Intermatic C8835/ Honeywell RA89A Relay Wiring Problem
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
Greetings, I have a EFM520 Coal furnace. I am replacing a Honeywell R883 timer/relay unit on this unit with an Intermatic C8835 and a Honeywell RA89A relay. Can anyone help with the proper wiring of these new parts vs. the old Honeywell R883. I have low and high temp aquastats that are Honeywell. I have wired these new parts and can get the stoker motor to function but not in a call for heat situation to recover water temp. I have the inline power to the C8835 timer and power then to the RA89A relay and out the relay to the stoker motor and that works. WHAT WIRES DO I NEED TO CONNECT TO THE "TT" TERMINALS ON THE RA89A RELAY SO THAT THE FIRE IS MAINTAINED AND THE STOKER MOTOR STARTS ALSO IN A CALL FOR HEAT SITUATION??????? What might I be doing wrong??????? Thanks so very much.
- ntp71
- Member
- Posts: 277
- Joined: Sat. May. 17, 2008 9:14 am
- Location: Nanticoke, PA
- Hand Fed Coal Boiler: Reading Foundry Water Heater
- Hot Air Coal Stoker Stove: Old Mill Mini Stoker with Keystoker Feed System
- Hand Fed Coal Stove: Gibraltar SCR
- Baseburners & Antiques: Caloric UltraMatic Coal-Gas Range
- Coal Size/Type: Chestnut
pm glenn harris ... he should know
- McGiever
- Member
- Posts: 10130
- Joined: Sun. May. 02, 2010 11:26 pm
- Location: Junction of PA-OH-WV
- Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
- Hand Fed Coal Boiler: BUCKET A DAY water heater
- Hand Fed Coal Stove: Warm Morning 414A
- Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
- Other Heating: Ground Source Heat Pump and some Solar
So, the timer part works as expected...just that the boiler never recovers from a heat call?
TT should be signal from aquastat that boiler water temp is below setpoint. Open/Close signal...Just a Dry Contact...no power needs sent.
You may test this by touching a jumper wire across the TT points.
TT should be signal from aquastat that boiler water temp is below setpoint. Open/Close signal...Just a Dry Contact...no power needs sent.
You may test this by touching a jumper wire across the TT points.
- Rob R.
- Site Moderator
- Posts: 18004
- Joined: Fri. Dec. 28, 2007 4:26 pm
- Location: Chazy, NY
- Stoker Coal Boiler: EFM 520
- Hand Fed Coal Stove: Chubby Jr
Is this a steam system? Normally that is what the R883 would be used for, and the thermostat would be connected to the TT terminals. If this is a hot water system, I would wire it differently. Explain how the entire system is wired/setup.
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
My system is Hot Water. Presently my low temp aquastat is on the "TT" terminals. If I jump the "TT" terminals on the RA89A with the C8835 the stoker motor starts and will run until the timer setting expires. I connected the old Honeywell R883 again and everything works, however I need to change the old unit out as it is not reliable. When it is wired correctly the stoker runs every 1/2 hour to maintain the fire. When I hooked up the new C8835/ RA89A it will not run to maintain unless I manually jump the "TT" terminals. On my new setup should the thermostat wires be on the "TT" terminals or the aquastat. Again I can not put my finger on what I am doing wrong. It is probably so simple. Thanks Much for Helping
- McGiever
- Member
- Posts: 10130
- Joined: Sun. May. 02, 2010 11:26 pm
- Location: Junction of PA-OH-WV
- Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
- Hand Fed Coal Boiler: BUCKET A DAY water heater
- Hand Fed Coal Stove: Warm Morning 414A
- Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
- Other Heating: Ground Source Heat Pump and some Solar
Leave t'stat at L8124 "TT" terminals.
You need to parallel feed the stoker/burner motor.
At the L8124 take 120volts from "B-B1" to stoker/burner...and at same time, get switched/cycled 120volt from C8835 timer to stoker/burner...2 different sorces...1 motor.
An easy way to parallel is to make a splice in a junction box nearer to both the timer and to the L8124 using wire nuts...then you only need to run the combined single 120volt any distance.
Obviously the old [all-in-one] RB-883 did this paralleling internally.
You need to parallel feed the stoker/burner motor.
At the L8124 take 120volts from "B-B1" to stoker/burner...and at same time, get switched/cycled 120volt from C8835 timer to stoker/burner...2 different sorces...1 motor.
An easy way to parallel is to make a splice in a junction box nearer to both the timer and to the L8124 using wire nuts...then you only need to run the combined single 120volt any distance.
Obviously the old [all-in-one] RB-883 did this paralleling internally.
Last edited by McGiever on Sun. Sep. 28, 2014 10:56 am, edited 2 times in total.
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
Mc Giever, Thanks. I should have stated that I have seperate LOW (L444B) and HIGH (L4006A) temp aquastats. Can I use a L8124 on a coal unit???? Thanks Much
- McGiever
- Member
- Posts: 10130
- Joined: Sun. May. 02, 2010 11:26 pm
- Location: Junction of PA-OH-WV
- Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
- Hand Fed Coal Boiler: BUCKET A DAY water heater
- Hand Fed Coal Stove: Warm Morning 414A
- Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
- Other Heating: Ground Source Heat Pump and some Solar
Sorry for mix up, was another poster w/ L8124.
Yes, can use L8124, or L7224 is even better. There are variations of these, so be sure which one you want/need.
Yes, can use L8124, or L7224 is even better. There are variations of these, so be sure which one you want/need.
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
McGiever, Can the C8835/RA89A be used with my present aquastats??????
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
MCGiever, If so what wires go on the new RA89A relay "TT" terminals to trip it to work????????
- McGiever
- Member
- Posts: 10130
- Joined: Sun. May. 02, 2010 11:26 pm
- Location: Junction of PA-OH-WV
- Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
- Hand Fed Coal Boiler: BUCKET A DAY water heater
- Hand Fed Coal Stove: Warm Morning 414A
- Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
- Other Heating: Ground Source Heat Pump and some Solar
Yes, "TT" in RA89A...but is stoker motor already paralleled also?
Cause now 2 separate devices need to start 1 motor.
Cause now 2 separate devices need to start 1 motor.
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
This is probably where I am messed up. What does it mean PARALLELED??????
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
The motor will start if I manually jump the RA89A relay "TT" terminals. So I must have something missing regarding what is needed to make this new setup trip. Perhaps the old R883 did this internally. Thanks
-
- New Member
- Posts: 17
- Joined: Sun. Sep. 28, 2014 6:40 am
- Stoker Coal Boiler: EFM520 coal
- Coal Size/Type: rice
McGiever, Thank You for your patience
- McGiever
- Member
- Posts: 10130
- Joined: Sun. May. 02, 2010 11:26 pm
- Location: Junction of PA-OH-WV
- Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
- Hand Fed Coal Boiler: BUCKET A DAY water heater
- Hand Fed Coal Stove: Warm Morning 414A
- Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
- Other Heating: Ground Source Heat Pump and some Solar
Manually jumping the "TT" is a simulation of the thermostat calling for heat...when satisfied it's off until the next call comes. Period.blacklab11 wrote:The motor will start if I manually jump the RA89A relay "TT" terminals. So I must have something missing regarding what is needed to make this new setup trip. Perhaps the old R883 did this internally. Thanks
As for the timer, it needs to call for a cycled run-time independent of when the thermostat calls. You see this is 2 devices now, where before it was all in only one device.
At your L440B aquastat install a permanent (short) jumper from the same connection that now has the wire leading out to stoker motor is on... over to the unused connection opposite of it...now it is paralleled.
Report back your results, please.