Same Flue for Oil and Coal Boilers???

 
biggreen1
Member
Posts: 173
Joined: Wed. May. 14, 2008 7:39 pm

Post by biggreen1 » Wed. May. 14, 2008 7:54 pm

Hello everyone,
I just found this site, its great. I haven't found a answer to this question. Can you use the same flue for the oil and coal boilers or should they always have their own. My plan was to install a coal boiler to the same flue, but a contractor just told me that you never do that. Is he correct????


 
User avatar
Rob R.
Site Moderator
Posts: 18004
Joined: Fri. Dec. 28, 2007 4:26 pm
Location: Chazy, NY
Stoker Coal Boiler: EFM 520
Hand Fed Coal Stove: Chubby Jr

Post by Rob R. » Wed. May. 14, 2008 8:18 pm

Your contractor is correct, it is against building code. That said, my house has had a radiant stove and oil boiler hooked into the same chimney for 30+ years. If you have the option, you may want to power vent the oil boiler and run the coal boiler into the chimney.

 
User avatar
coalkirk
Member
Posts: 5185
Joined: Wed. May. 17, 2006 8:12 pm
Location: Forest Hill MD
Stoker Coal Boiler: 1981 EFM DF520 retired
Hand Fed Coal Stove: Jotul 507 on standby
Coal Size/Type: Lehigh anthracite/rice coal

Post by coalkirk » Wed. May. 14, 2008 9:44 pm

It's also most likley that once you have the coal boiler hooked up, you won't need to use the oil burner. They certainly should not fire at the same time.

 
rberq
Member
Posts: 6446
Joined: Mon. Apr. 16, 2007 9:34 pm
Location: Central Maine
Hand Fed Coal Stove: DS Machine 1300 with hopper
Coal Size/Type: Blaschak Anthracite Nut
Other Heating: Oil hot water radiators (fuel oil); propane

Post by rberq » Wed. May. 14, 2008 10:20 pm

Forgetting for a moment that it's against code, why couldn't the oil and the coal boilers be on the same flue and fire at the same time? The baro for my oil burner is set for very low draft, much less draft than the chimney can produce, and it could handle a considerably bigger oil burner than is actually installed. So what's the difference between running coal and oil together into one flue, or running an oil burner twice as big? I think when I was on the Field Controls web site looking at diagrams on how to mount the baro, they had examples of how to combine several appliances into one flue, and where to mount the individual baros for the individual burners. Or did I dream that .... I'm never sure anymore.... :|

 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Wed. May. 14, 2008 11:05 pm

It's just big brother protecting us from ourselves. Yes, it's against code, I'll assume everywhere now. Yes, it has been done without issue. I always thought it stemmed from a wood stove and some other appliance in the same flu. If there's a chimney fire with just a wood stove, you shut down the air & the fire goes out. If there's a boiler in the same flu, the damper allows air to feed the fire.

 
User avatar
Sting
Member
Posts: 2983
Joined: Mon. Feb. 25, 2008 4:24 pm
Location: Lower Fox Valley = Wisconsin
Other Heating: OBSO Lennox Pulse "Air Scorcher" burning NG

Post by Sting » Thu. May. 15, 2008 8:02 am

rberq wrote: I think when I was on the Field Controls web site looking at diagrams on how to mount the baro, they had examples of how to combine several appliances into one flue, and where to mount the individual baros for the individual burners. Or did I dream that .... I'm never sure anymore.... :|
The examples are for like appliances.

 
User avatar
coaledsweat
Site Moderator
Posts: 13767
Joined: Fri. Oct. 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stoker Coal Boiler: Axeman Anderson 260M
Coal Size/Type: Pea

Post by coaledsweat » Thu. May. 15, 2008 8:36 am

coalkirk wrote: They certainly should not fire at the same time.
Not true, they can operate together or independantly if done right. Anyone that wants to do this can PM me for Burnam Boiler's recommendations in the proper installation. I don't advise it as it is against code, but the code is wrong when it comes to coal. I think the concern is that a lot of coal appliances will also see wood burned in them at some point.


 
biggreen1
Member
Posts: 173
Joined: Wed. May. 14, 2008 7:39 pm

Post by biggreen1 » Thu. May. 15, 2008 8:53 pm

So it seems as though it's actually OK but against code. But generally, you should not try to run both at the same time. Thank you for all the responses

 
User avatar
coaledsweat
Site Moderator
Posts: 13767
Joined: Fri. Oct. 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stoker Coal Boiler: Axeman Anderson 260M
Coal Size/Type: Pea

Post by coaledsweat » Thu. May. 15, 2008 10:45 pm

biggreen1 wrote:you should not try to run both at the same time.
Except at startup, the need for running both would be a highly unlikely event anyway unless the solid fuel appliance was undersized for the load or the domestic water is off the oil burner.

