User avatar
StanT
Member
Posts: 261
Joined: Fri. Aug. 29, 2008 5:10 am
Location: Ne Pa

Post by StanT » Mon. Nov. 03, 2008 6:26 pm

Fired it up today, temp set 170 10 offset, went right up to 150 and shut off, could the temp gauge be off this much? Also how do you have the restrictor plate on the blower set?

Thanks, Stan

 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Mon. Nov. 03, 2008 7:15 pm

What's it got for an aquastat? If it's a triple, it sounds like the T-stat terminals do not have a jumper wire.....or it has a thermostat on the wall that is not calling for heat.


 
User avatar
StanT
Member
Posts: 261
Joined: Fri. Aug. 29, 2008 5:10 am
Location: Ne Pa

Post by StanT » Mon. Nov. 03, 2008 7:52 pm

theromostat was not calling for heat but aquastat was set at 170
Stan

 
User avatar
Freddy
Member
Posts: 7301
Joined: Fri. Apr. 11, 2008 2:54 pm
Location: Orrington, Maine
Stoker Coal Boiler: Axeman Anderson 130 (pea)
Coal Size/Type: Pea size, Superior, deep mined

Post by Freddy » Mon. Nov. 03, 2008 8:12 pm

That's why I asked what kind of aquastat. If it's a triple aquastat and the low is set at 150 and the high at 170, it will not go to 170 unless the thermostat is constantly calling for heat. To answer your original question, I have seem many gauges that were 10 degrees off. Aquastats seem to be more accurate.