I'm sure you are correct, Jim. We both have seen galvie or black iron for 50 years, but all brand new installs are copper....with a union so you can take it apart without any effort to replace a leaking PRV......next year or whenever.
Any inspector would fail it without copper, BUT, there are frequently no inspectors checking. Most gas or oil burner techs will tag a boiler and recommend replacement or put it out of service. 200 degree water or worse yet 212 steam will MORE than get your attention. As Jim will relate, most of us replace the PTV if there is a hint or dripping simply because it make a damned mess of whatever it drips on. Orange concrete floors, rust steel if not piped properly...
If you are rehabbing an older boiler of whatever fuel, always replace the PRV. $35.00 or there abouts.