 
User avatar
CoalHeat
Member
Posts: 8862
Joined: Sat. Feb. 10, 2007 9:48 pm
Location: Stillwater, New Jersey
Stoker Coal Boiler: 1959 EFM 350
Hand Fed Coal Stove: Harman Magnafire Mark I
Baseburners & Antiques: Sears Signal Oak 15 & Andes Kitchen Range
Coal Size/Type: Rice and Chestnut
Other Heating: Fisher Fireplace Insert

Post by CoalHeat » Fri. May. 16, 2008 8:49 pm

It is against code but it can be done. I know someone who did it. :twisted:
I don't recommend doing anything that is against building codes.

 
syncmaster
Member
Posts: 300
Joined: Sat. Apr. 19, 2008 1:29 pm
Location: long Island,NY
Stoker Coal Boiler: harmanVF3000 Coal/oil option
Coal Size/Type: Rice

Post by syncmaster » Fri. May. 30, 2008 8:51 pm

I just talked to a chimney guy on long Island,NY and he said you can have 2 devices like coal stove and oil burner in the same chimney but the chimney flu must be 7" and the 2 devices are 6" each. he said you cannot share a chimney with a wood burning device.
If you want to connect a oil burner and a coal boiler in the same chimney.
the Harman VF3000 coal boiler has a 6" chimney pipe.
the keystoker KAA-2 coal boiler has a 6" chimney pipe.
the AHS-S130 coal boiler has a 5" chimney pipe.

of course check your local codes before doing this.
Last edited by syncmaster on Fri. May. 30, 2008 9:50 pm, edited 3 times in total.

 
User avatar
coaledsweat
Site Moderator
Posts: 13767
Joined: Fri. Oct. 27, 2006 2:05 pm
Location: Guilford, Connecticut
Stoker Coal Boiler: Axeman Anderson 260M
Coal Size/Type: Pea

Post by coaledsweat » Fri. May. 30, 2008 9:12 pm

syncmaster wrote:I just talked to a chimney guy on long Island,NY and he said you can have 2 devices like coal stove and oil burner in the same chimney but the chimney flu must be 7" and the 2 devices are 6" each. he said you cannot share a chimney with a wood burning device.
If you want to connect a oil burner and a coal boiler in the same chimney.
the Harman VF3000 coal boiler has a 6" chimney pipe.
Your saying they must share a common thimble? This is what Burnham Boiler recommends, the two are connected by stovepipe prior to the chimney.

 
syncmaster
Member
Posts: 300
Joined: Sat. Apr. 19, 2008 1:29 pm
Location: long Island,NY
Stoker Coal Boiler: harmanVF3000 Coal/oil option
Coal Size/Type: Rice

Post by syncmaster » Fri. May. 30, 2008 9:31 pm

coaledsweat wrote:[

Your saying they must share a common thimble? This is what Burnham Boiler recommends, the two are connected by stovepipe prior to the chimney.
Yes, that is right the two 6" heating devices can share the 7" chimney through a common thimble.

 
syncmaster
Member
Posts: 300
Joined: Sat. Apr. 19, 2008 1:29 pm
Location: long Island,NY
Stoker Coal Boiler: harmanVF3000 Coal/oil option
Coal Size/Type: Rice

Post by syncmaster » Fri. May. 30, 2008 10:27 pm

If sharing a chimney is not allowed where you live another alternitive if your oil boiler chimney has a 7" flu.
You can replace you oil boiler with a Harman vf3000 with a optional oil burner.
to change from burnning coal to oil you must remove a cover that covers the oil nozzle and flick a switch from coal to oil.
the price for the VF3000 is as follows:
vf3000 boiler with hopper and stoker $4200.00
oil burner option $750.00
DHW coil $250.00
total $5200.00 plus shipping and tax

 
wannabwarm
New Member
Posts: 18
Joined: Fri. May. 16, 2008 9:56 pm
Location: Reading, MA

Post by wannabwarm » Sat. May. 31, 2008 10:01 pm

Reading all your input has been a great learning exp for me. While we are on the subject is there any problem with having two coal fired units with 6" flues connected to the same 8" SS chimney?


Post Reply

Return to “Coal Bins, Chimneys, CO Detectors & Thermostats”