have a keystoker 90, been having issues with it since day one this year. everything was cleaned, now it seems the coal is building up to about 2" on the grate and the temp on stove is at 200 deg. I have the feed at the slowest possible. im sure i'll have more Q's to follow, but any help would be greatly appreciated.

 
Olllotj
Member
Posts: 558
Joined: Thu. Sep. 04, 2014 10:01 am
Location: Western NY 14141
Stoker Coal Boiler: Keystoker KB-8
Coal Size/Type: Buckwheat
Other Heating: Utica Propane Hot Water

Post by Olllotj » Tue. Dec. 13, 2016 2:22 pm

is the thermostat calling for heat?

 
User avatar
2001Sierra
Member
Posts: 2211
Joined: Wed. May. 20, 2009 8:09 am
Location: Wynantskill NY, 10 miles from Albany
Hot Air Coal Stoker Stove: Keystoker 90 Chimney vent
Coal Size/Type: Rice
Other Heating: Buderus Oil Boiler 3115-34

Post by 2001Sierra » Tue. Dec. 13, 2016 2:36 pm

Combustion fan clean and running continuosly? Coal-trol or Keystoker controlling the stove?


 
User avatar
WNY
Member
Posts: 6307
Joined: Mon. Nov. 14, 2005 8:40 am
Location: Cuba, NY
Hot Air Coal Stoker Stove: Keystoker 90K, Leisure Line Hyfire I
Coal Size/Type: Rice
Contact:

Post by WNY » Tue. Dec. 13, 2016 6:22 pm

Thermostat or CoalTrol for temp. control?

A few more details would be helpful. Many of have keystokers, or similar stoves. they all operate about the same.

Sounds like your only running on the TIMER box if equipped and not thermostat.

 
KLook
Member
Posts: 5791
Joined: Sun. Feb. 17, 2008 1:08 pm
Location: Harrison, Tenn
Other Heating: Wishing it was cold enough for coal here....not really

Post by KLook » Tue. Dec. 13, 2016 9:13 pm

I read that as the coal is building up to deep on the plate. I had to sand the cast iron plates one year as the coal would not slide on them. Maybe you have some roughness from over the summer?

Kevin

 
User avatar
oliver power
Member
Posts: 2970
Joined: Sun. Apr. 16, 2006 9:28 am
Location: Near Dansville, NY
Stoker Coal Boiler: KEYSTOKER Kaa-2
Hand Fed Coal Stove: Hitzer 50-93 & 30-95, Vigilant (pre-2310), D.S. 1600 Circulator, Hitzer 254

Post by oliver power » Wed. Dec. 14, 2016 2:11 am

You say you've had problems since day one this year. Does this mean the stove ran fine last year? Or, is this a new install this year?

A couple things to try:
1.) As mentioned, smooth grate surface.
2.) Is the stoker side of stove plumb? (Stoker flange needs to be plumb)
3. Are you putting wet coal through the stove? (Damp fines sticking together)