Post by Lightning » Sun. Jan. 13, 2013 10:06 am

Rigar wrote:....do you have a baro installed ?
A baro helps a tame a strong draft but doesn't help a weak one..
Rigar wrote:....in the summer ?
No, I don't burn in the summer.. But I do idle it thru warm days on the shoulder months, thats when I risk draft failure.

 
Rigar
Member
Posts: 856
Joined: Tue. Dec. 04, 2012 6:30 am
Location: central new york (syracuse area)
Hot Air Coal Stoker Furnace: Keystoker A 150
Coal Size/Type: anthracite rice

Post by Rigar » Sun. Jan. 13, 2013 10:20 am

Rigar wrote:....do you have a baro installed ?
A baro helps a tame a strong draft but doesn't help a weak one "

...but HEAT will

 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Sun. Jan. 13, 2013 5:04 pm

Interesting...

Here's my $.02...

How about a "repeat timer" with a "stack temp switch" supervising it...only "repeats" if "stack" temp falls below the set point of "switch". :)

This is a highly adjustable circuit...One can adjust the "timer"...and even adjust the "stack switch" set point, allowing a nice range for "fine tuning".

 
Rigar
Member
Posts: 856
Joined: Tue. Dec. 04, 2012 6:30 am
Location: central new york (syracuse area)
Hot Air Coal Stoker Furnace: Keystoker A 150
Coal Size/Type: anthracite rice

Post by Rigar » Sun. Jan. 13, 2013 5:15 pm

McGiever makes a great point...and I thought some sort of timer was understood

...2 more cents from me
...the timer should be "retriggerable"......so the cycle RESTARTS each time its enegized
...other wise it could potentially be in its "OFF" time when it is called upon...and depending on your repeat parameters...you could still lose draft all together while it "catches up"


 
User avatar
lsayre
Member
Posts: 21781
Joined: Wed. Nov. 23, 2005 9:17 pm
Location: Ohio
Stoker Coal Boiler: AHS S130 Coal Gun
Coal Size/Type: Lehigh Anthracite Pea
Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75

Post by lsayre » Sun. Jan. 13, 2013 5:22 pm

The TORK EJWT "Percentage Timer" resets itself and starts counting time all over again from zero every time the current feeding it is dropped. A relay can be incorporated to drop the current to the timer whenever the stack is hot enough to draft sufficiently.

 
Rigar
Member
Posts: 856
Joined: Tue. Dec. 04, 2012 6:30 am
Location: central new york (syracuse area)
Hot Air Coal Stoker Furnace: Keystoker A 150
Coal Size/Type: anthracite rice

Post by Rigar » Mon. Jan. 14, 2013 9:54 am

Rigar wrote:McGiever makes a great point...and I thought some sort of timer was understood

...2 more cents from me
...the timer should be "retriggerable"......so the cycle RESTARTS each time its enegized
...other wise it could potentially be in its "OFF" time when it is called upon...and depending on your repeat parameters...you could still lose draft all together while it "catches up"
...i meant "one shot"..... triggerable or non should not really matter in your case... As you would be looking for a short fire to regain draft only...
... I get these terms confused all the time... sorry

p.s. MACROMATIC makes a huge selection of these type of timers.... and they are very affordable

 
User avatar
Rob R.
Site Moderator
Posts: 18004
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Mon. Jan. 14, 2013 11:56 am

I have a Macromatic repeat-cycle relay on my EFM...part # TR-63122. It restarts the cycle when the power is cycled. Mine begins with the "off cycle", but you they make one that beings with "on" as well.