lsayre wrote:L4006A = 180 degrees (turns the fan (or blower) motor on at 170 and shuts it off at 180)
L4081B high limit side = 200 degrees (turns the fan motor off at 200 degrees if the L4006A fails to turn it off at 180)
L4081B dump zone side = 210 degrees (opens the dump zone valve and turns on the circulator at 210 degrees)
Rob R. wrote:Set your S130 to run between 180-190, I bet the draft will improve and the boiler will run more often to maintain temperature.
lsayre wrote:-0.03" sounds quite adequate to me. I'm baffled by your problems. Could there be a blockage somewhere? Where are you seeing the -0.03" mano reading? Where is your manometer take-off located? Mine is only a few inches above the boiler.
Is your sight port cover plate springing open nicely when the fan shuts off? Is it slamming shut tightly when the fan comes on?
Rob R. wrote:It sounds like you have a serious problem with you chimney.
NWBuilder wrote:Yes it is a negative reading. I took the stove pipe apart completely and there may have been 1/2 in of fly ash. I checked the masonry chimney as well clear all the way to the heavens. The cyclonic separator i clear as well. I am trying to relight it now but I don't hold much hope. The manometer is at dead zero right now. Better then negative 3 I guess.