Yellow Flame, A Christmas Stoker Boiler

 
User avatar
coalkirk
Member
Posts: 5185
Joined: Wed. May. 17, 2006 8:12 pm
Location: Forest Hill MD
Stoker Coal Boiler: 1981 EFM DF520 retired
Hand Fed Coal Stove: Jotul 507 on standby
Coal Size/Type: Lehigh anthracite/rice coal

Post by coalkirk » Thu. Dec. 26, 2013 10:14 am

I don't think you mentioned an expansion tank which is a must. Sizing it correctly can eliminate the need for a dump zone. Member Yanche has posted tutorials on this topic.


 
User avatar
Rob R.
Site Moderator
Posts: 17965
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Thu. Dec. 26, 2013 10:19 am

coalkirk wrote:I don't think you mentioned an expansion tank which is a must. Sizing it correctly can eliminate the need for a dump zone. Member Yanche has posted tutorials on this topic.
I like the 14 gal. floor mounted units.

 
User avatar
StokerDon
Site Moderator
Posts: 7484
Joined: Mon. Nov. 11, 2013 11:17 am
Location: PA, Southern York County!
Stoker Coal Boiler: Gentleman Janitor GJ-5, Van Wert VA-600, Axeman Anderson130 X3.
Hand Fed Coal Furnace: Harman SF3500 reduced down to 3 grates connected to its own plenum
Coal Size/Type: Rice, Chestnut and whatever will fit through the door on the Harman
Other Heating: Noth'in but COAL! Well, Maybe a little tiny bit of wood

Post by StokerDon » Thu. Dec. 26, 2013 10:27 am

coalkirk wrote:I don't think you mentioned an expansion tank which is a must. Sizing it correctly can eliminate the need for a dump zone. Member Yanche has posted tutorials on this topic.
Since this garage intsallation is kind of an experiment, I am trying to use as much of the parts that came with the unit as I can. It did come with an expansion tank that I was ging to use. But, I guess that this tank is sized the the preveious owners system and may not be right for my system. More studying.

coalkirk,

I have found a good company to buy the PEX and the heat exchangers from. The problem is that 120 feet of insulated PEX comes on a pallet. I would think this means it only comes by truck, which means if I order it from Wisconson it won't be here for 10 days or so. Do you know of a local supplier to get insulated PEX?

-Don

 
User avatar
StokerDon
Site Moderator
Posts: 7484
Joined: Mon. Nov. 11, 2013 11:17 am
Location: PA, Southern York County!
Stoker Coal Boiler: Gentleman Janitor GJ-5, Van Wert VA-600, Axeman Anderson130 X3.
Hand Fed Coal Furnace: Harman SF3500 reduced down to 3 grates connected to its own plenum
Coal Size/Type: Rice, Chestnut and whatever will fit through the door on the Harman
Other Heating: Noth'in but COAL! Well, Maybe a little tiny bit of wood

Post by StokerDon » Thu. Dec. 26, 2013 10:31 am

Rob R. wrote:
coalkirk wrote:I don't think you mentioned an expansion tank which is a must. Sizing it correctly can eliminate the need for a dump zone. Member Yanche has posted tutorials on this topic.
I like the 14 gal. floor mounted units.
After looking at a lot of installs, I was wondering how this tank, full of gallons of water hung on there with .25" pipe thread without breaking off? I like the idea of the floor mount.

-Don

 
User avatar
whistlenut
Member
Posts: 3548
Joined: Sat. Mar. 17, 2007 6:29 pm
Location: Central NH, Concord area
Stoker Coal Boiler: AA130's,260's, AHS130&260's,EFM900,GJ & V-Wert
Hand Fed Coal Boiler: Franks,Itasca 415,Jensen, NYer 130,Van Wert
Hot Air Coal Stoker Furnace: Alaska, EFM, Keystoker, Yellow Flame
Hot Air Coal Stoker Stove: Alaska, Keystoker-2,Leisure Line
Hand Fed Coal Stove: Alaska, Gibraltar, Keystone,Vc Vigilant 2
Hand Fed Coal Furnace: Ford, Jensen, NYer, Van Wert,
Baseburners & Antiques: Glenwoods
Coal Size/Type: Barley, Buck, Rice ,Nut, Stove
Other Heating: Oil HWBB

Post by whistlenut » Thu. Dec. 26, 2013 10:39 am

Don, look around at a local OWB supplier if you need insulated pipe immediately. They may be able help you out. I use the floor mounted expansion tanks only, and the small price difference is well worth it. Call local supply houses, too. They may just want your business enough to make the convenience well worth your time. Pipe of that diameter might be able to be shipped without a common carrier......find out about Fed-Ex ground or UPS ground also.

