Post by tnf75 » Tue. Sep. 01, 2015 7:07 am

Thank You everyone ~

I will have the well cleaned out and purchase recommended aquastat.


 
User avatar
Rob R.
Site Moderator
Posts: 17980
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Wed. Sep. 02, 2015 4:34 am

One more thing, where is your aquastat well located? It should be on the back of the boiler next to the tankless coil.

Does your boiler have a bypass piped between the supply and return header? If not, the water in the boiler will stratify and the aquastat will get a false temperature reading.