Warm Air Vs Boiler
-
- Member
- Posts: 133
- Joined: Thu. Jan. 23, 2014 10:23 am
- Location: Western Michigan
- Stoker Coal Boiler: KAA-2
- Hand Fed Coal Stove: Hitzer model 30-95 EZ Flow Sadly Retired
- Coal Size/Type: Rice
- Other Heating: Propane furnace/elec. water heater
$125.00 is way less than I would have expected to Michigan. I am remodeling a 6 story building that has a lot of steam radiators in it, can they be used for hot water?
- StokerDon
- Site Moderator
- Posts: 7486
- Joined: Mon. Nov. 11, 2013 11:17 am
- Location: PA, Southern York County!
- Stoker Coal Boiler: Gentleman Janitor GJ-5, Van Wert VA-600, Axeman Anderson130 X3.
- Hand Fed Coal Furnace: Harman SF3500 reduced down to 3 grates connected to its own plenum
- Coal Size/Type: Rice, Chestnut and whatever will fit through the door on the Harman
- Other Heating: Noth'in but COAL! Well, Maybe a little tiny bit of wood
If they are 1 pipe steam radiators and have a threaded plug on the opposite side. I would think you just remove the plug and then you have 2 pipe hot water radiators!
I would love to have radiators in my system.
-Don
I would love to have radiators in my system.
-Don
- coaledsweat
- Site Moderator
- Posts: 13763
- Joined: Fri. Oct. 27, 2006 2:05 pm
- Location: Guilford, Connecticut
- Stoker Coal Boiler: Axeman Anderson 260M
- Coal Size/Type: Pea
You can use them but typically hot water requires more radiation then steam due to the difference in temperatures between the two. If it is piped for steam, put steam in. The boilers are the same, but in a steam boiler there is a headspace above the water level and the controls are slightly different.Tryingitout wrote:$125.00 is way less than I would have expected to Michigan. I am remodeling a 6 story building that has a lot of steam radiators in it, can they be used for hot water?
-
- Member
- Posts: 3555
- Joined: Tue. Sep. 04, 2007 10:14 pm
- Location: Dalton, MA
- Stoker Coal Boiler: H.B. Smith 350 Mills boiler/EFM 85R stoker
- Coal Size/Type: Buckwheat/anthracite
x2. All else equal, the same radiator will yield about 1/3 less heat with hot water than with steam, so you'd be putting in a lot of effort to downgrade the usable capacity of the system. Most of the difference in output stems from the capture by the steam radiator of the "latent heat of vaporization" - the large chunk of energy required to convert water at 212 deg to steam - and not just from the temperature differential.coaledsweat wrote:You can use them but typically hot water requires more radiation then steam due to the difference in temperatures between the two. If it is piped for steam, put steam in.
If you were starting from scratch, a properly-designed hot water system almost certainly would be somewhat more efficient than a steam system, but that doesn't mean running hot water through existing steam radiation would produce satisfactory performance.
Mike
-
- Member
- Posts: 3555
- Joined: Tue. Sep. 04, 2007 10:14 pm
- Location: Dalton, MA
- Stoker Coal Boiler: H.B. Smith 350 Mills boiler/EFM 85R stoker
- Coal Size/Type: Buckwheat/anthracite
All else equal boilers tend to be more efficient than furnaces because water is better than air as a medium for transferring and storing btu's. Obviously, the actual performance of individual units depends on such factors as the size and design of their heat exchangers.Tryingitout wrote:I suppose there is no way to know if I would burn more coal with a warm air or boiler. I can assume these will burn more than my Hitzer.
A boiler or furnace conceivably could burn less coal than the Hitzer if you give it the same job (i.e., radiating space heat from a single point). It is reasonable to expect it to burn more if you use it to power a central system that provides controlled heat over a larger area, makes DHW, etc.
Mike
Last edited by Pacowy on Wed. Feb. 18, 2015 4:15 pm, edited 1 time in total.
- coalkirk
- Member
- Posts: 5185
- Joined: Wed. May. 17, 2006 8:12 pm
- Location: Forest Hill MD
- Stoker Coal Boiler: 1981 EFM DF520 retired
- Hand Fed Coal Stove: Jotul 507 on standby
- Coal Size/Type: Lehigh anthracite/rice coal
I understand your concerns but take it from the experts here. Boiler with hot water coil in your ductwork and never look back. It's a no brainer. Just do the homework to size the boiler for your anticipated demand.
- McGiever
- Member
- Posts: 10130
- Joined: Sun. May. 02, 2010 11:26 pm
- Location: Junction of PA-OH-WV
- Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
- Hand Fed Coal Boiler: BUCKET A DAY water heater
- Hand Fed Coal Stove: Warm Morning 414A
- Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
- Other Heating: Ground Source Heat Pump and some Solar
And give equal attention to the sizing of the true output of the air coil.
Sizing a air coil too small will make even the biggest of boiler seem too small.
Sizing a air coil too small will make even the biggest of boiler seem too small.
-
- Member
- Posts: 133
- Joined: Thu. Jan. 23, 2014 10:23 am
- Location: Western Michigan
- Stoker Coal Boiler: KAA-2
- Hand Fed Coal Stove: Hitzer model 30-95 EZ Flow Sadly Retired
- Coal Size/Type: Rice
- Other Heating: Propane furnace/elec. water heater
I would then assume that oversizing is a problem also. I will do my home work before any purchases. I am glad that there is a place like this for us to get information, thanks.
- windyhill4.2
- Member
- Posts: 6072
- Joined: Fri. Nov. 22, 2013 2:17 pm
- Location: Jonestown,Pa.17038
- Stoker Coal Boiler: 1960 EFM520 installed in truck box
- Hand Fed Coal Stove: Crane 404 with variable blower
- Coal Size/Type: 404-nut, 520 rice ,anthracite for both
I've never seen any issues with the over-sized heat exchangers I installed in our buildings. One is not required to use all the BTU's available in the water going thru the exchanger.
- coaledsweat
- Site Moderator
- Posts: 13763
- Joined: Fri. Oct. 27, 2006 2:05 pm
- Location: Guilford, Connecticut
- Stoker Coal Boiler: Axeman Anderson 260M
- Coal Size/Type: Pea
Exactly, there would be no losses and a big reserve. Sounds better than being on the edge to me.windyhill4.2 wrote:I've never seen any issues with the over-sized heat exchangers I installed in our buildings. One is not required to use all the BTU's available in the water going thru the exchanger.