Coal Trol/Keystoker/Dual Blowers

Coal Trol/Keystoker/Dual Blowers

PostBy: jrn8265 On: Wed Jul 30, 2008 6:28 am

I purchased a Keystoker 105 with the Coal Trol.

In my setup I want to use my oil furnace blower. Need it to come on when the Keystokers 350cfm blower comes on. How exactly do I wire the Coal Trol to operate both blowers? Thanks!
jrn8265
Member
 
Posts: 890
Joined: Tue Jul 22, 2008 11:52 am
Location: Near Coal Country, PA
Stove/Furnace Make: Keystoker Koker
Stove/Furnace Model: Koker 160


Re: Coal Trol/Keystoker/Dual Blowers

PostBy: WNY On: Wed Jul 30, 2008 7:04 am

You will probably have to hook an external relay, the output of the coaltrol to the blowers is only 2-3 amps, I believe. The furnance blower proably draws more than that....

Neil/Paul would probably have more insight....
User avatar
WNY
Site Moderator
 
Posts: 5452
Joined: Mon Nov 14, 2005 9:40 am
Location: Cuba, NY
Stove/Furnace Make: Keystoker, LL & CoalTrol
Stove/Furnace Model: 90K, Hyfire I, VF3000 Soon

Re: Coal Trol/Keystoker/Dual Blowers

PostBy: pvolcko On: Thu Jul 31, 2008 12:07 pm

Jrn,

I've sent you a PM about this. We offer a set of dry contacts on our Advanced models that is specifically for this purpose. It can be wired to the control circuit of your furnace to turn on the blower under the control of the Coal-trol. Please contact us for more information so a change to your order for the Keystoker can be made should you want to take this option. 315-299-3589.