Pressure relief valve leaking

Pressure relief valve leaking

PostBy: chevymatt On: Tue Apr 24, 2012 8:52 pm

Hey guys. I shut down my boiler this past wknd to replace the fan shaft AHS sent me. I refired it Sunday because of the incoming weather and when it got back up to 180* the pressure relief valve kicked and stuck open and ran water all over the top of the boiler soaking the insulation. I pressed it down and released it and got it to stop. I thought it was over but know there is a leak just below the valve and a small amount of steam keeps coming out.

My first question is how do I safely change out the pressure valve? Will any 30psi relief valve work or do I go back to AHS?

Second question is do you think the insulation will dry out and still be effective? My unit is in an out building and I count on it.

Thanks for any input and yes I've learned my lesson about not plumbing in my pressure relief valve.
chevymatt
Member
 
Posts: 71
Joined: Sun Sep 11, 2011 1:51 pm
Location: Oneonta NY
Stove/Furnace Make: AHS
Stove/Furnace Model: S260


Re: Pressure relief valve leaking

PostBy: tsb On: Tue Apr 24, 2012 9:47 pm

The insulation will be fine when it dries out, but the
valve should be piped over the top and down to a few inches
from the floor or to a drain. You'll get a face full of hot water or
steam if you don't pipe it down.
Get a new one while your at it.
User avatar
tsb
Member
 
Posts: 1127
Joined: Wed Jul 30, 2008 8:38 pm
Location: Douglassville, Pa
Stove/Furnace Make: saey/LL Pioneer/Binford Boiler
Stove/Furnace Model: Hanover II/BF 2000

Re: Pressure relief valve leaking

PostBy: whistlenut On: Tue Apr 24, 2012 10:24 pm

You can get the PRV at any plumbing supply house, and probably most Big Box Stores. Matt, they do stick sometimes, particularly when shut down and restarted. Pop it as your boiler fills, and usually they are fine. I must have you convinced that the shaft was your issue. Understand that the shaft seems to differ from machine to machine, but basically unlike AA's, the design is limited in it's ability to cool the shaft; hence sometimes the steel in the shaft gives you fits. Rubber mounts on all AA machines and the fan bearing box have a specific purpose past supporting the shaft and blower wheel. Hope all works out well with the new shaft. ;)

All codes require you to pipe the overflow pipe to within 12" of the floor the boiler sits on. 240 degree steam would ruin your day and every day after...if you survived the blast of hot water and steam. Code also says 'rigid piping' for all drains, no pex (can't take the heat?
User avatar
whistlenut
State of New Hampshire Moderator
 
Posts: 2742
Joined: Sat Mar 17, 2007 6:29 pm
Location: Central NH, Concord area
Stove/Furnace Make: AA130's/AA260's,AHS 130's-260
Stove/Furnace Model: GJ 600,EFM DF520-900 VWert 600

Re: Pressure relief valve leaking

PostBy: jim d On: Tue Apr 24, 2012 11:26 pm

doug i think the code also calls for non ferros on the piping
jim d
Member
 
Posts: 1306
Joined: Mon Dec 08, 2008 8:16 pm
Location: taunton ma
Stove/Furnace Make: alaska//coaljck
Stove/Furnace Model: liberty// cj3

Re: Pressure relief valve leaking

PostBy: whistlenut On: Wed Apr 25, 2012 7:28 am

I'm sure you are correct, Jim. We both have seen galvie or black iron for 50 years, but all brand new installs are copper....with a union so you can take it apart without any effort to replace a leaking PRV......next year or whenever.
Any inspector would fail it without copper, BUT, there are frequently no inspectors checking. Most gas or oil burner techs will tag a boiler and recommend replacement or put it out of service. 200 degree water or worse yet 212 steam will MORE than get your attention. As Jim will relate, most of us replace the PTV if there is a hint or dripping simply because it make a damned mess of whatever it drips on. Orange concrete floors, rust steel if not piped properly...

