Power Venter Clearances

Post Reply
 
User avatar
heatwithcoal
Member
Posts: 248
Joined: Wed. Sep. 12, 2007 9:48 pm
Location: Western Massachusetts
Hot Air Coal Stoker Furnace: AK-110

Post by heatwithcoal » Sat. Oct. 04, 2008 3:54 pm

Ok, so I have looked a number of places online for horizontal clearances to a window spec. I have found:

9"horizontal clearance for stoves under 50K BTU and 1' over 50K BTU. This is listed on LL's website and is just below the listing for SWG 4HDs power venter
This is consistent with what my AK dealer told me today on the phone. He opened the AK PV box and looking at the installation manual it states the same 9" or 1' depending on your heater BTU's. He read me the P/N for this PV and it was Field Controls SWG 463956401.(SWG 4HDs)

I have also read that these clearances are for Direct Vent and not Power Vent, further defining a DV system as:
"sealed combustion". Aren't most coal stokers sealed combustion?

Other places I have looked were 4' horizontally to window. Is there anybody out there that has had a PV system installed at 9" or 1' from a window and had it pass inspection?

I don't really want to buy and install a SS chimney so I want to exhaust(no pun intended :D ) all other options before pursuing this chimney thing.

Thanks for any input.

Mark

 
User avatar
vtec350
Member
Posts: 303
Joined: Thu. May. 08, 2008 4:47 pm
Location: Western Mass.

Post by vtec350 » Sat. Oct. 04, 2008 8:44 pm

Mark

I have a power vent for my oil boiler and the clearances are 4' below or horizontally from any window Here's a link to SWG power vents web site. Scroll half way down and there's a diagram showing you all the clearances.

Dave

http://www.fieldcontrols.com/venting.php

 
User avatar
heatwithcoal
Member
Posts: 248
Joined: Wed. Sep. 12, 2007 9:48 pm
Location: Western Massachusetts
Hot Air Coal Stoker Furnace: AK-110

Post by heatwithcoal » Sat. Oct. 04, 2008 10:01 pm

Yes, I saw that but also was told that the same PV SWG-4HDs unit can be placed 9" or 1' away by both the AK dealer and it seemed as though is was listed that same way on the LL website.

http://www.leisurelinestoves.com/

Scroll down to where it describes the SWG power vent. Just below that it says "Planning the venting system." It is there that is states the 9" and 1'. I guess maybe the "planning your venting system" portion is not part of the SWG PV spec just above it?

Thanks for the reply Dave and
Where in Western Mass are you?

Mark

 
User avatar
Adamiscold
Member
Posts: 1116
Joined: Fri. Feb. 29, 2008 7:09 am
Location: Winchendon,Ma

Post by Adamiscold » Sun. Oct. 05, 2008 8:54 am

Mark

I see what you mean.

B#
The vent termination of a direct vent or sealed combustion
appliance with an input of 50,000 BTU's per hour or less must be
located at least 9" from any opening through which vented gases
could enter the building. With an input over 50,000 BTU's per
hour, a 1' termination clearance is required. Another term for direct
vent is sealed combustion.


C#
The venting systems with the exception of direct vent appliances,
must terminate at least 4' below, 4' horizontally, or 1' above
any door, window or gravity air inlet into the building.


I'm not sure what they are considering to be any opening through which vented gases
could enter the building.
But since it clearly states 4' below, 4' horizontally, or 1' above
any door, window
I would have to go with the 4' rule for a power-vent of any kind.


 
User avatar
vtec350
Member
Posts: 303
Joined: Thu. May. 08, 2008 4:47 pm
Location: Western Mass.

Post by vtec350 » Sun. Oct. 05, 2008 11:23 am

Adamiscold wrote:I'm not sure what they are considering to be any opening through which vented gases
could enter the building.
They might be talking about bath exhaust vents or dryer vents.

Mark, I'm just outside Springfield in Monson

 
User avatar
heatwithcoal
Member
Posts: 248
Joined: Wed. Sep. 12, 2007 9:48 pm
Location: Western Massachusetts
Hot Air Coal Stoker Furnace: AK-110

Post by heatwithcoal » Sun. Oct. 05, 2008 2:04 pm

Yeah, I am not sure, it is just strange that my dealer said that it stated 9" and 1' inside the SWG kit.
Anyways, Monson huh? You must get your energy from CSM? I am in Belchertown.

Mark

 
User avatar
maurizziot
Member
Posts: 96
Joined: Sun. Oct. 05, 2008 1:32 pm
Location: Middletown N.Y.

Post by maurizziot » Sun. Oct. 05, 2008 2:40 pm

heatwithcoal wrote:Ok, so I have looked a number of places online for horizontal clearances to a window spec. I have found:

9"horizontal clearance for stoves under 50K BTU and 1' over 50K BTU. This is listed on LL's website and is just below the listing for SWG 4HDs power venter
This is consistent with what my AK dealer told me today on the phone. He opened the AK PV box and looking at the installation manual it states the same 9" or 1' depending on your heater BTU's. He read me the P/N for this PV and it was Field Controls SWG 463956401.(SWG 4HDs)

I have also read that these clearances are for Direct Vent and not Power Vent, further defining a DV system as:
"sealed combustion". Aren't most coal stokers sealed combustion?

Other places I have looked were 4' horizontally to window. Is there anybody out there that has had a PV system installed at 9" or 1' from a window and had it pass inspection?

I don't really want to buy and install a SS chimney so I want to exhaust(no pun intended :D ) all other options before pursuing this chimney thing.

Thanks for any input.

Mark
I have a pv on my leisure line pioneer coal stove approx from 2'-0" from a double hung window. I would discuss with local municipality on deeming the windows inoperable by proving a lock feature on the window. that would affectively be a none operable window there for meeting the requirement as dictated by the IRC (Residential Code) For venting of solid fuel burning appliances

Post Reply

Return to “Coal Bins, Chimneys, CO Detectors & Thermostats”