Bituminous Stoker/Lump Coal Grates

 
unhippy
Member
Posts: 512
Joined: Mon. Dec. 27, 2010 1:59 am
Location: New Zealand
Stoker Coal Boiler: MK2 #1

Post by unhippy » Sat. Aug. 29, 2015 7:05 am

Teddy wrote:1. What is the angle of the Polish vee grates? based on the pictures I was going to set them at 35deg off horizontal
2. I will hopefully know what the klinkers are actually like. I am planning on building the furnace outside to experiment with the grates and feeding of the coal. I'll use the brick and insulation and preheat the air to try and duplicate the combustion temp. First I will run a front end loader of my coal through my 8" auger to see if it will break it up a little and use what will actually be dropping onto the bed. If the grates I have can't be used because of klinker control, I could drop the coal into a conventional stoker burner hopper - if I could find one. I looked up the Wilburt site and their smallest stoker is for 30#/hr!!! My burner needs to be max 6#/hr with a typical rate of 1.5 to 2#/hr. Do you know of any commercial burners that are that small? Not any that are currently made in the states....if you went hunting an older one this is the kind of thing you would be after https://youtu.be/N3sviUsbujw https://youtu.be/NAQaAaOIs7Q altho the coal you have is too large for them.....you might have make a coal breaker to resize your coal....not too difficult....building a test burner would be a good idea.....it will give an idea of what your going to need to deal with in the way of clinker and any swelling of the coal as it burns.....you might need to set it up to be able to run unattended and then you could leave it running for a longer test, simulating it being be run in the boiler without someone hovering over it and poking and fiddling with it
3. Slow ramp up and down will not cause problems I don't believe. I have a 1000 gallon insulated "milk tank" that the hot water will go to, so I have an enormous amount of thermal buffering, in the 600,000 BTU range. All thermal demands are withdrawn from this tank. In the summer my geothermal system cycles the compressors on at 44 Deg F and off at 40 Deg F tank temperature. The house and shop have been heavenly this summer. The house is 6600 ft2 and the shop in 2400 ft2. In heating mode, I have 3 way TC valves on each pump circuit from the tank to control the delivery temp to the radiant floor piping at around 95 Deg F. I had intended to coal heat the tank water at max fire rate to 195 Deg F and then let the demand draw it down to 100 F over a few hours to a few days. However, that means starting and stopping the burner which I am not sure will work well. Then I thought I should design the burner for 2 fire rates - max and 1/4th max. When the tank gets to100 F, go to max fire rate. When it gets to 140 to 160 F, drop to minimum fire rate. If it gets to 180 Deg F on min fire rate, open the shop doors and heat the universe, but keep the burner going. I have a lot of experience with co-generation engines burning biogas. DON'T turn them off, keep them hot and running all the time. The thermal stress of heating and cooling almost triples the maintenance costs of running the system. The joy of this project is I have never burned coal and have no experience, so I am desperately needing help understanding the pitfalls. Having that much of a thermal buffer isn't a normal coal heating system so your right, a slow ramp up and down isn't going to be too much of a problem as long as you have some way of shutting the burner off completely if your tank begins to get anywhere close to boiling.....or an automated heat dump circuit would have the same result in preventing the tank from boiling.....1000 gallons of water jumping around and trying to get out of its prison isn't alot of fun
4. What is your proposed klinker breaker made of? Stainless? Inconel? Cast? its just mainly steel flat bar as its at the end of the firebed and not actually in the fire
5. What might make more sense is to build a very small burner and run the heck out of it. If it can't keep up with demand, the geothermal will be there to keep the water at 95 degrees. Last winter the new house was finished and the geothermal did all the heating. At 8 tons or 96,000 Btu/Hr the geothermal did everything. I kept track of the minutes/hr that the compressors were on each day and the absolute worst case it ran about 40 minutes an hour or about 65,000 Btu/Hr. More typically it ran about 10 to 15 minutes per hour or about 15,000 to 20,000 Btu/Hr. I got started with this project because at the age of 73, I didn't want to split wood anymore and because the stupid "greenies" were closing down power plants due to their improper understanding of the carbon cycle, I better buy some coal before you couldn't get it any more. Also, the cost of the Illinois coal delivered to my home was $105/ton, about 1/3 the cost of firewood delivered to my home on a BTU basis. I thought, why not get about 20 years worth of coal and not have to worry about it anymore? Just load it into my hopper with my front end loader on the tractor every few days, build a large ash box and relax. So now I HAVE to finish the project!!!!65,000btu wouldn't be enough for a house that size here even if it is brand new....and we don't get anywhere near as cold as you do over there....Power Co's are are closing down the coal and gas power plants here as well.....and then jacking the power prices "Because there is a power shortage in the winter"....$0.30c per kw/hr is the current rate i'm on.....thankfully all my heating and hotwater is on coal....i know a fair number of people that think a monthly $400 power bill in winter is normal....i chuck my toys out of the cot if my power bill go's over $90....and in winter I average roughly 1/2 ton +/- of coal per month at $94 Ton picked up at the mine

