By: whistlenut On: Sun Nov 25, 2012 9:34 am
The wiring has been modified, and it is not correct. The combustion fan should be on 24/7, and the timer maintains minimum fire. Perhaps there is a relay for the stoker stove to circulate hot air when the stove temp reaches 140 degrees. Look at the Keystoker site, or call them in the am if you don't get enough relief. There should be a 120V relay like a Honeywell RA89 to accept the TT which you may not have. I just looked at mine in my garage and thought someone might have removed yours.
It came from the factory with one, and is the means by which a thermostat can be used to control the stoker feed motor, hence duration of run time to add coal to the carpet. Look it over, all there is on the back is a stoker motor, combustion fan, and a circulation fan.....plus the RA89 relay to control the carpet. The timer is used to maintain fire when there is no call for heat, and is usually set at 1 minutes on, 10 minutes off. You will have to experiment with the settings if you have any out=fires. We need a model number.....and a picture of the rear of the stove. The model number is usually on the lower left or right....not sure on yours.....