryland [western]
Stove/Furnace Make: Keystoker Kaa-2

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: kstills On: Sun Jan 15, 2012 7:55 pm

dave brode wrote:I ruined a very nice 5 section cast iron boiler by running the water temps too low [bit coal, iron fireman stoker]. I ran it 130-140* spring/fall, maybe 160 in cold winter. I thought that I was saving money. It was pristine when I put it into use. It took 17 years, but the apx 3/8" casting were deeply pitting in the upper section.

When cleaning the upper chamber, I did notice that the fly ash was stuck onto the metal, like it was glued on. Not until I joined this group that I learned what was happening.

Dave


Did you run it in the summer, or did you shut it down?

And if you shut it down, did you observe good practice for keeping it dry?
kstills
Member
 
Posts: 257
Joined: Tue Jan 18, 2011 7:41 am
Location: New Britain, PA
Stove/Furnace Make: Leisure Line
Stove/Furnace Model: LL 110k

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: steamup On: Sun Jan 15, 2012 9:18 pm

dave brode wrote:I ruined a very nice 5 section cast iron boiler by running the water temps too low [bit coal, iron fireman stoker]. I ran it 130-140* spring/fall, maybe 160 in cold winter. I thought that I was saving money. It was pristine when I put it into use. It took 17 years, but the apx 3/8" casting were deeply pitting in the upper section.

When cleaning the upper chamber, I did notice that the fly ash was stuck onto the metal, like it was glued on. Not until I joined this group that I learned what was happening.

Dave



Bit coal has lower carbon and higher volatiles. The volatiles (coal tars) will condense at lower temperature and cause a problem. Not as big of a problem with anthracite. Personally, running any boiler temperature setpoints below the 150 to 160 deg. range(on call for heat) is not a good idea, unless the boiler was designed for condensing operation such as the modern gas and oil boilers. I have my K-6 idling at 140 + on the low side of the aquastat. High side setting is 180.
User avatar
steamup
Member
 
Posts: 1206
Joined: Fri Oct 03, 2008 12:13 pm
Location: Napoli, NY
Stove/Furnace Make: HS Tarm, Keystoker, Axeman-And
Stove/Furnace Model: Tarm 502 wood/oil, K-6, AA-130

Re: Can You Get Condensation Inside A Solid Fuel Boiler?

PostBy: Rob R. On: Sun Jan 15, 2012 9:34 pm

I ran my EFM at 140 degrees (max) for part of the summer...after about a month I noticed some funky deposits on the inside of the firebox. It looked like flyash, but was peeling off in small pieces rather than the dusty ash I was used to. I cleaned it out and bumped the aquastat to 160 degrees...after that there was just a light layer of dusty ash that was easily brushed off. I can't say what caused the deposits in the firebox, but whatever it was hasn't returned since the boiler has been allowed to run at higher temperatures.
User avatar
Rob R.
Member
 
Posts: 5028
Joined: Fri Dec 28, 2007 5:26 pm
Location: Chazy, NY
Stove/Furnace Make: EFM
Stove/Furnace Model: 520

Visit Lehigh Anthracite