I am sorry this is so long, I can't wait to get home and start burning some coal. It will take a couple days to get set up. I am at my son's home waiting for a baby to be born, we might be here for another week and then I have another vintage motorcycle race to compete in before I can get to the job at hand!!!! You have been very helpful, I am looking forward to your response of this post.
What bike are you racing?.....lol I come from a family of riders.....everyone has a bike including mum.....


 
unhippy
Member
Posts: 512
Joined: Mon. Dec. 27, 2010 1:59 am
Location: New Zealand
Stoker Coal Boiler: MK2 #1

Post by unhippy » Sat. Aug. 29, 2015 8:25 am

carlherrnstein wrote: you need to find out some things about the coal you plan on burning. Like is it going to clinker or will it burn to ash, and is it going to swell an stick together. Those two factors will massively effect the design of the burn pot. Those polish stoker units are built to burn anthracite, lignite, sub bituminous, and wood pellets. All of these fuels do not clinker, do not swell, and burn without much smoke. Some bituminous coal will clinker and will swell an fuse into a mass when burning however some does not but, all has a lot tars that burn with black smoke.

What you need to find out is the ash fusion temperature (this will tell you if it will clinker) and something called the coke button (this tells you how much it will swell)

If you havent already, you need to look at the many different types of stokers made. That will give you a idea of how they are made.

The polish stokers are most likely not going to burn bit coal well at all, it will smoke like a smudge pot and if the coal fuses the fire will drop off into the ash pit. I suggest searching prill stokers(they burn non swelling, non clinkering bit an sub bit. Combustioneer they burn swelling, clinkering bit.
Those particular fixed retort underfeed stokers from that company may have problems with coal that fuses together if it builds up a 'coke tree' and then falls over the side .......but they will burn clean up until that point.....i have been quietly looking around for Bit stoker's for the last year suitable for the boiler i'm lining up to build.....talked to a fair number of people in eastern europe that run the same burners I have looked at (Google translate is awesome!!).....

i initially wanted a burner with a rotating pot so I would be able to burn any coal mined in this country as about half of it (by volume) has between a 3.5 and a 9++ coke button number depending on where its mined.

One thing they said when I asked them about the burners without a rotating pot being run on high coke button bituminous coal was that they would burn clean even if you had to manually deal with the 'coke tree' a several times a day, even if the 'coke tree' fell off, only one had the fire go out completely, the rest all said that there was enough embers left in the burner that it just carried on running....those with the rotating pot type burners had almost no problems with the coal fusing together until they started burning metallurgical coal with a coke button of 8 or higher.

After hearing that and with much thought and considering the specs from the locally available coal (within 3 hours drive) I decided that I didn't need a rotating pot burner

If teddys design of burner turns out not to perform as well as is he wants/needs it to then if he could find a Combustioneer or something similar in good condition he would be sorted..... if he can't find something in the US then looking at some of the eastern european rotating pot stoker's is going to be his best option at that point.....as far as I know any of the manufactured stokers will probably need the coal to be resized down to pea size
Last edited by unhippy on Sat. Aug. 29, 2015 7:37 pm, edited 1 time in total.

