Aquastat Wiring for Outfire
-
- Member
- Posts: 27
- Joined: Sun. Dec. 21, 2014 8:21 am
- Location: Mt. Carmel
- Stoker Coal Boiler: EFM 520
- Coal Size/Type: Rice
I have a Honeywell 6006A aquastat that I would like to use as an outfire control on my EFM. Although I have piped and wired a few stokers in the past I have never put an outfire control on them. The schematic shows that R B opens and R W closes on temperature increase. Am I correct to assume that I will only be using the R and W terminals???? Also, does it matter which terminal I connect the incoming hot line to?? I understand the need for a bypass switch to restart the boiler. Any help will be greatly appreciated.
- McGiever
- Member
- Posts: 10130
- Joined: Sun. May. 02, 2010 11:26 pm
- Location: Junction of PA-OH-WV
- Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
- Hand Fed Coal Boiler: BUCKET A DAY water heater
- Hand Fed Coal Stove: Warm Morning 414A
- Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
- Other Heating: Ground Source Heat Pump and some Solar
You got it!
And it does not matter which.
Proceed with confidence, my Friend.
And it does not matter which.
Proceed with confidence, my Friend.
-