Chimney Adapter Question
-
- Member
- Posts: 35
- Joined: Wed. Nov. 27, 2013 8:51 am
- Location: Kentucky
- Hand Fed Coal Furnace: Shenandoah
- Coal Size/Type: Bituminous, Anthracite
Greetings all! Last year I installed an older wood/coal stove in my basement. The house had no existing chimney or fireplace so everything other than the actual stove was new. The stove has an 8 inch flue collar so I used 8 inch triple wall for the chimney and 8 inch double wall for the the stove to the wall. No problems, other than maybe too much draft, I haven't measured it but it's impressive. Anyway, the stove is in the basement and it's not enough to do the job I want it too do so I'm thinking about installing a wood/coal furnace. All of the furnaces I'm looking at have 6 inch collars and I am curious about what, if any, problems I may have connecting such a furnace to a 8 inch chimney. Any thoughts?
- michaelanthony
- Member
- Posts: 4550
- Joined: Sat. Nov. 22, 2008 10:42 pm
- Location: millinocket,me.
- Hand Fed Coal Stove: Vigilant 2310, gold marc box stove
- Hand Fed Coal Furnace: Gold Marc Independence
- Baseburners & Antiques: Home Sparkle 12
- Coal Size/Type: 'nut
- Other Heating: Fujitsu mini split, FHA oil furnace
Welcome, most chimneys are bigger than 6 inches.
- Rick 386
- Member
- Posts: 2508
- Joined: Mon. Jan. 28, 2008 4:26 pm
- Location: Royersford, Pa
- Stoker Coal Boiler: AA 260 heating both sides of twin farmhouse
- Hot Air Coal Stoker Stove: LL Hyfire II w/ coaltrol in garage
- Coal Size/Type: Pea in AA 260, Rice in LL Hyfire II
- Other Heating: Gas fired infared at work
- Contact:
The only true way to check the draft is with a manometer.
Guessing about how well it draws can lead to problems.
Rick
Guessing about how well it draws can lead to problems.
Rick
-
- Member
- Posts: 35
- Joined: Wed. Nov. 27, 2013 8:51 am
- Location: Kentucky
- Hand Fed Coal Furnace: Shenandoah
- Coal Size/Type: Bituminous, Anthracite
I intend to install a manometer with the new furnace, maybe sooner. I know I have plenty of draft with my current setup, it may be too much but that is easier to deal with than not enough. My concern with the future install would be losing draft due to using a 6" to 8" adapter.
-
- Member
- Posts: 4197
- Joined: Wed. Oct. 03, 2012 9:53 am
- Location: Western Massachusetts
- Baseburners & Antiques: Crawford 40, PP Stewart No. 14, Abendroth Bros "Record 40"
- Coal Size/Type: Stove / Anthracite.
- Other Heating: Oil fired, forced hot air.
The chimney is completely outside the house and exposed?
As the gasses transition from 6 inch to 8 inch pipe they will expand, losing velocity and temperature.
It's a guess how much until you have a tool to measure it.
In all applications a Monometer, either permanently mounted, or a pocket draft gauge is a very good idea.
As the gasses transition from 6 inch to 8 inch pipe they will expand, losing velocity and temperature.
It's a guess how much until you have a tool to measure it.
In all applications a Monometer, either permanently mounted, or a pocket draft gauge is a very good idea.
-
- Member
- Posts: 35
- Joined: Wed. Nov. 27, 2013 8:51 am
- Location: Kentucky
- Hand Fed Coal Furnace: Shenandoah
- Coal Size/Type: Bituminous, Anthracite
The 6 to 8 inch adapter will be as close to the furnace as I can get it. There is about 4 feet of pipe in the house, the rest of the chimney is outside and goes up about 24 feet.