Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Sun. Sep. 14, 2008 2:16 pm

I have a L6006A high limit aquastat that shuts the boiler down if the temp hits 230. It opens a set of terminals to make that happen. At the same time it closes another set of terminals. Is that closing set of terminals what I'd use to turn on a circulator to a baseboard? The wiring diagram that comes with the boiler does not show a dump zone. Or.. with the Axeman Anderson is this something that I just do not need?

 
User avatar
billw
Member
Posts: 1089
Joined: Mon. Apr. 24, 2006 5:40 pm
Location: Dallas, PA

Post by billw » Sun. Sep. 14, 2008 2:46 pm

Freddy,
The set of contacts that make (close) when the temp rises past the setpoint is where you want to tie your pump to. Once the setpoint is exceeded the pump comes on and blows off the excess heat. When the temp comes down the contacts then open and the pump shuts off.


 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Sun. Sep. 14, 2008 3:10 pm

Cool beans. Thanks!