By: Boots On: Wed Dec 12, 2012 5:07 pm
LS,
The make up water does feed directly into my cast iron oil fired boiler.
Sting,
short answer, Yes.
I have drained my boiler when hot before. And have done some purging. I have hose bib drain valves the i purge the air from, and i have a heavy duty hose with "water hose" ends that i place the discharge end of into a bucket. I have done this cold a few times, and purged a lot of air from the system. and i have done it hot only a hand full of times, but do not normally get enough air out that it needs to displace it with makeup water.
Last night i noticed that i could hear air bubbles as the main circulator ran. when the house was up to temp i decided to purge the air. I got enough air/water out that it dropped the pressure enough to allow makeup water to flow. I stopped purging the instant i heard it. I figured that it could cause an issue, but wanted to be sure.