If you are rehabbing an older boiler of whatever fuel, always replace the PRV. $35.00 or there abouts. :idea: ;)
User avatar
whistlenut
State of New Hampshire Moderator
 
Posts: 2742
Joined: Sat Mar 17, 2007 6:29 pm
Location: Central NH, Concord area
Stove/Furnace Make: AA130's/AA260's,AHS 130's-260
Stove/Furnace Model: GJ 600,EFM DF520-900 VWert 600

Re: Pressure relief valve leaking

PostBy: chevymatt On: Wed Apr 25, 2012 7:32 am

Thanks for the help guys. Still one question remaining. How do I change out the PRV? do i have to drain the unit or just let it cool and relief the pressure? I realize theres a huge potential for injury and dont want to be on the receiving end of a steam bath. Thanks again for all the great help.

Whistlenut, I truly appreciate all the help you given me. If it wasn't for you I probably would have blown the damn thing up by now.
chevymatt
Member
 
Posts: 71
Joined: Sun Sep 11, 2011 1:51 pm
Location: Oneonta NY
Stove/Furnace Make: AHS
Stove/Furnace Model: S260

Re: Pressure relief valve leaking

PostBy: Rob R. On: Wed Apr 25, 2012 8:19 am

Hey Matt - What are you using for an expansion tank on that beast? I have a suspicion that it may be undersized.

As for the PRV swap, you just need to drain the boiler down until there is zero pressure. You can change it with the boiler warm, but if you aren't comfortable with that let it cool first. Don't forget some pipe dope for the threads, and when you run the pipe down towards the floor make sure you install a union near the PRV itself...that way if you need to change it again it will be a simple task.

I wasn't aware the "blow off tube" had to be copper, but I did know the end cannot be threaded...that way someone can't screw on a cap to "fix" a leaking PRV.
User avatar
Rob R.
Member
 
Posts: 5028
Joined: Fri Dec 28, 2007 5:26 pm
Location: Chazy, NY
Stove/Furnace Make: EFM
Stove/Furnace Model: 520

Re: Pressure relief valve leaking

PostBy: hophead On: Wed Apr 25, 2012 2:23 pm

It should terminate no more than 1 and 1/2 times the diameter of the pipe from the floor.
hophead
Member
 
Posts: 226
Joined: Tue Jun 03, 2008 8:00 pm
Location: Sch County
Stove/Furnace Make: efm520

Re: Pressure relief valve leaking

PostBy: whistlenut On: Wed Apr 25, 2012 7:56 pm

Matt, changing the PRV should be simple.....I NEVER drain the boiler much below the PRV.......turn it off, close ALL the valves to and from the boiler, then hook up a hose to the boiler drain. Open the drain, then when pressure on the Tridacator goes to 'zero', I also open the PRV by hand. I then loosen and remove the PRV valve and check to see where the liquid level is in the boiler. If below the threads, remove, and reinstall the new PRV already tefloned and gooped. Shut off the drain hose quickly. Tighten the PRV, and I start refilling the boiler immediately...as I reassemble the drain piping. I know that the drain pipe is suppose to be a couple inches off the floor, however most of us crusty old turds leave it up about 10" SO THAT WE CAN GET A 5 GALLON BUCKET UNDER THAT DRAIN PIPE. I don't really care about the 2"off the floor issue, because the bucket stays in place...just so we can 'bump' the valve a few times. WHEN the testing is completed we will add more copper if required; some folks like to test the valve occasionally. :idea: :!: :shock:
User avatar
whistlenut
State of New Hampshire Moderator
 
Posts: 2742
Joined: Sat Mar 17, 2007 6:29 pm
Location: Central NH, Concord area
Stove/Furnace Make: AA130's/AA260's,AHS 130's-260
Stove/Furnace Model: GJ 600,EFM DF520-900 VWert 600

Re: Pressure relief valve leaking

PostBy: jim d On: Wed Apr 25, 2012 11:34 pm

hoppy i would like to see that in wrighting ,the only thing that comes to mind with the 1&1/2 times the diameter is the distance between the 1st. elbow & the suction sid of a pump or circ to prevent cavatating , my code book reads 8 to 12 " if the boiler is on the lowest floor of the structure , if not then the drain must be piped all the way to it
jim d
Member
 
Posts: 1306
Joined: Mon Dec 08, 2008 8:16 pm
Location: taunton ma
Stove/Furnace Make: alaska//coaljck
Stove/Furnace Model: liberty// cj3

Re: Pressure relief valve leaking

PostBy: whistlenut On: Thu Apr 26, 2012 8:20 am

I am not familiar with the 1' to 2" reg either. 10" is enough to make anyone want to have a Chubby....coal stove anyway. 1" to 2", not so much. I suppose that is what some guys carry a spare shoe string for..... or depends......

