Been Running About 5 Hrs Now

 
User avatar
ShawnTRD
Member
Posts: 519
Joined: Tue. Feb. 04, 2014 1:04 am
Location: Spencer, NY
Stoker Coal Boiler: Keystoker KA6 (New in April 2014)
Coal Size/Type: Anthracite Rice
Other Heating: Weil Mclain WGO-2 (Net 75k BTU)

Post by ShawnTRD » Wed. Oct. 15, 2014 7:56 pm

On timer (4 pin ever 15 min) only took about 3 hours to go from 155ish to 140.
Image
Image
Image
Image
Image

On high fire for about 10 minutes
Image

Once it reached about 155. But high aquastat is set for 180. Why did it shut off?
Image


 
User avatar
lsayre
Member
Posts: 21781
Joined: Wed. Nov. 23, 2005 9:17 pm
Location: Ohio
Stoker Coal Boiler: AHS S130 Coal Gun
Coal Size/Type: Lehigh Anthracite Pea
Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75

Post by lsayre » Wed. Oct. 15, 2014 8:05 pm

Lookin good there ShawnTRD!

 
User avatar
ShawnTRD
Member
Posts: 519
Joined: Tue. Feb. 04, 2014 1:04 am
Location: Spencer, NY
Stoker Coal Boiler: Keystoker KA6 (New in April 2014)
Coal Size/Type: Anthracite Rice
Other Heating: Weil Mclain WGO-2 (Net 75k BTU)

Post by ShawnTRD » Wed. Oct. 15, 2014 8:12 pm

Question about the triple aquastat. If I have the "Low" setting at 140, and the "High" setting at 160. Shouldn't the feeder kick in at 140 and stay running to 160? And what the Diff for?

 
User avatar
lsayre
Member
Posts: 21781
Joined: Wed. Nov. 23, 2005 9:17 pm
Location: Ohio
Stoker Coal Boiler: AHS S130 Coal Gun
Coal Size/Type: Lehigh Anthracite Pea
Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75

Post by lsayre » Wed. Oct. 15, 2014 8:17 pm

ShawnTRD wrote:Question about the triple aquastat. If I have the "Low" setting at 140, and the "High" setting at 160. Shouldn't the feeder kick in at 140 and stay running to 160? And what the Diff for?
Coal Gun's don't use triple aquastats, so I can't help you there. Someone more familiar with them should be along soon to assist you. if not, my advice would be to try sending Rob a PM.

 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Wed. Oct. 15, 2014 8:18 pm

ShawnTRD wrote:Question about the triple aquastat. If I have the "Low" setting at 140, and the "High" setting at 160. Shouldn't the feeder kick in at 140 and stay running to 160? And what the Diff for?
Which model aquastat do you have?
L8124.png
.PNG | 117.2KB | L8124.png
Last edited by McGiever on Wed. Oct. 15, 2014 8:28 pm, edited 1 time in total.

 
franco b
Site Moderator
Posts: 11417
Joined: Wed. Nov. 05, 2008 5:11 pm
Location: Kent CT
Hand Fed Coal Stove: V ermont Castings 2310, Franco Belge 262
Baseburners & Antiques: Glenwood Modern Oak 114
Coal Size/Type: nut and pea

Post by franco b » Wed. Oct. 15, 2014 8:21 pm

ShawnTRD wrote:Question about the triple aquastat. If I have the "Low" setting at 140, and the "High" setting at 160. Shouldn't the feeder kick in at 140 and stay running to 160? And what the Diff for?
My understanding is that the unit will run at the low setting and then at the high setting when the thermostat calls for heat. The differential is to shut off the circulator when the boiler temp falls how many degrees it is set for below the high limit.

 
lzaharis
Member
Posts: 2379
Joined: Sun. Mar. 25, 2007 8:41 pm
Location: Ithaca, New York
Stoker Coal Boiler: Keystoker KAA-4-1 dual fuel boiler
Hand Fed Coal Boiler: former switzer CWW100-sold
Coal Size/Type: rice
Other Heating: kerosene for dual fuel Keystoker/unused

Post by lzaharis » Wed. Oct. 15, 2014 8:28 pm

I have the strap on pipe aqaustats Shawn.

But it comes down to the satisfaction of the thermostat and the aquastats from what I
remember and if the pumps are set at a slow speed like I have mine set
(3 speed B+G pumps set on the number one setting) you have more hot water
staying in the boiler longer.

I am unsure if you have too much unburned coal in the ash tube but opening
the air inlet on the secondary fan would help with that.

Are you leaving your oil tank by the stoker?