 
User avatar
StokerDon
Site Moderator
Posts: 7484
Joined: Mon. Nov. 11, 2013 11:17 am
Location: PA, Southern York County!
Stoker Coal Boiler: Gentleman Janitor GJ-5, Van Wert VA-600, Axeman Anderson130 X3.
Hand Fed Coal Furnace: Harman SF3500 reduced down to 3 grates connected to its own plenum
Coal Size/Type: Rice, Chestnut and whatever will fit through the door on the Harman
Other Heating: Noth'in but COAL! Well, Maybe a little tiny bit of wood

Post by StokerDon » Thu. Dec. 26, 2013 10:47 am

whistlenut wrote:Don, look around at a local OWB supplier if you need insulated pipe immediately. They may be able help you out. I use the floor mounted expansion tanks only, and the small price difference is well worth it. Call local supply houses, too. They may just want your business enough to make the convenience well worth your time. Pipe of that diameter might be able to be shipped without a common carrier......find out about Fed-Ex ground or UPS ground also.
OK, Thanks whistlenut!

Hopefully I can consult with coalkirk about local suppliers. I'm kind of new to the area, so I don't know any.

-Don

 
User avatar
coalkirk
Member
Posts: 5185
Joined: Wed. May. 17, 2006 8:12 pm
Location: Forest Hill MD
Stoker Coal Boiler: 1981 EFM DF520 retired
Hand Fed Coal Stove: Jotul 507 on standby
Coal Size/Type: Lehigh anthracite/rice coal

Post by coalkirk » Thu. Dec. 26, 2013 1:31 pm

I've never purchased any but I would try R. E. Michel.
http://www.remichel.com/locations/maryland.asp


 
User avatar
StokerDon
Site Moderator
Posts: 7484
Joined: Mon. Nov. 11, 2013 11:17 am
Location: PA, Southern York County!
Stoker Coal Boiler: Gentleman Janitor GJ-5, Van Wert VA-600, Axeman Anderson130 X3.
Hand Fed Coal Furnace: Harman SF3500 reduced down to 3 grates connected to its own plenum
Coal Size/Type: Rice, Chestnut and whatever will fit through the door on the Harman
Other Heating: Noth'in but COAL! Well, Maybe a little tiny bit of wood

Post by StokerDon » Thu. Dec. 26, 2013 3:24 pm

coalkirk wrote:I've never purchased any but I would try R. E. Michel.
http://www.remichel.com/locations/maryland.asp
coalkirk,

Well they sell OB PEX, but they won't sell it to me, only contractors. And they don't sell it insulated.

I will keep search'in.

-Don

 
User avatar
CoalHeat
Member
Posts: 8862
Joined: Sat. Feb. 10, 2007 9:48 pm
Location: Stillwater, New Jersey
Stoker Coal Boiler: 1959 EFM 350
Hand Fed Coal Stove: Harman Magnafire Mark I
Baseburners & Antiques: Sears Signal Oak 15 & Andes Kitchen Range
Coal Size/Type: Rice and Chestnut
Other Heating: Fisher Fireplace Insert

Post by CoalHeat » Thu. Dec. 26, 2013 4:25 pm

I'll save ya a trip:
Lowe's has O2 barrier PEX but only up to 3/4", made in Red China.
You ever work with PEX? It SUCKS.
IMG_4128.jpg
.JPG | 160.6KB | IMG_4128.jpg