 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Sat. Aug. 29, 2015 9:24 am

Here in the States I will occasionally come across a underfed bit stoker every so often. Anyone interested in one, I can pass on some info of what I discover. :idea:

Combustioneers, Winklers and Iron Fireman mostly, but you never know. :)

 
User avatar
SWPaDon
Member
Posts: 9857
Joined: Sun. Nov. 24, 2013 12:05 pm
Location: Southwest Pa.
Hand Fed Coal Furnace: Clayton 1600M
Coal Size/Type: Bituminous
Other Heating: Oil furnace

Post by SWPaDon » Sat. Aug. 29, 2015 9:36 am

There's still a Combustioneer for sale in Kentucky: **Broken Link(S) Removed**

 
User avatar
SWPaDon
Member
Posts: 9857
Joined: Sun. Nov. 24, 2013 12:05 pm
Location: Southwest Pa.
Hand Fed Coal Furnace: Clayton 1600M
Coal Size/Type: Bituminous
Other Heating: Oil furnace

Post by SWPaDon » Sat. Aug. 29, 2015 9:45 am

And here are 2 more Combustioneers: **Broken Link(S) Removed**

 
Pacowy
Member
Posts: 3555
Joined: Tue. Sep. 04, 2007 10:14 pm
Location: Dalton, MA
Stoker Coal Boiler: H.B. Smith 350 Mills boiler/EFM 85R stoker
Coal Size/Type: Buckwheat/anthracite

Post by Pacowy » Sat. Aug. 29, 2015 1:52 pm

unhippy wrote:If teddys design of burner turn out not to perform as well as is he wants/needs it to then if he could find a Combustioneer or something similar in good condition
I don't think he's going to find much of anything in an underfeed design that meets his spec of 6 lb/hr max feed rate. The smallest EFM I know of was 12.5; IIRC the smallest unit in the collection of Motor Stokors in my garage is 20. If an underfeed stoker turns out to be needed, I would like to know more about the sizing computations because they don't seem to align with the way equipment in the past has been designed to meet market needs.

Mike

 
User avatar
carlherrnstein
Member
Posts: 1542
Joined: Tue. Feb. 07, 2012 8:49 am
Location: Clarksburg, ohio
Hot Air Coal Stoker Stove: combustioneer model 77B
Coal Size/Type: pea stoker/Ohio bituminous

Post by carlherrnstein » Sat. Aug. 29, 2015 2:08 pm

I have gotten some tall coke trees in my combustioneer they always fall over and burn in the hearth. Combustioneers don't have a rotating ring, they are supposed to make clinkers that are removed with tongs. I know iron fireman and winkler stokers do the same.

You can change pulley sizes on the motor and gearbox to slow down the feed rate. You will just have to be mindful that you can only cut the air rate so much without putting a separate combustion fan in its place.

A under feed stoker is what is needed to burn coal that is high in volatiles (tar/oils) they cook out of the fresh coal and travel up through the fire and are either burned in the red hot coke bed or burn just above the fire.


 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Sat. Aug. 29, 2015 3:30 pm

You say a smaller under-fed stoker...how about the Alaska 140 Auger...it is a mini EFM under-fed stoker that can do wood pellets or rice coal.
Sadly, I do not think those are still in production today. However there are members here that own and still operate them each season.
New Burn Grates.jpg
.JPG | 190.3KB | New Burn Grates.jpg
See figure 9
AUGER FEED PADDLE FEED.pdf
.PDF | 589.5KB | AUGER FEED PADDLE FEED.pdf

 
unhippy
Member
Posts: 512
Joined: Mon. Dec. 27, 2010 1:59 am
Location: New Zealand
Stoker Coal Boiler: MK2 #1

Post by unhippy » Sat. Aug. 29, 2015 7:34 pm

Pacowy wrote:
I don't think he's going to find much of anything in an underfeed design that meets his spec of 6 lb/hr max feed rate. The smallest EFM I know of was 12.5; IIRC the smallest unit in the collection of Motor Stokors in my garage is 20. If an underfeed stoker turns out to be needed, I would like to know more about the sizing computations because they don't seem to align with the way equipment in the past has been designed to meet market needs.

Mike
I suspect that the 6 lb/hr feed rate that teddy has specified is a result of lack of knowledge/experience with running coal.... I doubt that he realises that you can idle an underfeed Bit stoker with practically no heat coming off it.....if your only solid fuel experience has been burning wood, the ability to 'turn the fire on and off at will' with a stoker is something that has to be seen to be believed.

