RIB relay 2401D

RIB relay 2401D

PostBy: wilder11354 On: Fri Sep 06, 2013 9:21 pm

http://www.functionaldevices.com/images/diagrams/RIB2401D.jpg

On left side of relay shows COM, 24VDC leg, 120V leg. ? is can 24V also be used instead of 120V on that leg?
wilder11354
 
Hand Fed Coal Boiler: Harman SF260
Coal Size/Type: nut or pea, anthracite
Other Heating: crown oil boiler, backup.if needed

Re: RIB relay 2401D

PostBy: jpete On: Fri Sep 06, 2013 9:54 pm

It's my understanding that low voltage can be used through high voltage contacts with no issue.

Not sure on a coil like this. Maybe too much resistance through the whole coil for 24V to work?
jpete
 
Hand Fed Coal Stove: Harman Mk II
Coal Size/Type: Stove, Nut, Pea
Other Heating: Dino juice

Re: RIB relay 2401D

PostBy: Scottscoaled On: Fri Sep 06, 2013 10:09 pm

Put 24volts to the white/yellow striped wire and white/blue striped wire, the contacts will cycle. Put 115volts to the white/yellow striped wire and the white/black striped wire, the contacts will cycle. Wire nut off the wire not being used.
Scottscoaled
 
Stoker Coal Boiler: EFM 520x4, 700. Van Wert 1200.
Hot Air Coal Stoker Furnace: EFM 150, Keystoker 150
Coal Size/Type: Lots of buck


Re: RIB relay 2401D

PostBy: wilder11354 On: Sat Sep 07, 2013 7:51 pm

Thanks Scottcoaled... what i needed to know.
wilder11354
 
Hand Fed Coal Boiler: Harman SF260
Coal Size/Type: nut or pea, anthracite
Other Heating: crown oil boiler, backup.if needed

Re: RIB relay 2401D

PostBy: 2001Sierra On: Sat Sep 07, 2013 9:12 pm

I am using a RIB they are the nuts, will activate with multiple voltages as you found out, wire nut the unused.
2001Sierra
 
Hot Air Coal Stoker Stove: Keystoker 90 Chimney vent
Coal Size/Type: Rice
Other Heating: Buderus Oil Boiler 3115-34
Stove/Furnace Model: Keystoker 90 Chimney Vent