 
User avatar
whistlenut
Member
Posts: 3548
Joined: Sat. Mar. 17, 2007 6:29 pm
Location: Central NH, Concord area
Stoker Coal Boiler: AA130's,260's, AHS130&260's,EFM900,GJ & V-Wert
Hand Fed Coal Boiler: Franks,Itasca 415,Jensen, NYer 130,Van Wert
Hot Air Coal Stoker Furnace: Alaska, EFM, Keystoker, Yellow Flame
Hot Air Coal Stoker Stove: Alaska, Keystoker-2,Leisure Line
Hand Fed Coal Stove: Alaska, Gibraltar, Keystone,Vc Vigilant 2
Hand Fed Coal Furnace: Ford, Jensen, NYer, Van Wert,
Baseburners & Antiques: Glenwoods
Coal Size/Type: Barley, Buck, Rice ,Nut, Stove
Other Heating: Oil HWBB

Post by whistlenut » Thu. Dec. 26, 2013 5:21 pm

Perhaps someone here will make a call to get you trade pricing. It's not like you are gonna let some secret out of the bag. If you have the ability to go to Uponor/Wirsboro, you will think you have died and gone to heaven. Just have to ask for 'heat' for heat lines and potable for normal water lines. PM if you need more info, and an honest opinion on the temp ranges that are safe for Uponor. Ever hear: "it will stretch a mile, before it will rip an inch". True statement regarding Uponor. Not saving a damned thing more. If you could get the avatar girl to go to the supply house, they would probably let you have anything you wanted.....for free!!!!!

 
User avatar
Rob R.
Site Moderator
Posts: 17965
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Thu. Dec. 26, 2013 5:28 pm

Thermopex from Central Boiler is a great product...and you probably have a dealer nearby that will be happy to sell you some.

 
User avatar
Hambden Bob
Member
Posts: 8531
Joined: Mon. Jan. 04, 2010 10:54 am
Location: Hambden Twp. Geauga County,Ohio
Hot Air Coal Stoker Stove: Harman 1998 Magnum Stoker
Hand Fed Coal Stove: Blower Model Coal Chubby 1982-Serial#0097
Coal Size/Type: Rice-A-Roni ! / Nut
Other Heating: Pro-Pain Forced Air

Post by Hambden Bob » Thu. Dec. 26, 2013 5:35 pm

You beat me to it,Rob ! Excellent quality,waterproof outer membrane,and closed cell conforming insulation that fills all voids. It aint cheap,but the job's done right the first time. Just tell them "No"(politely)if and when they try to sell you an Outdoor Wood Burner ! :lol:

 
User avatar
Hambden Bob
Member
Posts: 8531
Joined: Mon. Jan. 04, 2010 10:54 am
Location: Hambden Twp. Geauga County,Ohio
Hot Air Coal Stoker Stove: Harman 1998 Magnum Stoker
Hand Fed Coal Stove: Blower Model Coal Chubby 1982-Serial#0097
Coal Size/Type: Rice-A-Roni ! / Nut
Other Heating: Pro-Pain Forced Air

Post by Hambden Bob » Thu. Dec. 26, 2013 5:39 pm

Helpful Linkage-Use their Dealer Locator http://www.centralboiler.com/thermopex.html

 
User avatar
ricoman2737
Member
Posts: 100
Joined: Mon. Apr. 13, 2009 12:22 pm
Location: Cincinnatus, NY 13040 (Cortland Co.)
Stoker Coal Boiler: EFM DF520
Coal Size/Type: Buckwheat
Other Heating: Lennox Fuel Oil boiler as a backup

Post by ricoman2737 » Thu. Dec. 26, 2013 5:45 pm

Don,

Check this website, it has all kinds of supplies to help you plumb your boiler, it even has oxygen barrier insulated piping.

http://www.altheatsupply.com

Good luck - John

 
User avatar
coalkirk
Member
Posts: 5185
Joined: Wed. May. 17, 2006 8:12 pm
Location: Forest Hill MD
Stoker Coal Boiler: 1981 EFM DF520 retired
Hand Fed Coal Stove: Jotul 507 on standby
Coal Size/Type: Lehigh anthracite/rice coal

Post by coalkirk » Thu. Dec. 26, 2013 6:05 pm

The central boiler link has insulated 1 1/4" barrier type pex and they list a dealer in Fallston Md. The Altheatsupply link doesn't seem to have anything over 1".


Post Reply