Direct Vent Vs Power Vent and Code

Post Reply
 
keithonline
New Member
Posts: 11
Joined: Fri. Jun. 13, 2008 10:46 pm

Post by keithonline » Fri. Jun. 20, 2008 7:04 pm

I'm considering the Alaska 140 or Keystoker Koker. First, I can't find an install manual for the Koker. Does anyone have one? What I can find on the 140 is limited too. I'm a bit confused about power vent vs direct vent. On Alaska's website, it seems to imply you can direct vent some units. I'm assuming direct vent means no fan in the process. Is this possible? I could put the unit right against the wall if needed to minimize the horizontal run.

Also curious if anyone has any suggestions about how much separation I would need between the cold air inlet from my house's return ducts to where I duct in the hot air from the coal furnace? I understand I'll have to relay my wholehouse furnace fan to kick on, but I'm a bit concerned about the duct layouts. Any help is appreciated. Thanks!

 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Fri. Jun. 20, 2008 8:22 pm

A direct vent has a fan, but it's a built in part of the stove and smaller, using less electricity. A power venter is a seperate unit. They can be adjusted to fit a varity of different units. Consequently they use more electricity.

 
User avatar
gaw
Member
Posts: 4464
Joined: Fri. Jan. 26, 2007 2:51 am
Location: Parts Unknown
Stoker Coal Boiler: Keystoker KA-6
Coal Size/Type: Rice from Schuylkill County

Post by gaw » Fri. Jun. 20, 2008 9:26 pm

I don't know if there is a difference between direct vent and power vent as far as the terms go and what they refer to. There is a system that uses a fan at the end of the pipe to draw the exhaust out of the stove and a system that mounts a fan directly on the rear of the stove to draw the exhaust from the stove and then push the exhaust under positive pressure out the exhaust pipe. Keystoker uses the later system, I don't know about Alaska. Any power vented system on a coal stove would have to run constantly as long as there was fire in the stove.

A naturally drafting chimney is the only system I know of that uses no power and is by far the best way to go if at all possible. Unfortunately a chimney is not always possible or practical for some applications.

 
User avatar
stoker-man
Verified Business Rep.
Posts: 2071
Joined: Mon. Nov. 19, 2007 9:33 pm
Location: Lehigh Valley, PA
Hand Fed Coal Boiler: 1981 efm wcb-24 in use 365 days a year
Coal Size/Type: Anthracite/Chestnut
Other Heating: Hearthstone wood stove

Post by stoker-man » Sat. Jun. 21, 2008 6:45 am

Using an oil burner for the example, a power venter would attach to the exhaust pipe of a unit between the barometric damper and the wall vent. It would start exhausting as soon as the oil burner motor started up. The burner motor fan would supply room air or outside air for the combustion and the power venter would create the negative draft usually supplied by a chimney.

In a direct vent application, a double walled pipe is used to supply fresh air and vent exhaust air to the outside wall of the house.

There are rules governing how far these vents can be from windows, doors, fresh air intakes etc.


 
User avatar
Devil505
Member
Posts: 7102
Joined: Tue. Jul. 03, 2007 10:44 pm
Location: SE Massachusetts

Post by Devil505 » Sat. Jun. 21, 2008 8:10 am

My opinion is this: Unless you have legitimate reasons for not building a masonry chimney, it makes little sense to power vent.
If you consider this:
1. A masonry chimney will last practically forever & probably never require maintenance in your lifetime (not even cleaning if you just burn anthracite coal)
2. A masonry chimney costs nothing to run & emits no noise
3. Once you deduct the cost of what a power vent would cost, a block & clay lined chimney is not that much more expensive (& can be faced with brick if looks are important)
4. A masonry chimney operates fine in power failures......a power vent means you lose your fire.

I would never power vent unless I had absolutely no alternative.

Just an opinion

 
keithonline
New Member
Posts: 11
Joined: Fri. Jun. 13, 2008 10:46 pm

Post by keithonline » Sun. Jun. 22, 2008 11:13 pm

I have two flues in my chimney. One goes to my fireplace on the main level, the other one goes to my oil fired furnace and oil DHW in the basement (yes into one flue, that's how the house was built in 1986). I don't want to put the Koker or 140 to that one flue, but I want it near the other furnace. I only have one wall I can come out of there. The basement at that point is a half foundation, and outside that wall is my deck. My town inspector said there is no code stating if I can go out that wall, and it must be installed per the mfg instructions. I can't find info on these two units about how to install them. I could power vent, but if I could install in near the exterior wall, and if the exhaust vent is low on the unit, would a 2-3 foot vert run, and 2' horiz run outside the wall give me enough draft without a direct/power vent? Seems like a type of install someone has probably tried.

 
User avatar
Devil505
Member
Posts: 7102
Joined: Tue. Jul. 03, 2007 10:44 pm
Location: SE Massachusetts

Post by Devil505 » Mon. Jun. 23, 2008 6:54 am

Not an expert on power venting but I've read allot of suggestions to vent your oil burner into a power vent (since it will be on rarely) & vent your coal stove/furnace into the chimney in place of the oil burner. (If you power vent your coal stove/furnace you will need to run the power vent 24/7)

Post Reply

Return to “Stoker Coal Furnaces & Stoves Using Anthracite (Hot Air)”