Corrosion at Fittings Where Copper Contacts Black Iron???

Post Reply
 
Fran654
Member
Posts: 134
Joined: Tue. Apr. 01, 2008 7:59 pm

Post by Fran654 » Fri. Sep. 21, 2012 10:06 pm

hello all, hooked my boiler up last year , now its gettin cool and we are talkin about heat for the winter,,, a steam fitter on the job and another mason told me that you cant put copper to black iron ,or steel/ said elecltrolisis wil happen and corrod the fittings, the fitter said I should put and electostat ????? union in .. basically a steel nipple out of the boiler then this special union then tne copper pipe..now is this that serious to worry, and change my set up or not... to change my plumbig I have to shut down , runnin an aa130 24/7 year round ... your t5houghts are apprecieted thank you , tommy I guess I need to know if this corrosion will blow out the fittings in 1 year or 20 yrs????
Last edited by Fran654 on Fri. Sep. 21, 2012 10:17 pm, edited 1 time in total.

 
User avatar
carlherrnstein
Member
Posts: 1536
Joined: Tue. Feb. 07, 2012 8:49 am
Location: Clarksburg, ohio
Hot Air Coal Stoker Stove: combustioneer model 77B
Coal Size/Type: pea stoker/Ohio bituminous

Post by carlherrnstein » Fri. Sep. 21, 2012 10:12 pm

You pretty much answered your question.

 
jim d
Member
Posts: 1271
Joined: Mon. Dec. 08, 2008 7:16 pm
Location: taunton ma
Contact:

Post by jim d » Fri. Sep. 21, 2012 11:48 pm

that is a bunch of bullcrap 1st of all it's called a dielectric union , 2nd the only places we ever used them was on gov. & large prevailling wage jobs where a mecanical engineer did the plans &specks , if you ggo into any celler , basement or residential boiler room churches ect. you will find c x m adpts screwed into b/m & ci fittings and they will outlast the boiler AMEN nuff said jim


 
User avatar
coaledsweat
Site Moderator
Posts: 13763
Joined: Fri. Oct. 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stoker Coal Boiler: Axeman Anderson 260M
Coal Size/Type: Pea

Post by coaledsweat » Sat. Sep. 22, 2012 7:49 am

Unless you are operating your boiler submerged in seawater, I wouldn't worry about it.

 
User avatar
steamup
Member
Posts: 1209
Joined: Fri. Oct. 03, 2008 12:13 pm
Location: Napoli, NY
Stoker Coal Boiler: Axeman-Anderson AA-130, Keystoker K-6
Hand Fed Coal Boiler: HS Tarm 502 Wood/Coal/Oil
Coal Size/Type: pea, buck, rice

Post by steamup » Sun. Sep. 23, 2012 12:54 pm

Corrosion occurs when oxygen is present in the fluid. On a sealed hydronic heating system there should be no problem with electrolysis. If you had a domestic water system, where there is a constant supply of fresh water, then di-electric unions should be used between iron and copper pipes.