thermal reset button on efm coal Air furnace

thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Wed Nov 07, 2012 11:57 am

Coal furnace keeps shuting down over night and going out. Hit reset button and the blower and auger start back up but of course I have to relight. If i lower the blower speed it seems like the coal does not burn all the way. Auger is set on two right now. Hard to figure out the perfect setting.
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af

Re: thermal reset button on efm coal Air furnace

PostBy: Rob R. On: Wed Nov 07, 2012 12:40 pm

What are you using for a timer setting? Any idea if the draft is correct?
Rob R.
 
Stoker Coal Boiler: EFM DF520
Hand Fed Coal Stove: Hitzer 50-93
Other Heating: Dad's 1953 EFM Highboy

Re: thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Wed Nov 07, 2012 7:18 pm

I checked the draft and it goes way up to - 17pa as the chimney warms up. when I open the damper all the way it clicks a couple times and the shuts off.
Attachments
P1010248.JPG
(114.1 KiB) Viewed 15 times
View: New PagePopup • Select:BBCode
[nepathumb]37701[/nepathumb]
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af

Visit Lehigh Anthracite

Re: thermal reset button on efm coal Air furnace

PostBy: Rob R. On: Wed Nov 07, 2012 7:22 pm

I had a brain fade earlier...if the reset button on the motor is popping it is probably time for a new motor. Maybe you can buy some time by oiling it.
Rob R.
 
Stoker Coal Boiler: EFM DF520
Hand Fed Coal Stove: Hitzer 50-93
Other Heating: Dad's 1953 EFM Highboy

Re: thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Wed Nov 07, 2012 7:28 pm

this is a photo, what is the thing upper right of the unit. If i hold up it runs. I put 3 in 1 oil in the little port.
Attachments
P1010252.JPG
(82.31 KiB) Viewed 32 times
View: New PagePopup • Select:BBCode
[nepathumb]37703[/nepathumb]
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af

Re: thermal reset button on efm coal Air furnace

PostBy: Scottscoaled On: Wed Nov 07, 2012 7:46 pm

Looks to me like a starting relay. That should start your stoker. There should be a black/red wire on terminal 4 that goes to your stoker motor.
Last edited by Scottscoaled on Wed Nov 07, 2012 8:30 pm, edited 1 time in total.
Scottscoaled
 
Stoker Coal Boiler: EFM 520x3, 700 Van Wert 800
Hot Air Coal Stoker Furnace: EFM 150, Keystoker 150
Coal Size/Type: Lots of buck

Re: thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Wed Nov 07, 2012 8:07 pm

If I hold this shut/open it runs.
Attachments
P1010252.JPG
(60.8 KiB) Viewed 21 times
View: New PagePopup • Select:BBCode
[nepathumb]37704[/nepathumb]
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af

Re: thermal reset button on efm coal Air furnace

PostBy: Rob R. On: Wed Nov 07, 2012 8:10 pm

That should not have anything to do with the reset button on the motor.

If the motor is able to run, closing that relay you pointed at would start the motor.
Rob R.
 
Stoker Coal Boiler: EFM DF520
Hand Fed Coal Stove: Hitzer 50-93
Other Heating: Dad's 1953 EFM Highboy

Re: thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Wed Nov 07, 2012 8:16 pm

Yep it runs if I close that relay. So I get it started it will run for awhile. Then in the morning or after a couple hours I will go down and the motor will have a slight hum buzz push that red button and it start up.
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af

Re: thermal reset button on efm coal Air furnace

PostBy: Rob R. On: Wed Nov 07, 2012 8:18 pm

Replace the motor.
Rob R.
 
Stoker Coal Boiler: EFM DF520
Hand Fed Coal Stove: Hitzer 50-93
Other Heating: Dad's 1953 EFM Highboy

Re: thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Wed Nov 07, 2012 8:20 pm

I did add oil to this port. Not very much though how much should it hold?
Attachments
P1010248.JPG
(74.76 KiB) Viewed 12 times
View: New PagePopup • Select:BBCode
[nepathumb]37705[/nepathumb]
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af

Re: thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Wed Nov 07, 2012 8:21 pm

Really, are you certain. Why does it run some?
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af

Re: thermal reset button on efm coal Air furnace

PostBy: Scottscoaled On: Wed Nov 07, 2012 8:32 pm

Replace motor #2
Scottscoaled
 
Stoker Coal Boiler: EFM 520x3, 700 Van Wert 800
Hot Air Coal Stoker Furnace: EFM 150, Keystoker 150
Coal Size/Type: Lots of buck

Re: thermal reset button on efm coal Air furnace

PostBy: oilman On: Wed Nov 07, 2012 10:32 pm

That is a very old motor. Needs a new one.
oilman
 

Re: thermal reset button on efm coal Air furnace

PostBy: minnick95@live.com On: Thu Nov 08, 2012 8:56 am

so I messed with the timer a lot and got it to run 10 on 18 off it ran all night in the morning the house was 73 degrees at the thermostat. so i waited for it to time out and shut down. Then ran the t stat up passed 73 did not come on strange because it was runninig with the t sat last week. T stat is digital and new. I think the moter is ok, but your right it is old.
minnick95@live.com
 
Stove/Furnace Make: efm
Stove/Furnace Model: af