At this point, I am trying to assemble the controls I will need to get my Van Wert 600 up and running. The boiler came with a honewell 4006a1967 aquastat mounted in a well. If I am correct, this stat only will do one function for me .. I am looking for something that will turn on/off the stoker when needed for heat, and one that will activate a dump zone when temps get too high. My circulator between the coal and oil boiler will be running constantly. I would prefer to use the one existing well on the boiler as getting another out will likely be a tough task. Am I missing something as far as what else I may need this aquastat to do ??
Which one aquastat wil fit my needs here? brand and model will be great so I may try to find a good deal out there ....
thanks
Brad
Aquastat Advice Needed ...
- lsayre
- Member
- Posts: 21781
- Joined: Wed. Nov. 23, 2005 9:17 pm
- Location: Ohio
- Stoker Coal Boiler: AHS S130 Coal Gun
- Coal Size/Type: Lehigh Anthracite Pea
- Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75
The Honeywell L4081B should work. Or perhaps the Honeywell L8124B.
Or you can try this idea:
http://www.beckettcorp.com/aquasmart/
Or look at the 'Hydrolevel' 3150 or 3250 models.
Or you can try this idea:
http://www.beckettcorp.com/aquasmart/
Or look at the 'Hydrolevel' 3150 or 3250 models.
- Rob R.
- Site Moderator
- Posts: 18004
- Joined: Fri. Dec. 28, 2007 4:26 pm
- Location: Chazy, NY
- Stoker Coal Boiler: EFM 520
- Hand Fed Coal Stove: Chubby Jr
Your existing aquastat will work for the stoker. Mount a tee & aquastat well in the supply header and install a L4006B for the dump zone.
Honeywell L8124, or L7224 will also work...so will a Hydrostat 3250. All three can maintain boiler temperature and offer a high limit for the timer circuit.
Honeywell L8124, or L7224 will also work...so will a Hydrostat 3250. All three can maintain boiler temperature and offer a high limit for the timer circuit.