I have been adjusting this boiler for 2 weeks and ended up with no fire in the boiler 3 times.
Right now I have the restrictor plate off.
the stoker shaft set 4.5 turns out.
time on= 4
time off=15
aquastat=170*
It has been 72* here during the day and 65* at night... so not much call for heat.
The Vf3000 is reading abou 190* all the time.... a few times I have seen it go to 195-200*
when I used the restrictor plate set at 50% The temp was lower but the ash didn't look completely burned.
with no restictor plate the coal ash looks more completely burned.
Thanks for your input
the manual says don't go less than 4 in the on mode, if i set it to 3 the fire goes out.
Is this as good as it gets?
do I need to add a low speed blower when in off mode?
