OUTFIRE!!!
Well, this is the same type of stoker with exactly the same settings hooked to the same chimney as the BairMatic. I learned today that the boiler itself plays a roll in how the stoker runs.
This boiler puts a lot less heat into the chimney than the BairMatic did and I think that is a big part of the problem. After I re-lit it, the flue temp only got up to 350 degrees right before it shut down on the HI limit.
The chimney draft only goes up to -.025. It was 90 degrees today though.
I didn't check the timer before lighting up the VA-600. Turns out that it was set for 1 minute every hour. I don't think the VA-600 likes that. I bumped it up to 2.5 minutes every hour. If that doesn't work we will try 2 minutes every 30. I also bumped the HI limit up to 180 and lowered the air to 4.
Current settings are:
Feed rate = 10 pounds per hour
Air = 4.0
LO limit = 130
HI limit = 180
DIFF = 10
Timer = 2.5 minutes every hour
I got the 2 fire view door videos up loaded.
https://www.youtube.com/watch?v=wZHBT-mmNl8&index=18&list=PLFU8SaWNbzx-riP8MZ8iWJ4g1_hcLDsHI
Check out what happens at about 1:25 on the second video. The flame seems to come down from the top of the fire box to meet the coal.