Expansion tank, circulator locations

Expansion tank, circulator locations

PostBy: Machinist On: Fri Sep 12, 2008 3:26 pm

I am beginning to plumb my Keystoker boiler and I am having trouble deciding where to locate the expansion tank and circulators. The best location for me seems to be against the stone foundation of my home. Is this a bad idea?

The foundation is about 2' thick and has about 1' exposed outside above ground level, not insulated.
The basement is only 65" high to the bottom of the floor joists. Bump my head often!
The nearest window will be about 4' away and will be the future coal chute.
The boiler will be located between the window and the expansion tank, circulators.

Looking forward to warm showers again!
Machinist
 
Stoker Coal Boiler: Keystoker KAA-2
Coal Size/Type: Rice
Other Heating: None

Re: Expansion tank, circulator locations

PostBy: titleist1 On: Fri Sep 12, 2008 4:29 pm

"Looking forward to warm showers again!"


Well, To quote Clint from Heartbreak Ridge.......

Just because we are holding hands
doesn't mean we'll take warm showers
until the wee hours of the morning.

But to answer your question....It wouldn't seem to be a good idea to have it directly against the stone foundation. Most I have seen are mounted between the ceiling joists.
titleist1
 
Hot Air Coal Stoker Stove: Harman Mag Stoker (old style) one in basement, one in workshop
Hand Fed Coal Stove: Harman Mark III on standby for long power outages
Coal Size/Type: Rice/Anthracite; Nut/Anthracite

Re: Expansion tank, circulator locations

PostBy: Machinist On: Fri Sep 12, 2008 5:12 pm

I have a very small basement. Along with the boiler there is a washer, dryer and future 4 ton coal bin. So I am looking to maximize the space, make things easily serviceable and certainly freeze resistant.

Would 2" foam board insulation between the foundation wall and equipment help?
Machinist
 
Stoker Coal Boiler: Keystoker KAA-2
Coal Size/Type: Rice
Other Heating: None


Re: Expansion tank, circulator locations

PostBy: TGMC On: Fri Sep 12, 2008 6:29 pm

mike
my keystoker boiler is under my concrete/block front porch and it is only 8"away from the wall. my exposure on that wall is 3 ' and i have no problems. just keep the plumbing away from the walls and insulate the pipes for best results.
good luck
TGMC
 
Stove/Furnace Make: KEYSTOKER
Stove/Furnace Model: KB 8

Re: Expansion tank, circulator locations

PostBy: Freddy On: Fri Sep 12, 2008 7:00 pm

Machinist wrote:Would 2" foam board insulation between the foundation wall and equipment help?


Yes, but it can't be left uncovered. Code requires it to be covered. Sheetrock usually.
Freddy
 
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Hot Air Coal Stoker Stove: Reading piece o' junk in the barn (rice)
Coal Size/Type: Pea size, Superior, deep mined

Re: Expansion tank, circulator locations

PostBy: Dallas On: Fri Sep 12, 2008 7:04 pm

I don't understand the problem. Usually the circulators are mounted right on the pipes as they enter the boiler and the expansion tank and auto fill valve are located right above the boiler before the line drops to the boiler. Aren't they?
Dallas
 
Hand Fed Coal Stove: Modified Russo C-35
Other Heating: Oil Hot Air
Stove/Furnace Make: Russo
Stove/Furnace Model: Modified C-35

Re: Expansion tank, circulator locations

PostBy: Machinist On: Fri Sep 12, 2008 7:46 pm

Dallas wrote:I don't understand the problem. Usually the circulators are mounted right on the pipes as they enter the boiler and the expansion tank and auto fill valve are located right above the boiler before the line drops to the boiler. Aren't they?


It's a small boiler about 23 x 28" x 36" tall on 2" thick blocks, in a low basement(65"). Doesn't leave much room above for a fill-trol (27" tall) and circulator pumps.
I am thinking of piping the feed line up, 25" and behind the boiler 45" to the wall then 1 foot or so to the right to leave room to service the vent. Then mount the fill-trol, circulator pumps, flow checks along the wall.

I like TGMC's and Freddy's comments, maybe a combination of both.
Thanks
Machinist
 