wilder11354 wrote:are you plumbing 2 boilers into the main primary loop?
wilder11354 wrote:And whats are you doing for flow control(flocheck)
wilder11354 wrote:your exspansion tank is on a dead head leg it looks like.
Flyer5 wrote:Nice Job. Just make sure the PRV is piped away from the Aquastat as well. Dave
dh1200s wrote:
WL110 Settings;
HI limit 180
Low Limit 160
Feed screw 12 turns
Idle fire timer settings 30 sec on 4 min off.
Idle fan at max
Stoker at 10 o’clock position.
Draft around .04 on hi fire no base draft measurement yet.
Over all very pleased with this boiler………..Dick
dh1200s wrote:Hi Dave,
The dump came after extended idle time.
I’m still working thru a L6006A High limit aquastat issue. The issue with that astat is I feel it is way off.
I feel the well is not air bound I have purged it multiple times and I installed forum member “Plumber” Hy Vent” retro ft off the left side port as seen in my previous pics. That was done before fire up.
The bulb is bottomed out in the well and when I saw the big discrepancy of boiler temp indicated by the L7224 (210F) and the trip point of the L6006 (140) I pulled the bulb out and coated with thermal compound reinstalled and no joy.
I need to pull that L6006 astat out and bench test at the kitchen range with my IR temp gun.
I have my LOVE TS2-10 protecting the boiler for Hi temp in the source nipple as see in my previous pics. You will see the LOVE TS-1 probe mounted horizontal in that 1.25 source tee. This set up is very accurate if the pri pump is circulating water in my pri loop. I read the temp from two IR Temp guns a company provided Fluke and my Raytech Mini Temp IR non contact temp gun and I see a 1.5 deg diff between the TS2-10 and both IR temp guns.
I do not have the primary loop pump on 24/7 it only runs on a call for heat so the temp monitored in that 1.25 T indicates low. I set the trip point for 170F on the LOVE TS2-10 and if remember the Temp indicated by the L7224 read 210F on the dump.
I was in the basement when the LOVE TS2-10 signaled my dump zone on via the SR503 pump control for the 1st floor loop. My house was running warm down stairs with the Harmon TLC 2K fired up so I knew it was not a call for heat form the 1st floor stat.
I don’t want to run the pri pump continuous to get accurate boiler temp reading for the Hi Temp astat. So for now what I plan on is to modify a well to accommodate the temp probe sensor for the LOVE TS2-10 in the left side 1.25 port that will get the temp sensor in deep enough for a more accurate monitor of boiler temp. I believe a WL110 owner has done that I need to find that post as see how that mod has worked out. At this point I feel it is the way to go.
I’m a rookie at this so if I’m in left field please point out the error in my troubleshooting and resolution direction.
What success have you, Matt and other users had with the L6006 mounted horizontal position in the source T? Do you run boiler water past the sensor bulb 24/7 or rely on static water temp migration to rise up to the bulb and trigger a Hi Temp dump?
Couple of pics of current HI Temp monitor setup.......wiring clean up in process.............Dick
the 4 minute "off" time seems a little short especially with this weather
It's a good idea to try the different combinations of on and off times to see how it behaves.
I too started with the dump zone setting around 210F and tried 220 and so on and ended up leaving it on 240, mainly for the summer for the extended times of no hot water or heat demand. I was getting stuck in a sequence where the dump zone would kick in, cool the boiler below the low limit, crank up the fire, hit the dump zone and so on again and again.... Raising the dump zone temp and increasing the "off" time helped keep me out of that.
When you mentioned purge I was not sure if you were purging your loops or actuating the pressure blow off near to the L6006A.
dh1200s wrote:the 4 minute "off" time seems a little short especially with this weather
I had been running 1 min on 8 off wanted to give the 30 sec on/4 min off timing a try. I'm new on the learning curve with this boiler and a dump from time to time in the winter is no biggie. I will pull that L6006A and check it out with a pot of boiling water and see where it's trip point is.
I do like the extended burn times of this boiler over my hand fed......dick
NEPA Crossroads is a creation of Nepadigital.Com ©2009 • Contact Admin | Terms of Use | Privacy Policy
Powered by phpBB © phpBB Group