 
User avatar
ShawnTRD
Member
Posts: 519
Joined: Tue. Feb. 04, 2014 1:04 am
Location: Spencer, NY
Stoker Coal Boiler: Keystoker KA6 (New in April 2014)
Coal Size/Type: Anthracite Rice
Other Heating: Weil Mclain WGO-2 (Net 75k BTU)

Post by ShawnTRD » Wed. Oct. 15, 2014 8:38 pm

franco b wrote:
ShawnTRD wrote:Question about the triple aquastat. If I have the "Low" setting at 140, and the "High" setting at 160. Shouldn't the feeder kick in at 140 and stay running to 160? And what the Diff for?
My understanding is that the unit will run at the low setting and then at the high setting when the thermostat calls for heat. The differential is to shut off the circulator when the boiler temp falls how many degrees it is set for below the high limit.
Ok so 180 is when the thermostat is on, and DIFF 10,15 or 20 is for turn on at 170, 165 or 160. Does the same go for the low side?

 
User avatar
ShawnTRD
Member
Posts: 519
Joined: Tue. Feb. 04, 2014 1:04 am
Location: Spencer, NY
Stoker Coal Boiler: Keystoker KA6 (New in April 2014)
Coal Size/Type: Anthracite Rice
Other Heating: Weil Mclain WGO-2 (Net 75k BTU)

Post by ShawnTRD » Wed. Oct. 15, 2014 8:42 pm

lzaharis wrote:Are you leaving your oil tank by the stoker?
It's getting moved this weekend.

 
User avatar
Rob R.
Site Moderator
Posts: 18004
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Wed. Oct. 15, 2014 8:44 pm

ShawnTRD wrote:Question about the triple aquastat. If I have the "Low" setting at 140, and the "High" setting at 160. Shouldn't the feeder kick in at 140 and stay running to 160? And what the Diff for?
No. It will not run up to the high limit unless the TT terminals are joined or if there is 120v at the ZR terminal.

Low limit differential is normally set at 10.

 
User avatar
ShawnTRD
Member
Posts: 519
Joined: Tue. Feb. 04, 2014 1:04 am
Location: Spencer, NY
Stoker Coal Boiler: Keystoker KA6 (New in April 2014)
Coal Size/Type: Anthracite Rice
Other Heating: Weil Mclain WGO-2 (Net 75k BTU)

Post by ShawnTRD » Wed. Oct. 15, 2014 8:45 pm

Image
Image

 
franco b
Site Moderator
Posts: 11417
Joined: Wed. Nov. 05, 2008 5:11 pm
Location: Kent CT
Hand Fed Coal Stove: V ermont Castings 2310, Franco Belge 262
Baseburners & Antiques: Glenwood Modern Oak 114
Coal Size/Type: nut and pea

Post by franco b » Wed. Oct. 15, 2014 9:09 pm

ShawnTRD wrote:Ok so 180 is when the thermostat is on, and DIFF 10,15 or 20 is for turn on at 170, 165 or 160. Does the same go for the low side?
Yes it should go to 180 when thermostat calls and is connected to the TT terminals. The differential is to turn off the circulator when the temperature falls below whatever the differential is set at. If hi limit is 180 and differential is 15 then the circulator should turn off at 165. It gives the boiler time to recover heat and prevents having domestic water run out of heat. Should not effect low limit. This is my understanding

I much prefer the set up of many years ago when three separate aquastats were used; low or running aquastat, High limit, Reverse. The aquastats were activated by a helical bi-metal coil that turned a mercury switch. Reliable and lasting and safer. The high limit was strictly an extra safety, ordinary operation was only with the low limit and generally the system was sized for 160 to 180 degree water. With the new system there is only one aquastat guarding against runaway water temperature when heat is called for and there is only one sensor. A micro switch as opposed to a mercury switch.

 
franco b
Site Moderator
Posts: 11417
Joined: Wed. Nov. 05, 2008 5:11 pm
Location: Kent CT
Hand Fed Coal Stove: V ermont Castings 2310, Franco Belge 262
Baseburners & Antiques: Glenwood Modern Oak 114
Coal Size/Type: nut and pea

Post by franco b » Wed. Oct. 15, 2014 9:15 pm

Rob says that the differential works on the low limit and I would prefer his word on this.

 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Wed. Oct. 15, 2014 9:30 pm

franco b wrote:Rob says that the differential works on the low limit and I would prefer his word on this.
You're both correct. :)

 
User avatar
ShawnTRD
Member
Posts: 519
Joined: Tue. Feb. 04, 2014 1:04 am
Location: Spencer, NY
Stoker Coal Boiler: Keystoker KA6 (New in April 2014)
Coal Size/Type: Anthracite Rice
Other Heating: Weil Mclain WGO-2 (Net 75k BTU)

Post by ShawnTRD » Wed. Oct. 15, 2014 9:33 pm

Ok so that makes sense. So in summer if your running just DHW and leave the High limit at 180 it doesn't matter. Because you never turn on the thermostat. So it can stay at 140 via the Low limit for DHW. But in the winter you change the Low to 160 so it's not that far from 180.

So the Diff works on both High and Low?


Post Reply

Return to “Stoker Coal Furnaces & Stoves Using Anthracite (Hot Air)”