The air vent riding above my boilers air separator and expansion tank has suddenly begun to leak water from the air bleed, and I have shut if off (screwed it down tight). Any ideas as to why this might happen?

 
bksaun
Member
Posts: 1037
Joined: Sat. Oct. 28, 2006 9:24 am
Location: Hustonville, Ky
Hand Fed Coal Boiler: Legacy SF-270
Hand Fed Coal Stove: Hitzer 503
Coal Size/Type: Stoker/Bit, Pea or Nut Anthracite

Post by bksaun » Fri. Apr. 19, 2013 8:43 pm

Most likely it has a piece of dirt or rust scale under the seat, or the seat is worn out depending on the age and how often it opens. On mine they can be taken apart and cleaned, if that wont work they are not terribly expensive and easy to replace.

Bk

 
User avatar
lsayre
Member
Posts: 21781
Joined: Wed. Nov. 23, 2005 9:17 pm
Location: Ohio
Stoker Coal Boiler: AHS S130 Coal Gun
Coal Size/Type: Lehigh Anthracite Pea
Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75

Post by lsayre » Fri. Apr. 19, 2013 9:02 pm

Thanks! I'll pick up a spare before attempting to fix it. The leak is minimal, but persistent.

 
User avatar
coalkirk
Member
Posts: 5185
Joined: Wed. May. 17, 2006 8:12 pm
Location: Forest Hill MD
Stoker Coal Boiler: 1981 EFM DF520 retired
Hand Fed Coal Stove: Jotul 507 on standby
Coal Size/Type: Lehigh anthracite/rice coal

Post by coalkirk » Fri. Apr. 19, 2013 9:57 pm

lsayre wrote:Thanks! I'll pick up a spare before attempting to fix it. The leak is minimal, but persistent.
When you replace it, put a shut off valve between it and the air separator. You will need to repalce it again and it makes it much easier.


 
User avatar
lsayre
Member
Posts: 21781
Joined: Wed. Nov. 23, 2005 9:17 pm
Location: Ohio
Stoker Coal Boiler: AHS S130 Coal Gun
Coal Size/Type: Lehigh Anthracite Pea
Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75

Post by lsayre » Fri. Apr. 19, 2013 10:04 pm

coalkirk wrote:When you replace it, put a shut off valve between it and the air separator. You will need to repalce it again and it makes it much easier.
Excellent advice. Thank you!!!

 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Sat. Apr. 20, 2013 5:22 am

Unless there's already a shut off under the vent they can be a pain to replace. You need to drop the pressure off the system....or at least let it cool down & prepare to take a shower. It's amazing how much water can floe from a small hole at 18 PSI. When you drop the pressure, you risk letting air into the system & now you must purge each and every zone....unless all zone have valves & you took the time to close them all, then purge the header pipe. But, for sure, spend the extra $2.80 and put a mini valve under the vent...do ALL the vents is there's more than one.

 
User avatar
lsayre
Member
Posts: 21781
Joined: Wed. Nov. 23, 2005 9:17 pm
Location: Ohio
Stoker Coal Boiler: AHS S130 Coal Gun
Coal Size/Type: Lehigh Anthracite Pea
Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75

Post by lsayre » Sat. Apr. 20, 2013 5:24 am

Freddy wrote:Unless there's already a shut off under the vent they can be a pain to replace. You need to drop the pressure off the system....or at least let it cool down & prepare to take a shower. It's amazing how much water can floe from a small hole at 18 PSI. When you drop the pressure, you risk letting air into the system & now you must purge each and every zone....unless all zone have valves & you took the time to close them all, then purge the header pipe. But, for sure, spend the extra $2.80 and put a mini valve under the vent...do ALL the vents is there's more than one.
I have 3 vents. Only the one is leaking.

 
User avatar
blrman07
Member
Posts: 2383
Joined: Mon. Sep. 27, 2010 3:39 pm
Location: Tupelo Mississippi

Post by blrman07 » Sat. Apr. 20, 2013 8:28 am

Replace all three while your at it. Save yourself some aggravation later. If one is leaking the other two can't be far behind!


 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Sat. Apr. 20, 2013 9:47 am

blrman07 wrote:Replace all three while your at it.
I wouldn't necessarily do that, but, I most certainly would put a valve under each one. I think I might buy a spare vent for the shelf, but I wouldn't use it til I needed to. Vents are quirky little fellows.... some will go about forever, others seem to leak in a short time.

 
User avatar
Rick 386
Member
Posts: 2508
Joined: Mon. Jan. 28, 2008 4:26 pm
Location: Royersford, Pa
Stoker Coal Boiler: AA 260 heating both sides of twin farmhouse
Hot Air Coal Stoker Stove: LL Hyfire II w/ coaltrol in garage
Coal Size/Type: Pea in AA 260, Rice in LL Hyfire II
Other Heating: Gas fired infared at work
Contact:

Post by Rick 386 » Sat. Apr. 20, 2013 11:11 am

coalkirk wrote: When you replace it, put a shut off valve between it and the air separator. You will need to repalce it again and it makes it much easier.
Freddy wrote:Unless there's already a shut off under the vent they can be a pain to replace. You need to drop the pressure off the system....or at least let it cool down & prepare to take a shower. It's amazing how much water can floe from a small hole at 18 PSI.............
Why weren't these tips posted before ????

Drop the temp and pressure ???? No, I wanted to get a bath with hot water and then attempt to hold my thumb over the hole until that got too hot so I removed my thumb.... you see where this is going...............

Never thought about the little valve.

I think I will be doing that to each vent this summer when I do the rebuild.

Great great advice. That is why I love this forum so much.

Rick

 
User avatar
Rob R.
Site Moderator
Posts: 18004
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Sat. Apr. 20, 2013 1:22 pm

Rick, search Yanche's old posts...he has recommended the isolation valves for a long time and posted picture.

Webstone makes a nice valve/drain setup for an expansion tank.

 
User avatar
Rick 386
Member
Posts: 2508
Joined: Mon. Jan. 28, 2008 4:26 pm
Location: Royersford, Pa
Stoker Coal Boiler: AA 260 heating both sides of twin farmhouse
Hot Air Coal Stoker Stove: LL Hyfire II w/ coaltrol in garage
Coal Size/Type: Pea in AA 260, Rice in LL Hyfire II
Other Heating: Gas fired infared at work
Contact:

Post by Rick 386 » Sat. Apr. 20, 2013 4:13 pm

Rob.

I was looking at this as something to use on the bleeders on the radiators. Not for the expansion tank. I already have a valve there.

Here we have bleeders on each and every radiator. Within the past few years, I have replaced every bleeder with "automatic" bleeders. Prior to we still used the old keys to bleed them.

Rick