My EFM has been running for a couple of weeks. This weekend I should have my last cast iron radiator repaired. I put valves in the zone plumbing so I can isolate that loop without dropping the system pressure. Do I need to shut the boiler off long enough to let the water cool to fill the radiator and purge the zone?


 
Bob
Member
Posts: 304
Joined: Sun. Mar. 18, 2007 11:28 am
Location: Schuylkill County
Stoker Coal Boiler: AHS 130
Coal Size/Type: Pea/Anthracite

Post by Bob » Tue. Oct. 21, 2008 7:23 pm

No.

In fact gasses can only be fully purged from the system by heating the water in the system.