Post by CoalHeat » Sat. Oct. 01, 2016 10:33 pm

Could be you just have a very low draft at idle in this weather. The baro doesn't move because the draft isn't going above what it's set for. We need a nice windy day.

Do you have a working CO detector in the house near where the stove is located?

Describe the chimney please. Tall/short, chimney block/other, flue size, etc.

 
Ribsyj
Member
Posts: 21
Joined: Mon. Aug. 08, 2016 8:18 pm
Location: NEPA
Hot Air Coal Stoker Stove: Leisure line ak-110

Post by Ribsyj » Mon. Oct. 03, 2016 12:51 pm

After speaking to leisure line they seem to think issue is stove minimum feed. With warmer weather I need to turn feed so low to keep temperature in house down I'm losing draft. They recommended turning it up or install draft inducer to get the .04 wc.

 
Ribsyj
Member
Posts: 21
Joined: Mon. Aug. 08, 2016 8:18 pm
Location: NEPA
Hot Air Coal Stoker Stove: Leisure line ak-110

Post by Ribsyj » Mon. Oct. 03, 2016 12:52 pm

On other posts. Chimney is two story and about 2ft above roof. New 8" round flue and is clear. Have two working co monitors on first floor stove in basement

 
titleist1
Member
Posts: 5226
Joined: Wed. Nov. 14, 2007 4:06 pm

Post by titleist1 » Mon. Oct. 03, 2016 2:19 pm

What is the range your manometer is able to measure? Something like 0.01 - 0.10" of H2O is what you want. Your draft is probably going to be close to 0.02. If your gauge starts measuring at 0.10 then you won't see a reading.


 
Ribsyj
Member
Posts: 21
Joined: Mon. Aug. 08, 2016 8:18 pm
Location: NEPA
Hot Air Coal Stoker Stove: Leisure line ak-110

Post by Ribsyj » Mon. Oct. 03, 2016 2:23 pm

Measures 0.00

 
titleist1
Member
Posts: 5226
Joined: Wed. Nov. 14, 2007 4:06 pm

Post by titleist1 » Mon. Oct. 03, 2016 2:25 pm

One of those 477 models goes from 0 - 200" water, that would not be the one I want to try to measure 0.02" of water. Do you know if you have the -000 or -00 model?

 
User avatar
WNY
Member
Posts: 6307
Joined: Mon. Nov. 14, 2005 8:40 am
Location: Cuba, NY
Hot Air Coal Stoker Stove: Keystoker 90K, Leisure Line Hyfire I
Coal Size/Type: Rice
Contact:

Post by WNY » Sat. Dec. 24, 2016 3:06 pm

bump the MIN up a couple numbers at a time and keep an eye on your draft with a gauge. sometimes in the warmer weather, that happens, and you need a little more heat to maintain a good draft.

I've seen mine as low as .02 or so, but never had a problem with draft even on 50 deg days. depends on your chimney too.

Like they said, make sure you have at least one good working CO detector. it can back feed easily if you dont' have enough draft.

do you have a Baro Damper, is it adjusted correctly.?