By: LsFarm On: Sun Oct 19, 2008 10:34 am
Hi crochunisclan , what make is your stove?? [you can add this information to your signature]
If your stoker mechanism has a pusher bar or shovel, it should be moving back and forth about 1/2" or so.. If it isn't moving this much, the mechanism that moves it is either damaged, worn or very loose..
We need to know what Make and Model your stove is,, there are many differences in the stoker designs..
As for the Power vent,, first IS it a powervent?? A Powervent is a unit that is installed in the outside wall of the house... and yes, most Powevent kits come with a reostat and a barometric damper to adjust the draft that the Powervent is pulling on the stove..
Your stove could have a Direct Vent, this is a motor/fan mechanism that is attached directly to the backof your stove, and it pushes air/exhaust out a pipe to the outdoors... Even these units often have a reostat added by the owners..
But ALL Reostat equiped venters MUST use a Manometer to set and monitor the draft.. otherwise you may turn the draft [venter speed] down too low and not have enough draft in the stove and have CO leaks... So a Manometer is a must if you install a Reostat.
If you give us a bit more info or start another thread on your stove and problems we can help you better..
Greg L
.