AA 130 Install

 
User avatar
lsayre
Member
Posts: 21781
Joined: Wed. Nov. 23, 2005 9:17 pm
Location: Ohio
Stoker Coal Boiler: AHS S130 Coal Gun
Coal Size/Type: Lehigh Anthracite Pea
Other Heating: Resistance Boiler (13.5 KW), ComfortMax 75

Post by lsayre » Fri. Oct. 28, 2016 7:55 pm

Rob R. wrote:Heating domestic hot water for two homes is actually better - because there is a better chance of the BTU's produced by the idling boiler going into the domestic hot water rather than the atmosphere. If it were me I would probably try running the AA and see how it does, but to each their own.
I agree. The savings may still benefit the AA over pellets. Unless a pellet boiler is inherently more efficient, which I doubt.


 
ziggy87
Member
Posts: 312
Joined: Sat. Oct. 25, 2014 11:22 am
Location: Halifax, Pa
Stoker Coal Boiler: axeman anderson 130
Coal Size/Type: Pea

Post by ziggy87 » Fri. Oct. 28, 2016 10:20 pm

We will see how things go running the boiler in the summer. Time will tell. I know that it is well worth it to keep a boiler warm. I use to work for a local fuel oil company doing furnace cleanings. You could always tell which boilers ran year round. It was a shame to see a ten year old boiler that looked 40 years old. Thank you for all the input so far I really appreciate it. I am hoping to pick up pipe and fittings by the of the week if all goes as planned and the phone does not ring off the hook for furnace work. But I guess as the saying goes, " the shoe makers' kids always get shoes last."

Jason

 
User avatar
Townsend
Member
Posts: 573
Joined: Tue. Nov. 21, 2006 7:38 pm
Location: Connecticut
Hand Fed Coal Stove: Hitzer 50-93 & Harman Mark I
Coal Size/Type: Pea / Nut

Post by Townsend » Mon. Oct. 31, 2016 10:39 am

My Axeman is similar to Mozz, heats my basement very toasty! In fact, I'm taking the ceiling insulation out of the basement. It's around 80 down there especially with that huge header piping I have. I should wrap it to conserve but I haven't got around to it.

Coaledsweat, you don't get warm down there cause your 260 is at idle pretty much with that small load it has! That pot just idles then rises a bit for heat cycle. Plus, you set the thermostat to 60! I like mine at 70!

 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Mon. Oct. 31, 2016 10:58 am

coaledsweat wrote:
ziggy87 wrote:Thank you that is good to know.
Also forgot to add, possibly looking to use a digital temp controller for ashing since there was no anthrastat with the unit. Anyone with any experience on this?
Best to just buy an anthrastat from Axeman, a beginner doesn't need a science project to add to their adventure. :)
That is sound logic there, but as for the pocket book goes that $30.00 Amazon Digital Controller doesn't hurt near as bad on any day, but the money saved can buy a bunch of fittings for on a installation day. ;)

All them AHS Coal Guns w/ digitals can't be wrong. 8-)
Last edited by McGiever on Mon. Oct. 31, 2016 11:00 am, edited 1 time in total.

 
User avatar
coaledsweat
Site Moderator
Posts: 13767
Joined: Fri. Oct. 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stoker Coal Boiler: Axeman Anderson 260M
Coal Size/Type: Pea

Post by coaledsweat » Mon. Oct. 31, 2016 11:00 am

It's a war here, I turn it up, she turns it down! :)

Yes, the beast is always loafing and laughs at heat calls.

 
User avatar
Rob R.
Site Moderator
Posts: 18004
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Mon. Oct. 31, 2016 11:05 am

Townsend wrote:My Axeman is similar to Mozz, heats my basement very toasty! In fact, I'm taking the ceiling insulation out of the basement. It's around 80 down there especially with that huge header piping I have. I should wrap it to conserve but I haven't got around to it.

