Timer Wiring Question

Post Reply
 
User avatar
thegreatone
Member
Posts: 71
Joined: Sat. Aug. 19, 2006 6:07 am
Stoker Coal Boiler: 1981 EFM DF520
Hand Fed Coal Stove: Currently: Hitzer 30-95 Previously:TLC2000, Hitzer 82, Warm Morning 400A
Coal Size/Type: rice/nut

Post by thegreatone » Tue. Nov. 19, 2013 1:24 pm

I have a question. Am I correct in thinking that #4 from the timer goes to ZR? Also where does the neutral from the relay for zone 2 tie in on the triple aqua-stat?

Thanks

 
User avatar
Rob R.
Site Moderator
Posts: 18009
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Tue. Nov. 19, 2013 1:35 pm

thegreatone wrote:Am I correct in thinking that #4 from the timer goes to ZR?
Yes, assuming you are using a Will-burt timer. Note that you also need to install a jumper from #1 to #3.
thegreatone wrote:Also where does the neutral from the relay for zone 2 tie in on the triple aqua-stat?
It doesn't have to "tie in" to the triple at all, you can easily put a j-box ahead of the triple aquastat and route power/neutral from there to the additional zone relays.

Are you using a tankless coil in the boiler?

 
User avatar
thegreatone
Member
Posts: 71
Joined: Sat. Aug. 19, 2006 6:07 am
Stoker Coal Boiler: 1981 EFM DF520
Hand Fed Coal Stove: Currently: Hitzer 30-95 Previously:TLC2000, Hitzer 82, Warm Morning 400A
Coal Size/Type: rice/nut

Post by thegreatone » Tue. Nov. 19, 2013 2:28 pm

Rob R. wrote:
thegreatone wrote:Am I correct in thinking that #4 from the timer goes to ZR?
Yes, assuming you are using a Will-burt timer. Note that you also need to install a jumper from #1 to #3.
thegreatone wrote:Also where does the neutral from the relay for zone 2 tie in on the triple aqua-stat?
It doesn't have to "tie in" to the triple at all, you can easily put a j-box ahead of the triple aquastat and route power/neutral from there to the additional zone relays.

Are you using a tankless coil in the boiler?
The 1 & 3 are bonded.

Yes I am using a tankless coil in the boiler. Why do you ask?

Thank you


 
User avatar
Rob R.
Site Moderator
Posts: 18009
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Tue. Nov. 19, 2013 3:20 pm

If you are going to use the tankless, and the additional zones are large enough to drop the boiler below the low limit setting, you should power the circulator via the ZC terminal. This will stop the circulator if the boiler drops below the LL setting, and allow the tankless to continue producing domestic hot water.

EFM's wiring diagram in the 520 manual shows how to hook it up.

 
User avatar
thegreatone
Member
Posts: 71
Joined: Sat. Aug. 19, 2006 6:07 am
Stoker Coal Boiler: 1981 EFM DF520
Hand Fed Coal Stove: Currently: Hitzer 30-95 Previously:TLC2000, Hitzer 82, Warm Morning 400A
Coal Size/Type: rice/nut

Post by thegreatone » Tue. Nov. 19, 2013 5:41 pm

I got it all squared away. Thank you for the help.