 
Pacowy
Member
Posts: 3555
Joined: Tue. Sep. 04, 2007 10:14 pm
Location: Dalton, MA
Stoker Coal Boiler: H.B. Smith 350 Mills boiler/EFM 85R stoker
Coal Size/Type: Buckwheat/anthracite

Post by Pacowy » Sat. Aug. 29, 2015 8:45 pm

Thanks, unhippy, for that suggestion, and yes it seems like that is at least part of it. My main concern is that the overall system design (boiler, radiation and stoker) may be based on averages that, by definition, will not be able to carry the load under conditions more difficult than average.

Mike

P.S. McGiever I do think the Alaska 140 auger model is still sold, but I think it has the same limitations (auger tube size and minimum feed rate) as an EFM 350 or 520 that would limit its ability to burn bit at the specified 6 lb/hr.

 
Teddy
Member
Posts: 36
Joined: Tue. Aug. 18, 2015 5:34 pm
Stoker Coal Boiler: building coal burning boiler
Coal Size/Type: stoker 2"/bituminous

Post by Teddy » Sat. Aug. 29, 2015 10:37 pm

Somehow the last few posts to this topic have disappeared???? Anybody know what happened or do I need to reboot my computer? Teddy

 
Teddy
Member
Posts: 36
Joined: Tue. Aug. 18, 2015 5:34 pm
Stoker Coal Boiler: building coal burning boiler
Coal Size/Type: stoker 2"/bituminous

Post by Teddy » Sat. Aug. 29, 2015 11:02 pm

I found them!!!! Sorry. OK, back to work:

You are right - a lack of experience burning coal IS my problem. I have been afraid that running the burner at high fire then turning it off with no air would produce smoke wasting carbon and coating the heat exchanger tubing and flue, also would produce un-burned gasses which might explode when finally given air, also if the burner is too big would mean the fire is off for too long a time and would have to be relit. I know that burning any hydrocarbon in the 1600 to 1800 deg f range for 0.6 to 1.0 seconds will totally oxidize all the long chain molecules and well as the simple ones to CO2, H2O, if sulphur is in the fuel to SOx and at that temperature NOx. Therefore, I thought that I should also burn the coal in this temperature range which means surrounding it with firebrick and insulation, the firebrick to try to maintain the high temps at low fire. But no fire??? Really? Or is the theory that the coal is so cheap, why not waste some of it? I've seen reports of a black ring on the roof around the flue exit in one of these blogs - I would not like that. Wouldn't a clean burning high and low fire rate be a preferred objective and try to size the burner to accomplish that? Teddy

 
Teddy
Member
Posts: 36
Joined: Tue. Aug. 18, 2015 5:34 pm
Stoker Coal Boiler: building coal burning boiler
Coal Size/Type: stoker 2"/bituminous

Post by Teddy » Sat. Aug. 29, 2015 11:23 pm

Actually, there still is a large post by me that does not appear in this thread. I answered unhippys question about what kind of bike I raced. Anybody know where it is?

 
Teddy
Member
Posts: 36
Joined: Tue. Aug. 18, 2015 5:34 pm
Stoker Coal Boiler: building coal burning boiler
Coal Size/Type: stoker 2"/bituminous

Post by Teddy » Sat. Aug. 29, 2015 11:28 pm

I also explained the thermal demand and insulation values of my home and how I arrived at the required heat rate for the burner. That info is missing also????

 
User avatar
rockwood
Member
Posts: 1381
Joined: Sun. Sep. 21, 2008 7:37 pm
Location: Utah
Hot Air Coal Stoker Furnace: Stokermatic
Hand Fed Coal Stove: Rockwood Stoveworks Circulator
Baseburners & Antiques: Malleable/Monarch Range
Coal Size/Type: Lump and stoker + Blaschak-stove size

Post by rockwood » Sat. Aug. 29, 2015 11:34 pm

I don't know about the area where you live, but here in Utah underfeed stokers can still be found...there is one for sale right now http://www.ksl.com/index.php?nid=218&ad=35868579& ... r&ad_cid=4


Post Reply

Return to “Stoker Coal Furnaces & Stoves Using Anthracite (Hot Air)”