Coaledsweat, you don't get warm down there cause your 260 is at idle pretty much with that small load it has!
That pot just idles then rises a bit for heat cycle. Plus, you set the thermostat to 60! I like mine at 70!
bingo. Whistlenut brought me to see a 260 heating a 10 unit apartment building. The boiler room was HOT. I think the radiant heat from the boiler would have heated a small house.

insulating that steam piping would really help...should also reduce the pickup load on repeat heat calls.

 
ziggy87
Member
Posts: 312
Joined: Sat. Oct. 25, 2014 11:22 am
Location: Halifax, Pa
Stoker Coal Boiler: axeman anderson 130
Coal Size/Type: Pea

Post by ziggy87 » Fri. Oct. 27, 2017 10:04 pm

IMG_0310.JPG

Side of building where chimney will go

.JPG | 988.3KB | IMG_0310.JPG
IMG_0312.JPG

Building in reference to house

.JPG | 896.5KB | IMG_0312.JPG
IMG_0314.JPG

Boiler and coal bin location

.JPG | 1034.1KB | IMG_0314.JPG
Finally have a chance to work on getting my boiler in. I will be putting up a 6" schedule 40 steel pipe chimney on the side of the building about 15' tall. Hope the house does not interfere with draft. I have 84' of 1-1/4 blk pipe and fittings being delivered Monday. So hopefully in 2 weeks I will be up and running.


 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Sat. Oct. 28, 2017 12:54 am

We're Pull'in for You :)

 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Sat. Oct. 28, 2017 4:40 am

Giddey up & go!

 
User avatar
Rob R.
Site Moderator
Posts: 18004
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Sat. Oct. 28, 2017 7:24 am

I will be putting up a 6" schedule 40 steel pipe chimney on the side of the building about 15' tall.
That seems like a bad idea to me, but I will be interested to hear how well that drafts once you get the boiler running.

 
User avatar
coaledsweat
Site Moderator
Posts: 13767
Joined: Fri. Oct. 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stoker Coal Boiler: Axeman Anderson 260M
Coal Size/Type: Pea

Post by coaledsweat » Sat. Oct. 28, 2017 7:58 am

Why would it be a bad idea?

 
CapeCoaler
Member
Posts: 6515
Joined: Sun. Feb. 10, 2008 3:48 pm
Location: Cape Cod, MA
Stoker Coal Boiler: want AA130
Hand Fed Coal Stove: DS Machine BS#4, Harman MKII, Hitzer 503,...
Coal Size/Type: Pea/Nut/Stove

Post by CapeCoaler » Sat. Oct. 28, 2017 11:03 am

outside steel pipe will be cold...
condensing exhaust gas...

 
ziggy87
Member
Posts: 312
Joined: Sat. Oct. 25, 2014 11:22 am
Location: Halifax, Pa
Stoker Coal Boiler: axeman anderson 130
Coal Size/Type: Pea

Post by ziggy87 » Sat. Oct. 28, 2017 7:20 pm

CapeCoaler wrote:
Sat. Oct. 28, 2017 11:03 am
outside steel pipe will be cold...
condensing exhaust gas...
Yes I thought about that, but that's what is in the budget right now. I will see how it does and go from there.

 
ziggy87
Member
Posts: 312
Joined: Sat. Oct. 25, 2014 11:22 am
Location: Halifax, Pa
Stoker Coal Boiler: axeman anderson 130
Coal Size/Type: Pea

Post by ziggy87 » Sat. Oct. 28, 2017 7:24 pm

McGiever wrote:
Wed. Oct. 26, 2016 10:51 pm
Here's some reading at Link >>> How Should an AA130's Fire Look at Full Burn?
On the type K thermocouple do you just have attached to the anthrastat. Going to be ordering a digital temp controller when I get home tonight.

 
User avatar
McGiever
Member
Posts: 10130
Joined: Sun. May. 02, 2010 11:26 pm
Location: Junction of PA-OH-WV
Stoker Coal Boiler: AXEMAN-ANDERSON 130 "1959"
Hand Fed Coal Boiler: BUCKET A DAY water heater
Hand Fed Coal Stove: Warm Morning 414A
Coal Size/Type: PEA,NUT,STOVE /ANTHRACITE
Other Heating: Ground Source Heat Pump and some Solar

Post by McGiever » Sat. Oct. 28, 2017 10:34 pm

Anthrastat is not used.

Digital controller takes Anthrastat's place.

K thermocouple probe can mount same location as where Anthrastat's probe was at.


Post Reply

Return to “Stoker Coal Boilers Using Anthracite (Hydronic & Steam)”