We will get to the bottom of this issue for Hop, but 10" to 12" is a number that makes me proud to know the correct answer. The all copper drain piping I was not aware of, if so, shame on me. I use copper just because it is there when trimming the boiler, but I've seen hundreds of boilers in black iron and galvie. Everyday we learn...... :idea: :!:
User avatar
whistlenut
State of New Hampshire Moderator
 
Posts: 2742
Joined: Sat Mar 17, 2007 6:29 pm
Location: Central NH, Concord area
Stove/Furnace Make: AA130's/AA260's,AHS 130's-260
Stove/Furnace Model: GJ 600,EFM DF520-900 VWert 600

Re: Pressure relief valve leaking

PostBy: steamup On: Thu Apr 26, 2012 3:09 pm

All copper?? certain distance from floor??? - just curious - what code does this come from.

The international building code states-

1006.6 Safety and relief valve discharge.
Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. The discharge pipe shall be the same diameter as the safety or relief valve outlet. Safety and relief valves shall not discharge so as to be a hazard, a potential cause of damage or otherwise a nuisance. Highpressure-steam safety valves shall be vented to the outside of the structure. Where a low-pressure safety valve or a relief valve discharges to the drainage system, the installation shall conform to the International Plumbing Code.

I know various states like to modify things. Here in NYS-

1006.6 Safety and relief valve discharge.
Safety and relief valve discharge pipes shall be of rigid pipe that is approved for the temperature of the system. The discharge pipe shall be the same diameter as the safety or relief valve outlet. Safety and relief valves shall not discharge so as to be a hazard, a potential cause of damage or otherwise a nuisance. High-pressure-steam safety valves shall be vented to the outside of the structure. Where a low-pressure safety valve or a relief valve discharges to the drainage system, the installation shall conform to the Plumbing Code of New York State.

Look similar - it is. Most states are adopting a version of the international building code.

However local codes can be more restrictive.

It is tough to keep up on the codes - especially from more than one state.
User avatar
steamup
Member
 
Posts: 1206
Joined: Fri Oct 03, 2008 12:13 pm
Location: Napoli, NY
Stove/Furnace Make: HS Tarm, Keystoker, Axeman-And
Stove/Furnace Model: Tarm 502 wood/oil, K-6, AA-130

Re: Pressure relief valve leaking

PostBy: tsb On: Thu Apr 26, 2012 3:30 pm

I don't care about codes, I just don't want hot water in the face.
If my insurance man ever did a real inspection, he'd *censored* a brick.
Last edited by tsb on Thu Apr 26, 2012 8:47 pm, edited 1 time in total.
User avatar
tsb
Member
 
Posts: 1127
Joined: Wed Jul 30, 2008 8:38 pm
Location: Douglassville, Pa
Stove/Furnace Make: saey/LL Pioneer/Binford Boiler
Stove/Furnace Model: Hanover II/BF 2000

Re: Pressure relief valve leaking

PostBy: jim d On: Thu Apr 26, 2012 6:04 pm

it's ma state code and i looked it upthis am 12 t0 15''' off the flooor
jim d
Member
 
Posts: 1306
Joined: Mon Dec 08, 2008 8:16 pm
Location: taunton ma
Stove/Furnace Make: alaska//coaljck
Stove/Furnace Model: liberty// cj3

Re: Pressure relief valve leaking

PostBy: steamup On: Fri Apr 27, 2012 8:45 am

jim d wrote:it's ma state code and i looked it upthis am 12 t0 15''' off the flooor



Good to know where it comes from. Each state has some perculiar specifics in their codes.
User avatar
steamup
Member
 
Posts: 1206
Joined: Fri Oct 03, 2008 12:13 pm
Location: Napoli, NY
Stove/Furnace Make: HS Tarm, Keystoker, Axeman-And
Stove/Furnace Model: Tarm 502 wood/oil, K-6, AA-130